centralita de relés de protección diferencial cbs- 4c ra...

4
Código code Tipo Type Sensibilidad (A) Sensivity Retardo disparo (s) Tripping delay Comunicaciones Communications P24912 CBS-4C RA 0,03-0,1-0,3-0,5-1-3 por ajuste directo by direct setting 5-10-30 por/ SETUP by INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1 por ajuste directo / by direct setting 3-5-10 por/ SETUP by No disponible Not available P X X X X 0 0 X Código Code Código interno Internal code Tensión de alimentación Power supply 230 V a.c. 110 V a.c. 0 1 Centralita de relés de protección diferencial CBS- 4C RA con reconexión automática Multipoint earth leakage relay CBS- 4C RA Self-reclosing Por ejemplo CBS-4C RA alimentada a 110 V c.a / . For example CBS - 4C RA 110 V a.c.. supplied by DESCRIPCIÓN GENERAL DESCRIPCIÓN DE LOS LED Y PULSADORES. - Dispositivo con 4 relés diferenciales independientes y programables. 4 canales de disparo. - Dispone de 5 salidas. 4 para disparo por relé y la de señalización bloqueo por reconexiones. - Sólo usar con elementos de corte donde la bobina de disparo puede rearmar (CONTACTOR). - Dispone de 1 entrada para realizar un Disparo/Rearme externo. - Montaje en Carril DIN 46277 (EN 50022) o en panel 72x72 mediante accesorio (M5ZZF1) - Asociado a transformador de corriente diferencial externo serie / . - Comprueba conexión con transformador exterior mediante test inductivo. - La detección y medida de la fuga se realiza calculando su verdadero valor eficaz (TRMS). - Visualización por display de los valores de ajuste y de la corriente diferencial instantánea - Indicación del estado del equipo mediante display y 2 LED. - Ajuste y programación del equipo mediante 5 pulsadores. - Operaciones de TEST y RESET del equipo mediante 2 pulsadores. WG WGS WG/WGS - - . INDICACIONES POR LED Y DISPLAY. RECONEXIÓN DEL EQUIPO. AJUSTES Y VISUALIZACIÓN DE CANAL AJUSTES PARÁMETROS CANAL AJUSTES POR SETUP - Señaliza por un cambio de estado de color verde a rojo, tanto del LED como del display. Se visualizan los mensajes o valores concernientes al tipo de evento y en el canal que se produce. . LED amarillo parpadeando. . LED amarillo fijo cuando se llega al número máximo de reconexiones automáticas establecidas en la secuencia de reconexión. - POR 1. Realizar un manual en el canal disparado o enclavado. 2. Realizar una señal de rearme remota (telemando). , . Al pulsar la tecla aparece en pantalla el mensaje y dos valores. El más pequeño indica el valor actual configurado y en el más grande los valores a configurar que debemos ir visualizando pulsando . Visualizado el valor escogido se espera a que el equipo valide el valor como configurado mostrando el mensaje de SAVE. . Al pulsar la tecla realizamos la operación con el mismo modus operandi que el anterior ajuste. El valor indica la inhabilitación de canal por ausencia de transformador diferencial. . Al pulsar esta tecla seleccionamos variamos la polaridad de los contactos de disparo NA/NC. (Std) aparece sólo (NA) - (+) aparece (NC) . Pulsando la tecla podemos ir variando secuencialmente la características de reconexión (SREC) en el canal que estamos visualizando. La secuencia OFF inhabilita reconexión y desaparece. Por pulsación larga en En este modo de funcionamiento mediante los pulsadores y nos iremos desplazándo y variando valores de configuración del equipo por los diferentes submenús de programación. DISPARO RELÉ POR CANAL. DISPARO ENTRE RECONEXIONES SEÑALIZACIÓN ENCLAVAMIENTO DISPARO / ENCLAVAMIENTO DE RECONEXIONES RESET - AJUSTE DEL RETARDO DE DISPARO - AJUSTE DE LA SENSIBILIDAD, OFF - AJUSTE DE CONTACTOS, std/+ NO NO + - SECUENCIAS DE RECONEXIÓN, REC PROG - Para escoger el canal de los 4 a ajustar se realiza mediante pulsación corta de la tecla PROG. Se indica en la esquina inferior derecha el número de canal. ( , y std/+ ) t I d d t t I d d d I d PROG activamos el menú de programación . - LED VERDE: Equipo encendido / - LED ROJO: Disparo por fuga / - LED AMARILLO: Fijo-Bloqueo Nº Reconexiones / Temporiza entre reconexiones - PULSADOR RESET / - PULSADOR TEST / GREEN LED: Equipment on RED LED: Leakage trip YELLOW LED: Fixed, Locked by reclosures. Blinked, waiting for self-reclosing RESET BUTTON TEST BUTTON Causa del disparo Mensaje display Test Señal remota ON/OFF Fuga de corriente TESt EXT valor instantáneo PROG PROG RGU - 10 C Con el pulsador navegamos por los submenús y con el pulsador vamos visualizando los valores a escoger. Para validar el valor tenemos que pulsar . PROG PROG Otros MENSAJES por display SAVE EXIT OVR ERRt Valida valores de configuración. Sale fuera modo programación. Lectura del valor fuera de escala. Mala conexión con toroidal M98205001-20-09A P2491201 GENERAL VISUALITZACION AND SETTING CHANNELS - . - . - . - . - BY - , . t . SAVE. . . The OFF value configure the channel is disable. . . You can choose the self-reclosing sequence (SREC) by pushing . - . LOCKED BY RECLOSURES TRIP / LOCKED RECLOSURES - , - CONTACTS RELAY , std/+ - Auto - By short press on PROG every channel and his adjustment parameters is displayed. ( , and std/+ ) t I d d t I I d d d d DESCRIPTION DESCRIPTION LED AND BUTTONS INDICATION BY LED AND DISPLAY RECLOSING THE EQUIPMENT RELAY CHANNEL PARAMETER SETTING Device with 4 independent and programmable differential relays. 4 tripping channels. - It has 5 outputs. 4 trip relays and locked by reclosures signal relay. - Only use with circuit breaker with reclosing coil. - It has one input for external Trip/Reclose. - Mounting in DIN rail 46277 (EN 50022) or PANEL 72x72 by means accesories M5ZFF1. - Associated to a Series external, toroidal current transformer. - It verifies connection with external transformer by inductive tests. - Leakage detection and measurement is via calculating its true effective value (TRMS). - Displays setting values and instant current different to its associated units Shows equipment status via a display and 2 LED's. - 5 button equipment setup and setting. - 2 button equipment TEST and RESET LED and display signals a change of status by changing from green to red. Display event type messages or values The yellow LED is blinking. The yellow LED is fixed when the the equipment arrive at maximun No od reclosures established by self-reclosing sequence. 1. Manual reclose by pushing button . 2. External reclose by remote signal. The message and two values appear on the screen after pressing the button. The lowest value indicates the current set value and the highest is the values to be configured which are displayed by pressing The selected value to be saved is displayed by showing the message The same operation as above setting is carried out by pressing To change the trip contact polarity is selected by pressing this button. (Std) appears on the display and (+) NC). this button. When SREC is OFF the symbol disappear and the self-reclosing sytem is disable. WG/WGS WG/WGS TRIP CHANNEL RELAY BETWEN RECLOSURES. RESET SETTING TRIP DELAY SENSITIVITY SETTING SETTING NO NO + ( SETTING OF SELF-RECLOSING SEQUENCE, Cause of trip Message display Test Remote signal ON/OFF Current leakage TESt EXT instant value PROG REC Other display MESSAGES SAVE EXIT OVR ERRt Enters setting values Exits setting mode Current leakage reading off scale Poor toroidal connection -AJUSTE RETARDO / - AJUSTE SENSIBILIDAD / - CONTACTOS SALIDA/ OUTPUT CONTACTS - -AJUSTE RECONEXIÓN / SELF-RECLOSING DELAY SETTING - / SETUPROTATION SENSITIVITY SETTING SETTING ROTACIÓN MENÚ SETUP SELECCIÓN VALORES EN PROGRAMACIÓN / VALUES SELECTION SETTING - PROGRAMACIÓN POR SETUP / - PROGRAMACIÓN PREALARMA / SETTING BY SETUP PROGRAMMING SETTING BY PREALARM PROGRAMMING AUTO Id CBS - 4 RA 1 NO Pulsador Pulsador PROG FREC LIM Pulsador 50 Hz 60 Hz 10 s, 30 A 1 s, 3A + + REC El equipo configura el valor visualizando ” por display y sale fuera del modo de programación. Si transcurre un cierto tiempo con el teclado inactivo el equipo automáticamente sale del modo de programación visualizando “ ” por display sin cambiar la configuración. SAVE EXIT PROG button . With the button the submenus are browsed and with the button the values to be selected are displayed PROG button PROG button FREC LIM 50 Hz 60 Hz 10 s, 30 A 1 s, 3A SETUP A . SETTINGS long press on activates the setting menu . Using the and buttons in this operating mode moves and changes the preset equipment values in the different setting submenus PROG PROG Press . . SAVE EXIT PROG to enter the value. The equipment configures the value by displaying on the display and then exits Setting Mode If the keypad remains inactive for a certain time, the equipment automatically exits Setting Mode and displays without changing the setting REC REC NO 1 CBS - 4 RA SREC NºRECONEXIONES SECUENCIA TIEMPOS/ TIEMPO DE RESET TIME SEQUENCE OFF Se inhabilita la reconexión / self-reclosing disable 1 6 8, 16, 30, 59, 115 y 224 s 15 min. 2 30 20, 40 s y 5 min.el resto / 15 min. 3 8 30 s, 1, 2, 3, 4, 5, 6 y 7 min. 15 min. 4 6 10, 20, 30, 60, 130 y 600 s 15 min. 5 6 2, 4 y 8 min. el resto / 15 min. 6 7 30 s, 1, 2, 3, 4, 8 y 16 min. 30 min. 7 10 1 min. 30 min. 8 10 90 s 30 min. 9 8 2, 4 y 6 min. el resto 15 min. 10 3 min. 30 min. 11 10 1 min. 60 min. to the end to the end / to the end 10 12 10 90 s 60 min No RECLOSURES RESET TIME REC REC 2

Upload: others

Post on 17-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Centralita de relés de protección diferencial CBS- 4C RA ...docs.circutor.com/docs/M98205001-20.pdf · esquemas de conexiÓn / connection diagram cbs-4c ra + wg/wgs marcado de bornes

Códigocode

TipoType

Sensibilidad (A)Sensivity

Retardo disparo (s)Tripping delay

ComunicacionesCommunications

P24912 CBS-4C RA

0,03-0,1-0,3-0,5-1-3por ajuste directo

by direct setting

5-10-30 por/ SETUPby

INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1por ajuste directo / by direct setting

3-5-10 por/ SETUPby

No disponibleNot available

P X X X X 0 0 XCódigoCode

Código internoInternal code

Tensión dealimentaciónPower supply

230 V a.c.

110 V a.c.

0

1

Centralita de relés de protección diferencial CBS- 4C RA con reconexión automáticaMultipoint earth leakage relay CBS- 4C RA Self-reclosing

Por ejemplo CBS-4C RA alimentada a 110 V c.a / .For example CBS - 4C RA 110 V a.c..supplied by

DESCRIPCIÓN GENERAL

DESCRIPCIÓN DE LOS LED Y PULSADORES.

- Dispositivo con 4 relés diferenciales independientes y programables. 4 canales de disparo.- Dispone de 5 salidas. 4 para disparo por relé y la de señalización bloqueo por reconexiones.- Sólo usar con elementos de corte donde la bobina de disparo puede rearmar (CONTACTOR).- Dispone de 1 entrada para realizar un Disparo/Rearme externo.- Montaje en Carril DIN 46277 (EN 50022) o en panel 72x72 mediante accesorio (M5ZZF1)- Asociado a transformador de corriente diferencial externo serie / .- Comprueba conexión con transformador exterior mediante test inductivo.- La detección y medida de la fuga se realiza calculando su verdadero valor eficaz (TRMS).- Visualización por display de los valores de ajuste y de la corriente diferencial instantánea

- Indicación del estado del equipo mediante display y 2 LED.- Ajuste y programación del equipo mediante 5 pulsadores.- Operaciones de TEST y RESET del equipo mediante 2 pulsadores.

WG WGSWG/WGS

-

-

.

INDICACIONES POR LED Y DISPLAY.

RECONEXIÓN DEL EQUIPO.

AJUSTES Y VISUALIZACIÓN DE CANAL

AJUSTES PARÁMETROS CANAL

AJUSTES POR SETUP

- Señaliza por un cambiode estado de color verde a rojo, tanto del LED comodel display. Se visualizan los mensajes o valoresconcernientes al tipo de evento y en el canal que seproduce.

. LED amarilloparpadeando.

. LED amarillo fijo cuando se llega al número máximo dereconexiones automáticas establecidas en la secuencia de reconexión.

- POR1. Realizar un manual en el canal disparado o enclavado.2. Realizar una señal de rearme remota (telemando).

, . Al pulsar la tecla aparece en pantalla el mensajey dos valores. El más pequeño indica el valor actual configurado y en el más grande los

valores a configurar que debemos ir visualizando pulsando . Visualizado el valor escogidose espera a que el equipo valide el valor como configurado mostrando el mensaje de SAVE.

. Al pulsar la tecla realizamos la operación con el mismomodus operandi que el anterior ajuste. El valor indica la inhabilitación de canal por ausenciade transformador diferencial.

. Al pulsar esta tecla seleccionamos variamos la polaridad delos contactos de disparo NA/NC. (Std) aparece sólo (NA) - (+) aparece (NC)

. Pulsando la tecla podemos ir variando secuencialmentela características de reconexión (SREC) en el canal que estamos visualizando. La secuencia OFFinhabilita reconexión y desaparece.

Por pulsación larga enEn este modo de

funcionamiento mediante los pulsadores ynos iremos desplazándo y variando valores de

configuración del equipo por los diferentessubmenús de programación.

DISPARO RELÉ POR CANAL.

DISPARO ENTRE RECONEXIONES

SEÑALIZACIÓN ENCLAVAMIENTO

DISPARO / ENCLAVAMIENTO DE RECONEXIONESRESET

- AJUSTE DEL RETARDO DE DISPARO

- AJUSTE DE LA SENSIBILIDAD,OFF

- AJUSTE DE CONTACTOS, std/+NO NO +

- SECUENCIAS DE RECONEXIÓN, REC

PROG

- Para escoger el canal de los 4 a ajustar se realiza mediante pulsación corta de latecla PROG. Se indica en la esquina inferior derecha el número de canal.

( , y std/+ )t Id d

t t

I

d d

dId

PROG activamos el menúde programación .

- LED VERDE: Equipo encendido /- LED ROJO: Disparo por fuga /

- LED AMARILLO: Fijo-Bloqueo Nº Reconexiones / Temporiza entre reconexiones

- PULSADOR RESET /

- PULSADOR TEST /

GREEN LED: Equipment onRED LED: Leakage trip

YELLOW LED: Fixed, Locked by reclosures. Blinked, waiting for self-reclosingRESET BUTTON

TEST BUTTON

Causa del disparo Mensaje display

TestSeñal remota ON/OFFFuga de corriente

TEStEXTvalor instantáneo

PROG

PROG

RG

U -

10

C

Con el pulsador navegamos por los submenúsy con el pulsador vamos visualizando los valores aescoger. Para validar el valor tenemos que pulsar

.

PROG

PROG

Otros MENSAJES por displaySAVEEXITOVRERRt

Valida valores de configuración.Sale fuera modo programación.Lectura del valor fuera de escala.Mala conexión con toroidal

M98205001-20-09A

P2491201

GENERAL

VISUALITZACION AND SETTING CHANNELS

-

.

-

.

- .

- .

- BY

- , .t

.SAVE.

. .The OFF value configure the channel is disable.

.

. You can choose the self-reclosingsequence (SREC) by pushing

.

- .

LOCKED BY RECLOSURES

TRIP / LOCKED RECLOSURES

- ,

- CONTACTS RELAY , std/+

- Auto

- By short press on PROG every channel and his adjustment parameters isdisplayed.

( , and std/+ )t Id d

t

I I

d

d

dd

DESCRIPTION

DESCRIPTION LED AND BUTTONS

INDICATION BY LED AND DISPLAY

RECLOSING THE EQUIPMENT

RELAY CHANNEL PARAMETER SETTING

Device with 4 independent and programmable differential relays. 4 tripping channels.- It has 5 outputs. 4 trip relays and locked by reclosures signal relay.- Only use with circuit breaker with reclosing coil.- It has one input for external Trip/Reclose.- Mounting in DIN rail 46277 (EN 50022) or PANEL 72x72 by means accesories M5ZFF1.- Associated to a Series external, toroidal current transformer.- It verifies connection with external transformer by inductive tests.- Leakage detection and measurement is via calculating its true effective value (TRMS).- Displays setting values and instant current different to its associated units

Shows equipment status via a display and 2 LED's.- 5 button equipment setup and setting.- 2 button equipment TEST and RESET

LED and displaysignals a change of status by changing fromgreen to red. Display event type messages orvalues

The yellow LED isblinking.

The yellow LED is fixed when the the equipment arrive atmaximun No od reclosures established by self-reclosing sequence.

1. Manual reclose by pushing button .2. External reclose by remote signal.

The message and two values appear on the screen afterpressing the button. The lowest value indicates the current set value and the highest is thevalues to be configured which are displayed by pressing The selected value to be savedis displayed by showing the message

The same operation as above setting is carried out by pressing

To change the trip contact polarity is selected bypressing this button. (Std) appears on the display and (+) NC).

this button. When SREC is OFF the symbol disappearand the self-reclosing sytem is disable.

WG/WGSWG/WGS

TRIP CHANNEL RELAY

BETWEN RECLOSURES.

RESET

SETTING TRIP DELAY

SENSITIVITY SETTING

SETTINGNO NO + (

SETTING OF SELF-RECLOSING SEQUENCE,

Cause of trip Message displayTestRemote signal ON/OFFCurrent leakage

TEStEXTinstant value

PROG

REC

Other display MESSAGESSAVEEXITOVRERRt

Enters setting valuesExits setting modeCurrent leakage reading off scalePoor toroidal connection

-AJUSTE RETARDO /

-AJUSTE SENSIBILIDAD /

- CONTACTOS SALIDA/ OUTPUT CONTACTS

- -AJUSTE RECONEXIÓN / SELF-RECLOSING

DELAY SETTING- / SETUPROTATION

SENSITIVITY SETTING

SETTING

ROTACIÓN MENÚ SETUP

SELECCIÓN VALORES EN PROGRAMACIÓN / VALUES SELECTION SETTING

- PROGRAMACIÓN POR SETUP /- PROGRAMACIÓN PREALARMA /

SETTING BY SETUP PROGRAMMINGSETTING BY PREALARM PROGRAMMING

AUTO

Id

CBS - 4 RA

1NO

Puls

ador

Pulsador PROG

FREC

LIM

Puls

ador50 Hz

60 Hz

10 s, 30 A

1 s, 3 A

+

+

REC

El equipo configura el valor visualizando “ ” por display y sale fuera del modo deprogramación. Si transcurre un cierto tiempo con el teclado inactivo el equipoautomáticamente sale del modo de programación visualizando “ ” por display sincambiar la configuración.

SAVE

EXIT

PROG

button

.

With the button the submenus are browsedand with the button the values to be selectedare displayed

PROG

button

PROG button

FREC

LIM

50 Hz

60 Hz

10 s, 30 A

1 s, 3 A

SETUPA

.

SETTINGSlong press on activates the setting

menu . Using the andbuttons in this operating mode movesand changes the preset equipmentvalues in the different setting submenus

PROGPROG

Press“ ” .

“ ” .

SAVE

EXIT

PROG to enter the value. The equipment configures the value bydisplaying on the display and then exits Setting Mode If the keypadremains inactive for a certain time, the equipment automatically exits SettingMode and displays without changing the setting

REC

RECNO 1

CBS - 4 RA

SREC NºRECONEXIONES SECUENCIA TIEMPOS/ TIEMPO DE RESETTIME SEQUENCE

OFF Se inhabilita la reconexión / self-reclosing disable1 6 8, 16, 30, 59, 115 y 224 s 15 min.2 30 20, 40 s y 5 min.el resto / 15 min.3 8 30 s, 1, 2, 3, 4, 5, 6 y 7 min. 15 min.4 6 10, 20, 30, 60, 130 y 600 s 15 min.5 6 2, 4 y 8 min. el resto / 15 min.6 7 30 s, 1, 2, 3, 4, 8 y 16 min. 30 min.7 10 1 min. 30 min.8 10 90 s 30 min.9 8 2, 4 y 6 min. el resto 15 min.

10 3 min. 30 min.11 10 1 min. 60 min.

to the end

to the end

/ to the end10

12 10 90 s 60 min

No RECLOSURES RESET TIME

REC

REC

2

Page 2: Centralita de relés de protección diferencial CBS- 4C RA ...docs.circutor.com/docs/M98205001-20.pdf · esquemas de conexiÓn / connection diagram cbs-4c ra + wg/wgs marcado de bornes

ESQUEMAS DE CONEXIÓN / CONNECTION DIAGRAM CBS-4C RA + WG/WGS

MARCADO DE BORNES /TERMINALCONNECTIONS DESIGNATIONS

DIMENSIONESDIMENSIONS

45

52,5 43,5

85

67,9

Fijación carril DIN 46277 (EN 50022)

M98205001-20-09A

CARACTERÍSTICAS TÉCNICAS- Tipo de relé: Electrónico, clase A. Filtrado de corriente de alta frecuencia.- Tipo de reconexión: Manual, mediante pulsador de RESET o corte de alimentación.- Tensión de alimentación nominal: 230 o 110 V c.a. (+/- 20%) 50/60 Hz, 6 V·A

- Temperatura de trabajo: -10 / +50 ºC- Conexionado:Sección cable permitida: 0,127 - 2,082 mmPar de apriete recomendado: 0,5-0,6 N.mLongitud de cable a desaislar: 7 mmDestornilladores recomendado: Varilla: 0,4 x 2,5 x 80 mm, longitud 160 mm

- Características contactos conmutados de salida 13-14-15 y 7-8-9.Corriente Nominal/Máxima corriente instantánea: 6/10 A c.a.Tensión Nominal: 230V c.a.Carga Nominal en AC: 2 500 V·AContactos protegidos por varistor.

- Características varistorTensión máxima : 275 V c.a

- Características entrada de disparo/rearme externo 10-12Entrada optoacopladaTensión máxima : 230 V c.a. ; 0,7 W

2

TECHNICAL FEATURESRelay type: Electronic class A. High frequency current filtering.

- Reclosing type: Manual via RESET button or by cutting power supply.- Rated power supply voltage

Operating temperatureConnections

Recommended tightening torque: 0.5-0.6 NmLength of cable to strip: 7 mmRecommended screwdrivers length

Switch Output contact featuresRated current/Maximum instant currentRated voltage/Maximum switching voltageRated load in

Permissible cable section:

- Features varistorsMaximum operating voltage: 275 V a.c.

- Trip/reclose input features external 10-12Input Opto-coupledMaximum voltage: 230 V a.c.; 0,7 W

- Tipo

: 230 o 110 Va.c. (+/- 20%) 50/60 Hz, 6 VA

- : -10ºC / 50ºC- :

: Bar 0.4 x 2.5 x 80 mm, 160 mm

- 13-14-15 and 7-8-9.: 6/10 A a.c.

: 250/230 V a.c.AC: 2,500 V·A

Contacts protected by varistor

0,127 - 2,082 mm2

ALIMENTACIÓN C.A. / SUPPLY A.C.

Poder de corte para cargas DC:Corriente máxima de apertura. (Ver gráfico adjunto)

Vida útil eléctrica para cargas AC: Nº de ciclos.(Ver gráfico adjunto)

Electrical useful life for AC loads o. of cycles.(See graph

: N)

Maximun DC Load Breaking Capacity:Maximum opening current. (See graph)

1

10 11

4 5 6

13 14 15

Reset

Test

12

CBS-4

987

Type WG

1S11S2

2 3

T4

Type WG

1S2

T4

Type WG

T3

Type WG

1S11S2

T4

Type WG

T2

Type WG

T1

L N

1S1

1S2

1S2

1S1

1S2

1S1

ON / OFF externoExternal ON/OFF

SE

ÑA

LIZ

AC

IÓN

BLO

QU

EO

PO

RR

EC

ON

EX

ION

ES

1

10 11

4 5 6

13 14 15

Reset

Test

12

CBS-4

9872 3

L N230 Vc.a.

NL1 L2 L3

UTILIZACIÓN

1S1

1S2

USE

Type

WG

1S1

1S2

NL1 L2 L3

UTILIZACIÓN

1S1

1S2

USE

Type

WG

1S1

1S2

NL1 L2 L3

UTILIZACIÓN

1S1

1S2

USE

Type

WG

1S1

1S2

NL1 L2 L3

UTILIZACIÓN

1S1

1S2

USE

Type

WG

1S1

1S2

T1

T2

T3

T4

Disparo por BOBINA DE MÍNIMATrip by UNDERVOLTAGE COIL

CONTACTOS DISPARO/ TRIPPING CONTACTS

SALIDA NA /

SALIDA COMÚN/

SALIDA NA /

OUTPUT NO

COMMON OUTPUT

OUTPUT NO

13

14

15

SALIDA NA /

SALIDA COMÚN /

SALIDA NA /

OUTPUT NO

COMMON OUTPUT

OUTPUT NO

7

8

9

TRANSFORMADOR DIFERENCIAL/ CORE BALANCE

ENTRADA 1S2 COMÚN /

ENTRADA 1S1-T4 /

COMMON INPUT 1S2

INPUT 1S1- T4

2

3

ENTRADA DISPARO/REARME EXTERNAEXTERNAL TRIP/RECLOSE

ENTRADA TENSIÓN / INPUT VOLTAGE10 12

10

ALIMENTACIÓN / POWER SUPPLY

ALIMENTACIÓN / (A1)

ALIMENTACIÓN / (A2)

SUPPLY

SUPPLY11

4

5

6

ENTRADA 1S1-T3 / INPUT 1S1- T3

ENTRADA 1S1-T2 / INPUT 1S1- T2

ENTRADA 1S1-T1 / INPUT 1S1- T1

13 14- RELÉ PROTECCIÓN TOROIDAL T1

15 14- RELÉ PROTECCIÓN TOROIDAL T2

7 8- RELÉ PROTECCIÓN TOROIDAL T3

9 8- RELÉ PROTECCIÓN TOROIDAL T4

1S1

Centralita de relés de protección diferencial CBS- 4C RA con reconexión automáticaMultipoint earth leakage relay CBS- 4C RA Self-reclosing

Page 3: Centralita de relés de protección diferencial CBS- 4C RA ...docs.circutor.com/docs/M98205001-20.pdf · esquemas de conexiÓn / connection diagram cbs-4c ra + wg/wgs marcado de bornes

AUTOAJUSTE SENSIBILIDAD/ SENSIVITY SETTING

POLARIDAD CONTACTOSCONTACTS POLARITIES

AJUSTE SECUENCIAS DE RECONEXIÓNSETTING SELF-RECLOSING SEQUENCES

PROGRAMACIÓN POR SETUP- Comunicaciones (CBS-4C RA)- Frecuencia 50/60 Hz- Escala Valores Corriente y tiempo

CAMBIO DE CANAL

0,03-0,1-0,3-0,5-1-3-5-10-30 A

ROTACIÓN MENÚ SETUPROTATIONAL BUTTON SETUP

AJUSTE RETARDO/DELAY SETTING

0,02-0,1-0,2-0,3-0,4-0,75-1-3-5-10 sCurva Inversa INS-SEL

Id

LED VERDE: Equipo encendidoLED ROJO: Disparo por fuga

LED AMARILLO: Fijo, Enclavamiento por reconexiones.Parpadeando, Temporizando entre reconexiones

YELLOW LED: Fixed, Locked by reclosures.Blinking, waiting betwen reclosures.

PULSADOR RESET

PULSADOR TEST

BUTTON RESET

BUTTON TEST

CORRIENTE DE AJUSTE, I ND

TRIPPING CURRENT TRESHOLD

TIEMPO DE AJUSTE, tdDELAY TIME

VALOR INSTANTÁNEO DE FUGAINSTANT LEAKAGE CURRENT VALUE

GREEN LED: Equipment ONRED LED: Leakage trip

SETUP SETTINGS- Communications (CBS-4C RA)- Frecuency 50/60 Hz- Range values current / time delay.

CHANGE CHANNEL

CBS - 4 RA

1NO

CBS - 4

1NO

CBS - 4 RA

1NO

C A N A LCHANNEL

M98205001-20-09A

Centralita de relés de protección diferencial CBS- 4C RA con reconexión automáticaMultipoint earth leakage relay CBS- 4C RA Self-reclosing

mS mA

mA

CBS - 4 RA

1NO

NO 1

mS mA

mANO 1

FF

AJUSTE SECUENCIAS DE RECONEXIÓN POR CANALSETTING SELF-RECLOSING SEQUENCES PER CHANNEL

REC

REC

REC

REC

REC

REC

COMUNICACIONES- Uno o varias CBS-4C RA pueden conectarse a un ordenador o PLC mediante conexiónSerie RS-485.- La comunicación es a través de protocolo MODBUS RTU. Bits, 8. Stop, 1.- Las comunicaciones con el equipo se señalizan en el display por el símbolo COMM

COMMUNICATIONS- One or more CBS-4C Ra’s can be connected to a computer or PLC using an RS-485connection.- Communication is via the MODBUS RTU protocol. Bits, 8. Stop, 1.- Communication with the equipment is shown on the display by the symbol.COMM

0000h Número de periférico / Peripherical number 1 - 99 -0001h Velocidad de comunicaciones/Communication baud rate 2 400 (0h)-4 800(1h)-9 600(2h)-19 200(3h)-38 400(4h)-57 600(5h)-115 200(6h) Bauds0002h Paridad / Parity None (0h) - Odd (1h) - Even (2h) -0003h Frecuencia de tra uency 50 - 60 Hz0004h Co0005h Corriente de disparo annel 20006h Corriente de disparo channel 3 0,03(1h)-0,1(2h)-0,3(3h)- 0,5(4h)-1(5h)-3(6h)-5(7h)-10(8h)-30(9h) A0007h Corriente de disparo canal hannel 40008h Tiempo de retardo canal 1 / Tripping delay time channel 10009h Tiempo de retardo canal 2 / Tripping delay time channel 2 INS(0h)-SEL(1h)-0,02(2h)-0,1(3h)-0,2(4h)-0,3(5h) s000Ah Tiempo de retardo canal 3 / Tripingp delay time channel 3 0,4(6h)-0,5(7h)-0,75(8h)-1(9h)-3(10h)-5(11h)-10(12h000Bh Tiempo de retardo canal 4 / Tripping delay time channel 4000Ch Modo trabajo Salidas relé / Output relay operating mode 0-Canales no señalización/no signal channels 1-Señalización canal 1/signaling channel 1

2-Señalización canal 2/signaling channel 2 3-Señalización canal 3/signaling channel 34-Señalización canal 4/signaling channel 4

bajo / freqrriente de disparo canal 1/ 1

canal 2/ chcanal 3/

4/ c

OperatingTrip current channelTrip currentTrip currentTrip current

000Dh Polaridad salida relé / Relay Output polarity Canal1/Channel1: 0000h (NO) 0001h (NC)

000Eh Corriente disparo pre-alarma/ Prealarm trip current 0-OFF 1-50 2-60 3-70 4-80 5-MAIN %

Canal2/Channel2: 0000h (NO) 0002h (NC)Canal3/Channel3: 0000h (NO) 0003h (NC) Canal4/Channel4: 0000h (NO) 0004h (NC)

-0019h Estado Relés / Relays state Off -0x00 On Trip relay - 0x01:Channel1 0x02:Channel2 0x03:Chanel3 0x04:Channel4001Ah Valor eficaz corriente fuga c1/ TRMS leakage current value ch1001Bh Valor eficaz corriente fuga c2/ TRMS leakage current value ch2001Ch Valor eficaz corriente fuga c3/ TRMS leakage current value ch3001Dh Valor eficaz corriente fuga c4/ TRMS leakage current value ch4001Eh Valor eficaz corriente disparo c1/ TRMS tripping current value ch1 0 (0h) - 65.000 (FFFFh) mA001Fh Valor eficaz corriente disparo c2/ TRMS tripping current value ch20020h Valor eficaz corriente disparo c3/ TRMS tripping current value ch30021h Valor eficaz corriente disparo c4/ TRMS tripping current value ch40022h Inhabilitar canal / Disable channel Reset - 0001h:1 0002h:2 0003h:3 0004h:4 Trip - 0100h:1 0200h:2 0400h:3 0800h:40023h Habilitar grabación configuraciónl / Enable configuration save 0000h - habilitar/enable FFFFh - Grabar/save000Fh Secuencia de reconexion del canal 1 0-OFF,1-secuencia1,2-Sec.2, ,,, 12-Sec 120010h Secuencia de reconexion del canal 2 0-OFF,1-secuencia1,2-Sec.2, ,,, 12-Sec 120011h Secuencia de reconexion del canal 3 0-OFF,1-secuencia1,2-Sec.2, ,,, 12-Sec 120012h Secuencia de reconexion del canal 4 0-OFF,1-secuencia1,2-Sec.2, ,,, 12-Sec 12

R/WR/WR/WR/W

Dirección Descripción Valores Unidades Lectura & EscrituraAddress Description Values Units Read/ Write

W

R/WR

W

R

R/W

R/W

R/W

R/W

R/WR/WR/WR/W

EJEMPLO/EXAMPLE: Escritura 0,03 A Id en canal 1 / Writing 0,03 A Id inthe channel 1

1-Habilitar/enable

TX: NP 0600230000

2-Introducir In / Introducing In

TX: NP 0600040001

3- Grabar/save

TX: NP 060023FFFF

06 Función de Escritura/ Function0023 Registro/ Register0000 Habilitar/enable

Writing

06 Función de Escritura/ Function0004 Registro/ Register0001 0,03 A

Writing

06 Función de Escritura/ Function0023 Registro/ RegisterFFFF Gravar/save

Writing

EJEMPLO/EXAMPLE: Leer Id en canal 1 / Reading Id in the channel 1

2- Leer In / Reading In

TX: NP 0300040001

3- Respuesta / Answer

RX: NP 03020001

03 Función de Lectura/ Reading Function0004 Registro/ Register0001 Numero de registros a leer / Number of registers to read

03 Función de Lectura/ Reading Function02 Numero de Bytes recibidos/ Number of bytes received0001 0,03 A

Page 4: Centralita de relés de protección diferencial CBS- 4C RA ...docs.circutor.com/docs/M98205001-20.pdf · esquemas de conexiÓn / connection diagram cbs-4c ra + wg/wgs marcado de bornes

Centralita de relés de protección diferencial CBS- 4C RA con reconexión automáticaMultipoint earth leakage relay CBS- 4C RA Self-reclosing

A1

A2

RS-232

7 5

2 3

5

2

7

25 1

CONVERSOR /RS-232 / RS-485

INTELLIGENT CONVERTER

RS-485

Id

AUTO

10 11 12 13 14 15

1 2 3 4 5 6 7 8 9

5

1

2

A(+)

B(-)S(GND)

CONEXIÓN POR COMUNICACIÓNCONNECTION FOR COMMUNICATIONS

PC

CVMk

CBS-4C RA tiene conexión de salida RS-485 para comunicaciones serie.CBS-4C RA has a RS-485 series communications output.

M98205001-20-09A

Vial Sant Jordi s/n08232 Viladecavalls (Bacelona) SPAINTel: (+34) 93 745 29 00Fax: (+34) 93 745 29 14

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

mS mA

mA

PROG

td

td

td

td

PROG

PROG

PROG

PROG

PROG PROG

PROG PROG

PROG

PROG

td

tdtd

td tdtdtd

tdtd

PROG

mAmA

GUARDA CAMBIOS

SALIR SETUP

SAVE CHANGES

EXIT SETUP

MENU SETUP / SETUP MENU