  • ANSUL line proportioners are designed to introduce a controlled flow offoam concentrate into a pressurized water stream. They provide an inex-pensive foam proportioning means for systems requiring fixed flow ratesand where available water supply pressures are adequate. Dependingon specific foam systems design, line proportioners may operate withinlet pressures as low as 80 psi (552 kPa). However, in most systems awater pressure between 125 psi and 200 psi (862 and 1379 kPa) isrequired. The flow rate and operating pressure required at the foammaking device are of primary importance in determining the requiredline proportioner inlet pressure. The line proportioner must match theflow rate of the foam making discharge device.ANSUL model PL line proportioners can be used with all types of foamconcentrates. The proportioners are available in a wide range of sizes forfixed foam system applications. These applications also require anatmospheric foam concentrate storage tank as shown in the Typical LineProportioning System schematic.Portable line proportioners with fire hose thread connections (typically foruse with matched handline nozzles) are also available for the PL-60through PL-350 sizes.Typical applications include use by municipal fire departments and CFRtype vehicles, or with fixed systems, for protecting flammable liquidstorage tanks, loading racks, dike areas, and anywhere flammableliquids are used, stored, processed, or transported.

    Each ANSUL line proportioner consists of a body, jet, throat, and meter-ing orifice all of which are corrosion-resistant brass.The line proportioner body is designed with a female NPT threaded inletand a male NPT threaded outlet (see Line Proportioner Dimensions).The proportioner body is clearly marked with a flow direction arrow andthe designed concentration percentage.The inlet jet is secured by a stainless steel retaining ring on modelsPL-60 through PL-350; the inlet jet is threaded in place on modelsPL-420 through PL-730. The metering orifice or adjustable meteringvalve is sized according to the type and percentage of foam concentrateused. The metering orifice is secured with a stainless steel retaining ringto enable ease of change-over to other concentrate percentages.In fixed systems the line proportioner may be mounted at a maximumdistance of 8 ft (2.4 m) above the minimum foam liquid surface.

    The line proportioner body, jet, and throat shall be of brass construction.Retaining rings for both the inlet jet and the metering orifice shall bestainless steel.

    The line proportioner body shall have a female NPT inlet and male NPToutlet (see Line Proportioner Dimensions). The body shall be clearlymarked with a flow direction arrow and the percentage of foam concen-trate that the proportioner was designed to provide.The convergent inlet jet shall have a rounded inlet and a smoothmachined finish to ensure minimum friction loss. It shall be retained by astainless steel retaining ring or shall be threaded in place. The inlet jetshall terminate in the foam concentrate annulus chamber, and shall beconcentric with and set back from the throat and pressure recoverysection. Line proportioner outlet pressure recovery shall be 65% of theinlet pressure. The line proportioner shall be approved for mounting up toa maximum height of 8 ft (2.4 m) above the minimum foam liquidsurface.

    The foam concentrate metering orifice shall be machined to the properdiameter for the agent. It shall rest on a machined surface to preventleakage and shall be secured by a removable stainless steel retainingring.

    Part No. Part No. ApproximateLine With With ShippingProportioner 3% Concentrate 6% Concentrate WeightModel Orifice Orifice lb (kg)__________ _____________ _____________ _________

    PL-60 75650 75656 7 (3.2)PL-95 75662 75668 7 (3.2)PL-120 75674 75679 12 (5.4)PL-210 75684 75689 19 (8.6)PL-240 76890 76895 19 (8.6)PL-280 75694 75699 19 (8.6)PL-350 75704 75709 19 (8.6)PL-420 71508 71504 24 (10.9)PL-480 71518 71514 24 (10.9)PL-550 71528 71524 24 (10.9)PL-600 71538 71534 29 (13.2)PL-660 71548 71544 29 (13.2)PL-730 71558 71554 29 (13.2)

    ORDERING INFORMATION

    SPECIFICATIONS

    DESCRIPTIONAPPLICATION

    FOAM SYSTEMS LINE PROPORTIONERSData/Specifications

    001184

    Typical Line Proportioning System

    8 FT MAXIMUM(2.4 m)

    CHECKVALVEWATER

    SUPPLYVALVE

    FOAMCONCENTRATESHUT-OFF VALVE

    FOAMCONCENTRATESTORAGE TANK(ATMOSPHERIC TYPE)

    LINEPROPORTIONER

    001185

    Line Proportioner Cross Section

    BODY THROAT

    JET

    METERING ORIFICEWATERINLET

    FOAMSOLUTIONDISCHARGE

    RETAINING RING

    FOAM CONCENTRATEINLET

  • Flow Rate at Given PressureLine Proportioner K Factor Water K Factor K FactorModel (No Proportioning) 3% 6%__________ _______________ _____ _____

    PL-60 4.3 4.5 4.6PL-95 6.7 7.0 7.1PL-120 8.5 8.8 9.0PL-210 15.3 15.9 16.2PL-240 16.8 17.4 17.8PL-280 20.2 21.0 21.5PL-350 26.3 27.2 27.9PL-420 32.1 33.2 34.1PL-480 35.5 36.8 37.7PL-550 41.8 43.3 44.4PL-600 44.2 45.8 46.9PL-660 50.1 51.9 53.2PL-730 56.3 58.4 59.8

    Formula: Q = (K P)Example: Find flow of PL-350 @ 180 psi (1241 kPa) when used with

    a 3% foam concentrate:PL-350 3% K Factor 28.00Square root of 180 psi X 13.41

    _____

    FLOW RATE 375 gpm @ 180 psi(1420 Lpm @ 1241 kPa)

    1. The line proportioner must not be mounted more than 8 ft (2.4 m)above the minimum foam concentrate liquid level as shown in Figure1.

    2. Downstream pipe, fittings, elevation head, and discharge devicesmust not result in line proportioner outlet backpressure in excess of65% of line proportioner inlet pressure. (Consult with the systemdesigner to verify.)

    3. A check valve must be installed in the foam concentrate line with thedirection of flow from the foam concentrate storage tank to the lineproportioner. (See Figure 1.)

    4. A shutoff valve in the foam concentrate line is recommended toenable flush out of foam solution piping or allow for water onlydischarge. (See Figure 1.)

    5. Piping to foam concentrate inlet must be sized to match the foamconcentrate inlet piping size. (See Figure 2, Dimension B.)

    6. ANSUL recommends that the foam concentrate inlet line not exceed11 ft (3.4 m) of pipe, two 90 elbows, one swing check valve, and onenonrestricting shutoff valve.

    NOTICEExceeding foam concentrate line limitations or using pipesizes smaller than the foam concentrate inlet of the lineproportioner may reduce concentration percentages.

    INSTALLATION REQUIREMENTS

    Dimensions Inches (cm)A B C D E F G H I J K L

    PL-60 1 1/2 11 1/2 1/2 14 1 1/2 11/12 2.50 1.59 10.00 2.47 1.25 2.47 5.00 3.50 .281NPT NPT NPT (6.35) (4.04) (25.40) (6.27) (3.18) (6.25) (12.70) (8.89) (.714)

    PL-95 1 1/2 11 1/2 1/2 14 1 1/2 11/12 2.50 1.59 10.25 2.63 1.38 2.63 5.00 3.50 .281NPT NPT NPT (6.35) (4.04) (26.04) (6.68) (3.51) (6.68) (12.70) (8.89) (.714)

    PL-120 2 1/2 8 1/2 14 2 1/2 8 3.56 2.38 14.25 2.88 2.00 2.88 8.00 3.50 .281NPT NPT NPT (9.04) (10.80) (36.20) (7.32) (5.08) (7.32) (20.32) (8.89) (.714)

    PL-210 2 1/2 8 1 11 1/2 2 1/2 8 3.75 2.69 16.00 4.25 2.63 4.25 8.50 4.00 .343NPT NPT NPT (9.53) (6.83) (40.64) (10.80) (6.68) (10.80) (21.59) (10.16) (.87)

    PL-240 2 1/2 8 1 11 1/2 2 1/2 8 3.75 2.69 16.00 4.25 2.63 4.25 8.50 4.00 .343NPT NPT NPT (9.53) (6.83) (40.64) (10.80) (6.68) (10.80) (21.59) (10.16) (.87)

    PL-280 2 1/2 8 1 11 1/2 2 1/2 8 3.75 2.69 16.00 4.25 2.63 4.25 8.50 4.00 .343NPT NPT NPT (9.53) (6.83) (40.64) (10.80) (6.68) (10.80) (21.59) (10.16) (.87)

    PL-350 2 1/2 8 1 11 1/2 2 1/2 8 3.75 2.69 16.00 4.25 2.63 4.25 8.50 4.00 .343NPT NPT NPT (9.53) (6.83) (40.64) (10.80) (6.68) (10.80) (21.59) (10.16) (.87)

    PL-420 2 1/2 8 1 11 1/2 3 8 4.03 2.97 18.38 4.75 3.00NPT NPT NPT (10.24) (7.54) (46.69) (12.07) (7.62)

    PL-480 2 1/2 8 1 11 1/2 3 8 4.03 2.97 18.38 4.75 3.00NPT NPT NPT (10.24) (7.54) (46.69) (12.07) (7.62)

    PL-550 2 1/2 8 1 11 1/2 3 8 4.03 2.97 18.38 4.75 3.00NPT NPT NPT (10.24) (7.54) (46.69) (12.07) (7.62) NOTICE

    PL-600 3 8 1 1/4 11 1/2 4 8 4.38 3.21 20.19 5.06 3.25 Mounting feet are not provided withNPT NPT NPT (11.13) (8.15) (51.28) (12.85) (8.26) models PL-420 through PL-730.

    PL-660 3 8 1 1/4 11 1/2 4 8 4.38 3.21 20.19 5.06 3.25NPT NPT NPT (11.13) (8.15) (51.28) (12.85) (8.26)

    PL-730 3 8 1 1/4 11 1/2 4 8 4.38 3.21 20.19 5.06 3.25NPT NPT NPT (11.13) (8.15) (51.28) (12.85) (8.26)

    MODELS PL-60 THROUGH PL-350

    D

    GF

    K

    JI

    E

    B

    AC

    H (HEX)

    L

    001186

    001187a 001187b

    MODELS PL-420 THROUGH PL-730

    D

    GF

    E

    B

    AC

    H (HEX)

    LINE PROPORTIONER DIMENSIONS

    Copyright 2008 Ansul IncorporatedForm No. F-8739-2

    ANSULis a trademark of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

  • An atmospheric foam concentrate storage tank is one component of afoam proportioning system. The high density cross-linked polyethylene(XLPE) storage tanks supplied by ANSUL are compatible with allANSUL foam concentrates including ANSULITE AFFF, ANSULITEAlcohol Resistant AFFF, JET-X High Expansion, SILV-EX, along withANSUL 3% Protein and Fluoroprotein concentrates. Because of theexcellent properties of XLPE relating to stress crack resistance, impactstrength, light weight and overall toughness, poly tanks are an excellentchoice for many foam system applications. An atmospheric concentratetank is typically used in conjunction with an ANSUL balanced pressurepump proportioning skid unit or in-line balanced pressure proportion-ing system. Additionally, similar tanks could be used with an ANSULline proportioning system.

    The atmospheric poly foam concentrate tanks are supplied with fittingsas shown on drawings enclosed. There are two (2) return fittingsprovided on all tanks located 180 degrees apart to enable ease and flex-ibility for piping on site. Either connection can be used as the foamconcentrate return with the other return connection having the providedpipe plug installed. The poly tanks are translucent and have a levelgauge strip for approximating tank contents.Optional tank trim components are also available including: Tank Trim Package (2 in. pressure/vacuum vent and 1 1/2 in. drain

    valve) Low Liquid Level Float Switch normally open or normally closed

    contact

    Flex Connectors (1 1/2 in. 6 in.) Seismic Restraints (Contact Ansul Technical Services for details.)Poly tanks of alternate sizes and configurations are also available.ANSUL can also provide tanks in fiberglass, carbon steel, and stainlesssteel. Contact ANSUL Applications Engineering Department for addi-tional information.

    Storage tanks shall be designed for storage of foam concentrate atatmospheric pressure and shall be of vertical, cylindrical, high densitycross-linked polyethylene construction. Tanks shall be equipped with thefollowing: valved drain/fill connection, foam concentration pump suctionand return connections, inspection hatch, pressure/vacuum vent valve,and gauge or unbreakable sight glass to permit visual determination oflevel of tank contents. The foam concentrate storage tank shall have aminimum capacity to provide sufficient foam concentrate for the timespecified when the system is discharging foam solution at totalmaximum system flow.

    ApproximateShipping Weight

    Part No. Description lb. (kg)______ __________ _____________

    416850 100 gal (379 L) Poly Foam Tank 75 (34)416851 205 gal (776 L) Poly Foam Tank 100 (45)416852 295 gal (1117 L) Poly Foam Tank 125 (57)416853 475 gal (1798 L) Poly Foam Tank 130 (59)416854 540 gal (2044 L) Poly Foam Tank 150 (68)416855 805 gal (3047 L) Poly Foam Tank 220 (100)416856 1000 gal (3785 L) Poly Foam Tank 250 (113)416857 1150 gal (4353 L) Poly Foam Tank 300 (137)416858 1450 gal (5489 L) Poly Foam Tank 350 (159)416859 2250 gal (8517 L) Poly Foam Tank 350 (159)416860 2550 gal (9653 L) Poly Foam Tank 450 (204)416861 3000 gal (11356 L) Poly Foam Tank 550 (250)416862 3900 gal (14763 L) Poly Foam Tank 800 (363)416863 5050 gal (19116 L) Poly Foam Tank 1300 (590)404377 Tank Trim Package 25 (11)

    (2 in. P/V Vent and 1 1/2 in. Drain Vent)403508 Low Liquid Level Switch 15 (7)

    (Normally Closed Contact)405777 Low Liquid Level Switch 15 (7)

    (Normally Open Contact)405613 Flex Connector 1 1/2 in. 3 (1.4)404886 Flex Connector 2 in. 4 (1.8)404854 Flex Connector 3 in. 7 (3.2)404855 Flex Connector 4 in. 9 (4.1)405538 Flex Connector 6 in. 14 (6.4)404382 Mineral Oil Concentrate Sealer 45 (20)

    5 gal Pail

    Seismic Zone Restraints are available.

    ORDERING INFORMATION

    SPECIFICATIONS

    DESCRIPTION

    APPLICATION

    ATMOSPHERIC POLY FOAM CONCENTRATE TANKSData/Specifications

  • Ansul Nominal Liquid Full Shipping WallPart Tank Size* Capacity A B C D Suction Return Weight Thick.No. Gal (L) Gal (L) in. (cm) in. (cm) in. (cm) in. (cm) Diameter Diameter lb (kg) in. (cm)___ ___ ___ ___ ___ __ ___ ___ ___ __ ___ __ ___ ________ ________ ___ ___ __ ___

    416850 100 379 106 401 23.0 58.4 66.50 168.9 8.0 20.3 11.5 29.2 2 in. FNPT 1.5 in. FNPT 75 34 0.25 0.64416851 205 776 214 810 31.0 78.7 73.50 186.7 8.0 20.3 15.5 39.4 2 in. FNPT 1.5 in. FNPT 95 43 0.25 0.64416852 295 1117 319 1208 46.0 116.8 53.00 134.6 8.0 20.3 23.0 58.4 2 in. FNPT 1.5 in. FNPT 115 52 0.25 0.64416853 475 1798 503 1904 48.0 121.9 75.00 190.5 8.0 20.3 24.0 60.9 2 in. FNPT 1.5 in. FNPT 125 57 0.25 0.64416854 540 2044 565 2139 48.0 121.9 81.75 207.6 8.0 20.3 17.5 44.5 3 in. Flange 2 in. FNPT 165 75 0.25 0.64416855 805 3047 834 3157 48.0 121.9 119.00 302.3 8.0 20.3 14.0 35.6 3 in. Flange 2 in. FNPT 215 98 0.25 0.64416856 1000 3785 1164 4406 86.0 218.4 56.50 143.5 8.0 20.3 17.5 44.5 3 in. Flange 2 in. FNPT 230 104 0.31 0.79416857 1150 4353 1229 4652 64.0 162.6 98.50 250.2 8.0 20.3 18.0 45.7 3 in. Flange 3 in. Flange 290 132 0.31 0.79416858 1450 5489 1611 6098 86.0 218.4 75.00 190.5 8.0 20.3 16.0 40.6 3 in. Flange 3 in. Flange 310 141 0.31 0.79416859 2250 8517 2492 9433 96.0 243.8 93.25 236.9 8.0 20.3 18.5 47.0 4 in. Flange 3 in. Flange 360 163 0.38 0.97416860 2550 9653 2701 10224 85.0 215.9 123.50 313.7 8.0 20.3 19.0 48.3 4 in. Flange 3 in. Flange 455 206 0.38 0.97416861 3000 11356 3173 12011 85.0 215.9 139.50 354.3 8.0 20.3 19.0 48.3 4 in. Flange 3 in. Flange 655 297 0.44 1.12416862 3900 14763 4131 15637 94.0 238.8 152.75 388.0 10.0 25.4 23.5 59.7 6 in. Flange 4 in. Flange 880 399 0.56 1.42416863 5050 19116 5244 19851 94.0 238.8 192.25 488.3 10.0 25.4 23.0 58.4 6 in. Flange 4 in. Flange 1550 703 0.75 1.91* Nominal tank size is used for design purposes. Up to 1.3% of nominal tank size volume may not discharge from tank based on suction drop tube being 1" from tank

    bottom. (liquid pad)Tank sizing should include room for required agent quantity + liquid pad + thermal expansion of agent (2.5% of fill volume) + required 1/4" mineral oilsealer.Manufacturing tolerance for A and B dimensions are + / 3% of number shown.Notes for factory installed fittings:1. 1.5 in. and 2 in. connections are PVC Bulk Head Type with FNPT, 3 in. and larger connections are PVC gusseted bolt on flange type which mate to

    Standard ANSI Flange Connection for Pipe Size shown.2. All Flanged Connections extend 6.5 in. (17 cm) from tank wall to flange face3. Suction connections supplied with drop tube.4. (1) return connection supplied with appropriate plug or blind flange, float switch connection supplied with pipe plug.5. 100-295 gallon (379-1117 L) tanks have 7 in. (18 cm) threaded inspection port; 540-1450 gallon (2044-5489 L) tanks have a 19 in. (48 cm) bolted

    manway with a 10 in. (25 cm) threaded inspection port. (Exception: 475 gallon (1798 L) and 1000 gallon (3785 L) tanks have 17 in. (43 cm) manway);2250-5050 gallon (8517-19116 L) tanks have a 24 in. (61 cm) combination manway.

    Copyright 2008 Ansul IncorporatedForm No. F-93215-3

    ANSUL, ANSULITE, JET-X and SILV-EX are trademarks of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com

    STORAGE TANK DIMENSIONAL INFORMATION

    001178

    A

    B

    C

    2 IN. P/V VENTCONNECTION

    SUCTION

    1 IN. FNPT FLOATSWITCH OUTLET

    1 1/2 IN. FNPT DRAIN

    RETURN, 2 PLCS. 180 PART

    D

  • Fig. 548

    SPECIFICATION OPTIONS:ASize: N.P.T. Threads (BSP Options Available)BPressure setting in oz. /sq. in.CVenting capacity / CFH in 1000s at 2.5 P.S.I.DVacuum setting in oz. / sq. in.EPoppet/Seat material: Brass (BR) or Viton Foam on Brass(BR/VF)FBody/Hood material: Brass (BR) or Aluminum (AL)GDryer connection: Male (M), Female (F), No connection (NO)HHeight of vent (inches)IWidth of vent (inches)JShipping Weight (lbs.)

    Pressure weight: LeadVacuum gasket: Fuel resistant materialScreen: 30 mesh stainless steelThreaded gauge hatch for manual gauging access.Horizontal discharge and field-adjustable, tripolar orientation.

    WARNING: DO NOT FILL OR UNLOAD FUEL FROM A STORAGETANK UNLESS IT IS CERTAIN THAT THE TANK VENTS WILL OPER-ATE PROPERLY. Morrison tank vents are designed only for use on shopfabricated atmospheric tanks which have been built and tested inaccordance with UL 142, NFPA 30 & 30A, and API 650 and in accordancewith all applicable local, state, and federal laws. In normal operation, dustand debris can accumulate in vent openings and block air passages.Certain atmospheric conditions such as a sudden drop in temperature,below freezing temperatures, and freezing rain can cause moisture to enterthe vent and freeze which can restrict internal movement of ventmechanisms and block air passages. All storage tank vent air passagesmust be completely free of restriction and all vent mechanisms must havefree movement in order to insure proper operation. Any restriction of airflowcan cause excessive pressure or vacuum to build up in the storage tank,which can result in structural damage to the tank, fuel spillage, propertydamage, fire, injury, and death. Monthly inspection, and immediateinspection during freezing conditions, by someone familiar with the properoperation of storage tank vents, is required to insure venting devices arefunctioning properly before filling or unloading a tank.

    WARNING: Normal vents such as pressure vacuum and updraft ventsfor aboveground storage tanks should be sized according to NFPA 30(2008) 21.4.3

    Fig. 548 Pressure/Vacuum VentsMorrison Bros. Co.

    Specification SheetThe Morrison Fig. 548 pressure/vacuum vent with gauge hatch is designed for normal ventingof Aboveground Storage Tanks. It allows tanks to breathe during filling and withdrawingoperations. Pressure/ Vacuum poppetsseal vapors in the tank when pressureis equalized. This vent must be usedin conjunction with an emergency ventand it is recommended that theopening pressure setting is set belowthat of the emergency vent so thenormal vent relieves first.

    P.O. Box 238 Dubuque, Iowa 52004-0238563.583.5701 (tel) 800.553.4840 563.583.5028 (fax)

    w w w . m o r b r o s . c o m

    I.D . N UM B ER A B C D E F G H I J548---0100 AV 2 2 20.2 1 BR BR NO 10.37 9.68 13.25

    548---0200 AV 2 4 20.2 1 BR BR NO 10.37 9.68 13.75

    548---0300 AV 2 6 20.2 1 BR BR NO 10.37 9.68 14.25

    548---0400 AV 2 8 20.2 1 BR BR NO 10.37 9.68 14.75

    548---0500 AV 2 12 18.6 1 BR BR NO 10.37 9.68 15.75

    548---0600 AV 2 16 18 1 BR BR NO 10.37 9.68 17

    548---0700 AV 3 2 43 1 BR BR NO 12.12 13.37 26.25548---0800 AV 3 4 43 1 BR BR NO 12.12 13.37 27.25

    548---0900 AV 3 6 43 1 BR BR NO 12.12 13.37 28.25

    548---1000 AV 3 8 43 1 BR BR NO 12.12 13.37 28.75

    548---1100 AV 3 12 43 1 BR BR NO 12.12 13.37 28.75

    548---1200 AV 3 16 40 1 BR BR NO 12.12 13.37 33.25

    548---1300 AV 2 2 20.2 1 BR BR M 13 9.68 13.25

    548---1400 AV 2 4 20.2 1 BR BR M 13 9.68 13.75

    548---1500 AV 2 6 20.2 1 BR BR M 13 9.68 14.25548---1600 AV 2 8 20.2 1 BR BR M 13 9.68 14.75

    548---1700 AV 2 12 18.6 1 BR BR M 13 9.68 15.75

    548---1800 AV 2 16 18 1 BR BR M 13 9.68 17

    548---1900 AV 3 2 43 1 BR BR F 12.12 13.37 26.25

    548---2000 AV 3 4 43 1 BR BR F 12.12 13.37 27.25

    548---2100 AV 3 6 43 1 BR BR F 12.12 13.37 28.25

    548---2200 AV 3 8 43 1 BR BR F 12.12 13.37 28.75

    548---2300 AV 3 12 40 1 BR BR F 12.12 13.37 29.25

    548---2400 AV 3 16 40 1 BR BR F 12.12 13.37 33.25548A---0100 AV 2 2 20.2 1 BR AL NO 10.37 9.68 7

    548ABSP0100 AV 2 2 20.2 1 BR AL NO 10.37 9.68 7

    548A---0200 AV 2 4 20.2 1 BR AL NO 10.37 9.68 7.75

    548A---0300 AV 2 6 20.2 1 BR AL NO 10.37 9.68 8.5

    548A---0400 AV 2 8 20.2 1 BR AL NO 10.37 9.68 9.5

    548A---0500 AV 2 12 18.6 1 BR AL NO 10.37 9.68 10.5

    548A---0600 AV 2 16 18 1 BR AL NO 10.37 9.68 11.25

    548A---0700 AV 3 2 43 1 BR AL NO 12.12 13.37 12.25548ABSP0700 AV 3 2 43 1 BR AL NO 12.12 13.37 12.25

    548A---0800 AV 3 4 43 1 BR AL NO 12.12 13.37 13.75

    548A---0900 AV 3 6 43 1 BR AL NO 12.12 13.37 15

    548A---1000 AV 3 8 43 1 BR AL NO 12.12 13.37 15.5

    548A ---1100 AV 3 12 40 1 BR AL NO 12.12 13.37 15.75

    548A---1200 AV 3 16 40 1 BR AL NO 12.12 13.37 20.5

    548A---1300 AV 2 2 20.2 1 BR AL M 13 9.68 7

    548A---1400 AV 2 4 20.2 1 BR AL M 13 9.68 7.75548A---1500 AV 2 6 20.2 1 BR AL M 13 9.68 8.5

    548A---1600 AV 2 8 20.2 1 BR AL M 13 9.68 9.5

    548A---1700 AV 2 12 18.6 1 BR AL M 13 9.68 10.5

    548A---1800 AV 2 16 18 1 BR AL M 13 9.68 11.25

    548A---1900 AV 3 2 43 1 BR AL F 12.12 13.37 12.25

    548A---2000 AV 3 4 43 1 BR AL F 12.12 13.37 13.75

    548A---2100 AV 3 6 43 1 BR AL F 12.12 13.37 15

    548A---2200 AV 3 8 43 1 BR AL F 12.12 13.37 15.5

    548A---2300 AV 3 12 40 1 BR AL F 12.12 13.37 15.75548A---2400 AV 3 16 40 1 BR AL F 12.12 13.37 20.5

  • H-9COPYRIGHT 2006 CONBRACO IND., INC. PRINTED IN U.S.A.

    BRONZE PAD LOCKING BALL VALVE

    75-100 SeriesBronze Pad Locking Ball Valve

    Threaded, 600 psig WOG, Cold Non-Shock. 150 psig Saturated Steam.Vacuum Service to 29 inches Hg.Federal Specification: WW-V-35C, Type: II, Composition: BZ, Style: 3.MSS SP-110; Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends.

    FEATURES Chromium plated ball Blow-out-proof stem design RPTFE seats and stuffing box ring Adjustable packing gland May be padlocked in open or closed position with no change of hardware

    STANDARD MATERIAL LIST1. Lever and grip Steel, zinc plated w/vinyl 7. Gland nut B162. Stem packing RPTFE 8. Stem B163. Stem bearing RPTFE 9. Lever nut Steel, zinc plated4. Ball B16, chrome plated 10. Body seal PTFE (1-1/4 & 2)5. Seat (2) RPTFE 11. Body B584-C844006. Retainer B16 (1/4 to 1)

    B584-C84400 (1-1/4 to 2)

    VARIATIONS AVAILABLE:75-140 Series (316 SS Ball & Stem)75-190 Series (Pinned Retainer)

    OPTIONS AVAILABLE:(SUFFIX) OPTION SIZES-02- Stem Grounded 1/4 to 2-05- Plain Ball 1/4 to 2-08- 90 Reversed Stem 1/4 to 2-10- SS Lever & Nut 1/4 to 2-14- Side Vented Ball (Uni-Directional) 1/4 to 2-17- Rough Chrome Plated - Bronze Valves 1/4 to 2-18- Plain Yellow Grip 1/4 to 2-20- Slot Vented Ball 1/4 to 2-24- Graphite Packing 1/4 to 2-41- Automatic Drain 1/4 to 2

    see page J-8-49- Assembled Dry 1/4 to 2-57- Oxygen Cleaned 1/4 to 2-60- Grounded Ball & Stem 1/4 to 2-P01- BSPP (Parallel) Thread Connection 1/4 to 2-T01- BSPT (Tapered) Thread Connection 1/4 to 2

    NUMBER SIZE A B C D E Wt.75-101-01 1/4 .43 1.12 2.25 1.81 3.00 .8075-102-01 3/8 .50 1.12 2.25 1.81 3.00 .7775-103-01 1/2 .50 1.12 2.25 1.81 3.00 .7075-104-01 3/4 .87 1.68 3.37 2.25 3.87 2.0375-105-01 1 .87 1.68 3.37 2.25 3.87 1.8375-106-01 1-1/4 1.00 2.00 4.00 2.62 5.50 3.4875-107-01 1-1/2 1.25 2.18 4.37 2.87 5.50 4.2375-108-01 2 1.50 2.34 4.68 3.06 5.50 5.69

    Pat. 3,865,130

    For Pressure/Temperature Ratings,Refer to Page M-8, Graph No. 4

  • MODEL CVB IN-LINE CHECK VALVE (61-100/200 Series)

    Conbraco Industries, Inc. 701 Matthews Mint Hill Rd. Matthews NC 28105 USA ; www.apollovalves.com

    Job Name: Contractor:

    Job Location: P.O. Number: Engineer: Representative: Tag: Wholesale Distributor:

    DESCRIPTION

    ; 704-841-6000

    Conbraco Industries can accept no responsibility for possible errors in this document and reserves the right to alter its product design or construction without notice and without incurring any obligation to make such changes on Conbraco products previously or subsequently sold. All product specifications are approximate and are provided for reference only.

    SS1024 11/08 Page 1 of 1

    The Apollo CVB Ball Cone check valves offer reliable protection against reverse flow and exceptional resistance to chemicals and corrosion using proven ASTM quality materials made in the USA.

    FEATURES FNPT and MNPT Inlet Option Spring Actuated Bronze Sizes to 3 Tight Shut-off With Liquid Media Flow Straight-through Design Efficiency RPTFE Ball Cone for Chemical Resistance Made in the USA Canadian Registration Number 0C11218.5C MATERIAL SPECIFICATIONS

    Part Name Material Body Cast Bronze C84400 Retainer ASTM B16 Brass Spring AISI 316 Stainless Steel Ball Cone Check RPTFE, 15% Glass Filled Stem ASTM B16 Brass

    PERFORMANCE RATING Max Pressure: 400 psi / 125 psi Steam Max Temp: 350F (176.6C)

    Flow Rate (Cv) 1 psi Differential Pressure

    Size GPM 3/8 1

    1-1/4 1-1/2

    2 2-1/2

    3

    .85 1.21 1.40 3.53 6.00 44 65 81

    175 265

    APPLICATIONS Well-suited for a broad range of applications, including saturated steam and chemical service. May be installed in both horizontal and vertical flow with upward flow. Do not use for reciprocating air compressor service.

    OPTIONS FNPT x FNPT (61-100 Series) MNPT x FNPT (61-200 Series) 0 psig Cracking Pressure (No Spring) 0.50 psig Cracking Pressure 5 psig Cracking Pressure (1/4-1 Only) 10 psig Cracking Pressure (1/4-1 Only) Oxygen Cleaned Satin Chrome Plate Finish BSPP Threads (1/2 1 Only) OTHER

    DIMENSIONS Model

    Number Item

    Number Size A

    MNPT A B C Wt. (Lb)

    CVB14 61-101-01 2.38 2.06 1.12 1.12 .38 CVB38 61-102-01 3/8 2.38 2.12 1.12 1.12 .38 CVB12 61-103-01 2.56 2.31 1.12 1.12 .38 CVB34 61-104-01 3.12 2.87 2.37 1.50 .75 CVB1 61-105-01 1 3.87 3.50 1.75 1.93 1.45 CVB114 61-106-01 1 4.44 4.19 2.12 2.37 2.75 CVB112 61-107-01 1 5.18 4.94 2.50 2.81 3.94 CVB2 61-108-01 2 6.50 6.00 3.00 3.68 6.30 CVB212 61-109-01 2 7.12 3.87 4.50 14.0 CVB3 61-100-01 3 8.13 5.31 4.63 16.6

    Note: Model CVBM (61-200 Series) is a MNPT x FNPT connection.

  • ANSULITE 6% (AFC-3) AFFF (Aqueous Film-Forming Foam)Concentrate is formulated from specialty fluorochemical and hydrocar-bon surfactants along with solvents. It is transported and stored as aconcentrate to provide ease of use and considerable savings in weightand space.

    It is intended for use as a 6% proportioned solution in fresh, salt or hardwater. It may also be used and stored as a 6% premixed solution infresh or potable water only. The correct proportioning or mixture ratio is6 parts of concentrate to 94 parts of water.

    Three fire extinguishment mechanisms are in effect when usingANSULITE 6% (AFC-3) AFFF Concentrate. First, an aqueous film isformed which works to help prevent the release of fuel vapor. Second,the foam blanket from which the film-forming liquid drains effectivelyexcludes oxygen from the fuel surface. Third, the water content of thefoam provides a cooling effect.

    Physiochemical Properties at 77 F (25 C)Appearance Colorless to Pale Yellow LiquidDensity 1.013 g/ml 0.020pH 7.0 8.5Refractive Index 1.3390 0.0030Surface Tension (6% Solution) 18 1 dynes/cmViscosity 2 1 centistokes

    ANSULITE 6% (AFC-3) AFFF Concentrate is intended for use on ClassB hydrocarbon fuel fires having low water solubility such as variouscrude oils, gasolines, diesel fuels, aviation fuels, etc. It is not suitablefor use on fuels having appreciable water solubility (polarsolvents), i.e., methyl and ethyl alcohol, acetone, and methyl ethylketone. It can be used with both aspirating and non-aspirating dischargedevices because of the low energy required to make it foam.Its excellent wetting characteristics make it useful in combating Class Afires as well. It can be used with dry chemical extinguishing agentswithout regard to the order of application to provide even greater fireprotection capability.

    Fire Performance The fire performance of ANSULITE 6% (AFC-3)AFFF Concentrate is measured against specifications and standardssuch as U.S. Military Specification MIL-F-24385 but is not on theQualified Product List (QPL). ANSULITE 6% (AFC-3) AFFFConcentrate has been tested to Underwriters Laboratories Standard162. Reports covering this fire performance are available on requestsince standards and specifications such as those cited are continuouslybeing upgraded and changed.Foaming Properties When used with fresh, salt, or hard water at thecorrect dilution with most conventional foam making equipment, theexpansion will vary depending on the performance characteristics of theequipment. Aspirating discharge devices produce expansion ratios offrom 6:1 to 10:1 depending primarily on type and flow rate. Subsurfaceinjection generally produces expansion ratios of 2:1 to 3:1. Non-aspirat-ing devices such as handline water fog/stream nozzles or standardsprinkler heads give expansion ratios of 2:1 to 4:1.

    Proportioning ANSULITE 6% (AFC-3) AFFF Concentrate can beproportioned easily at the correct dilution using most conventionalproportioning equipment such as:1. Balanced pressure and in-line balanced pressure pumped proportion-

    ing equipment2. Balanced pressure bladder tank type proportioner3. Around-the-pump type proportioners4. Fixed or portable (in-line) venturi type proportioners5. Handline nozzles with fixed induction/ pickup tubesThe minimum and maximum usable temperatures for ANSULITE 6%(AFC-3) AFFF Concentrate in this equipment is 35 F (2 C) to 120 F(49 C) respectively.Storage/Shelf Life When stored in the packaging supplied (polyethyl-ene drums or pails) or in equipment recommended by the manufactureras part of the foam system and within the temperature limits specifiedthe shelf life of ANSULITE 6% (AFC-3) AFFF Concentrate is about20-25 years.

    The factors affecting shelf life and stability for ANSULITE AFFF Agentsare discussed in detail in Ansul Technical Bulletin No. 54. If the productis frozen during storage or transportation, thawing will render the productcompletely usable.

    Compatibility Ansul has conducted testing with admixtures of differentmanufacturers 6% AFFF products in varying proportions and is satisfiedthat the ANSULITE 6% AFFF is compatible with these products. Refer toAnsul Technical Bulletin No. 48 for a more detailed discussion ofcompatibility.

    Different types of foam concentrates, i.e., AFFF, protein base, etc.,should not be mixed under any circumstances.

    Materials of Construction Compatibility Tests have been performedwith ANSULITE 6% (AFC-3) AFFF Concentrate verifying its compatibilitywith standard carbon steel black pipe and pipe manufactured fromvarious stainless steel or brass compounds. Alternative pipe, fittings, andvalves may be used in some cases if acceptable to the customer and/orthe authority having jurisdiction.Galvanized pipe and fittings must not be used in areas where undilutedconcentrate will contact them since corrosion will result.

    Refer to Ansul Technical Bulletin No. 59 addressing acceptable materialsof construction for use with ANSUL foam concentrates.Inspection As with any fire extinguishing agent, ANSULITE 6%(AFC-3) AFFF Concentrate, whether in the concentrate or pre-mixedform should be inspected periodically. Please refer to the FieldInspection Manual, Ansul Part No. 31274, for the detailed procedures toperform this inspection. An annual inspection is recommended unlessunusual conditions of exposure occur, such as are described in AnsulTechnical Bulletin No. 54. In such cases, ANSULs recommendationshould be sought.

    PERFORMANCE

    APPLICATION

    DESCRIPTION

    ANSULITE 6% (AFC-3) AFFF CONCENTRATEData/Specifications

  • ANSULITE 6% (AFC-3) AFFF Concentrate is approved, qualified under,listed or meets the requirements of the following specifications and stan-dards:

    Underwriters Laboratories Inc. UL Standard 1621. Foam Quality Tests2. Class B Hydrocarbon Fuel Fire Tests3. Foam Identification Tests4. Tests of Shipping Containers5. Class B Hydrocarbon Fuel Sprinkler Test (Foam water type both

    upright and pendent approvals only)It is impractical for ANSUL to list its ANSULITE 6% agents with everypiece of UL Iisted hardware. Moreover, there are numerous foam hard-ware components without UL Iistings that cannot be listed for use withany AFFF agent.Many unlisted pieces of foam hardware should be similar to those listed.However, on installations where ANSULITE 6% may be used with hard-ware components of significantly different types than those tested,contact ANSUL for recommendations.

    ANSULITE 6% AFC-3 AFFF Concentrate is available in pails, drums,totes, or bulk shipment.

    Part No. 54391 5 gallon pailPart No. 54392 55 gallon drumPart No. 432155 265 gallon totePart No. 30915 Bulk (contact ANSUL about domestic truckload

    delivery)Shipping Weight:

    5 gal (19 L) pail 45 Ib (20.4 kg)55 gal (208.1 L) drum 495 Ib (224.5 kg)265 gal (1000 L) tote 2465 lb (1118 kg)

    Cube:5 gal (19 L) pail 1.25 ft3 (0.353 m3)55 gal (208.1 L) drum 11.83 ft3 (0.3350 m3)265 gal (1000 L) tote 50.05 ft3 (1.42 m3)

    ORDERING INFORMATION

    APPROVALS AND LISTINGS

    Copyright 2007 Ansul IncorporatedForm No. F-83125-6

    ANSUL and ANSULITE are trademarks of Ansul Incorporated or its affiliates.

    Ansul IncorporatedMarinette, WI 54143-2542

    715-735-7411www.ansul.com