tópicos avançados em - faculdade de engenhariafdosreis/qee/download/paulofernandoribeiro.pdf ·...
TRANSCRIPT
1
Paulo Fernando Ribeiro, PhD, IEEE FellowCo-Chairman of the Power Quality Steering Committee of the IEEE
Professor: Calvin College
Visiting Scholar: Center for Advanced Power Systems (FSU)
Tópicos Avançados em Qualidade de Energia Elétrica
5 0 5
0
10 5 0 5 102
0
2
5 0 5
0
AgradecimentosMark McGranaghan
Alex McEachernAlex EmanuelErich Gunther
Gerald HeydtONS, EPRI August, 2005
A Power System of the Future?
Hospital with cogeneration (1.5 MW)
SubstationFeeder
Residential photovoltaic system
(6 kW)
Utility-owned Photovoltaic site
(500 kW)
Small wind turbine (10 kW)
Factory with natural gas fuel cell (100 kW to 5 MW)
Residential Fuel cell (7 kW)
Utility-owned wind turbine site (1 MW)
With permission of M. McGranaghan, and T. Key
2
E x a m p l e W a v e s h a p eo r R M S v a r i a t i o n
P o w e r Q u a l i t yV a r i a t i o nC a t e g o r y
M e t h o d o fC h a r a c t e r i z i n g T y p i c a l C a u s e s
E x a m p l eP o w e rC o n d i t i o n i n gS o l u t i o n s
Impulse
10 15 20 25 30- 150
- 100
- 5 0
0
50
10 0
15 0
Tim e (m S )
I m p u l s i v eT r a n s i e n t s
P e a k m a g n i t u d e ,R i s e t i m e ,D u r a t i o n
L i g h t n i n g ,E l e c t r o - S t a t i cD i s c h a r g e ,L o a d S w i t c h i n g ,C a p a c i t o rS w i t c h i n g
S u r g e A r r e s t eF i l t e r s ,I s o l a t i o nT r a n s f o r m e r s
Oscillatory Transient
0 20 40 60 80- 20 0
- 15 0
- 10 0
- 50
0
50
10 0
15 0
Tim e (m S )
O s c i l l a t o r yT r a n s i e n t s
W a v e f o r m s ,P e a k M a g n i t u d e ,F r e q u e n c yC o m p o n e n t s
L i n e / C a b l eS w i t c h i n g ,C a p a c i t o rS w i t c h i n g ,L o a d S w i t c h i n g
S u r g e A r r e s t eF i l t e r s ,I s o l a t i o nT r a n s f o r m e r s
Voltage Sag
0 100 200 300 400 500 - 10
10
30
50
70
90
1 10
Tim e (m S )
S a g s / S w e l l s R M S v s . t i m e ,M a g n i t u d e ,D u r a t i o n
R e m o t e S y s t e mF a u l t s
F e r r o r e s o n a n tT r a n s f o r m e r s ,E n e r g y S t o r a gT e c h n o l o g i e s *U P S
Interruption
0 20 00 40 00 60 00 0
20
40
60
80
10 0
12 0
Tim e (m S)
I n t e r r u p t i o n s D u r a t i o n S y s t e mP r o t e c t i o n( B r e a k e r s ,F u s e s ) ,M a i n t e n a n c e
E n e r g y S t o r a gT e c h n o l o g i e s *U P S ,B a c k u pG e n e r a t o r s
RMS Overvoltage
0 1 00 0 2 00 0 3 00 0 4 00 0 5 0
6 0
7 0
8 0
9 0
1 00
1 10
1 20
Tim e (m S )
U n d e r v o l t a g e s /O v e r v o l t a g e s
R M S v s . T i m e ,S t a t i s t i c s
M o t o r S t a r t i n g ,L o a d V a r i a t i o n s ,L o a d D r o p p i n g
V o l t a g eR e g u l a t o r s ,F e r r o r e s o n a n tT r a n s f o r m e r s
Distorted Current Waveform
10 20 30 40 50 60- 100 0
- 5 00
0
500
10 00
Tim e (m S )
H a r m o n i cD i s t o r t i o n
H a r m o n i cS p e c t r u m ,T o t a l H a r m .D i s t o r t i o n ,S t a t i s t i c s
N o n l i n e a r L o a d s ,S y s t e mR e s o n a n c e
F i l t e r s ( a c t i v e p a s s i v e ) ,T r a n s f o r m e r s( c a n c e l l a t i o n oz e r o s e q u e n c ec o m p o n e n t s )
Voltage Flicker
0 25 50 75 100 125 90
95
100
105
110
Tim e (s)
V o l t a g e F l i c k e r V a r i a t i o nM a g n i t u d e ,F r e q u e n c y o fO c c u r r e n c e ,M o d u l a t i o nF r e q u e n c y
I n t e r m i t t e n tL o a d s ,M o t o r S t a r t i n g ,A r c F u r n a c e s
S t a t i c V a rS y s t e m s
Peak overvoltage(pu)
XXXTransients
SARFI70(2)
XXXVoltage Sags
THD < 3.0%CP95%
XXXHarmonics
V2/V1 < 2.0%CP95%
XXXUnbalance
PstD95%< 1.0PltS95% < 0.8
XXXFlicker
–1Hz <fc < +1HzCP99.9%
XXXXXXFrequency Variation
-5% <Vn< +5%(1)
XXXVoltage Regulation
DEC, FECXXXContinuity
Indices and compatibility levels
DisturbancePhenomena
SteadyState
Phenomena
3
IndustryAssessments
Performance Indices
System Monitoring(Permanent or
Surveys)
System Studies(Simulations)
Actual Performance
Compare withIndices
IdentifyResponsibility and
Solutions
Implement Solutionsand Assess
Performance
Periodic ReportingEducation and
InformationPrograms
ExpectedPerformance
Information , Regulation,and Industry Interaction
Analysis and SimulationTools and Procedures
Monitoring and PerformanAssessment Systems
Qualidade de EnergiaUma Visão Integrada
QUESTIONS
What is power quality and its context?
What is the cost of power quality and related responsibilities?
What is the value of power quality for the different players?
Are the definitions and standards appropriate?
How deviations should be treated (rigid or flexible approach)?
What is the impact of deregulation and DG developments on PQ?
How is the power sector addressing power quality needs and risks?
How well equipped is the sector for dealing with an increasingly complex environment?
What are topics for future research and development (real needs)?
4
The Current Revolution is a Consequence of the Convergence of:
Power Systems Classical OperationAdvanced Power Systems Management
New Generation and Distribution TopologiesNew Power Electronics Technologies
Advanced Signal Processing and AnalysisAdvanced Monitoring
Much Higher Computer PowerAdvanced / Intelligent Communications, and Computer
Controls
Vision"Where there is no vision, the people perish"
Proverbs 29:18
Philosophy / StrategyNo aspect of reality (or a system) should be viewed in isolation
Initiative
Imagination, Creativity, Sustainability Norms and Citizenship (Ethics / Morality – engineering/technology is not a morally neutral activity)
Philosophy / Strategy?
5
Generation
Transmission
Performance Parameters
Planning
Operation
Economic Feasibility
Distribution
The Big, Integrated, Macro Picture
ConsumersConsumers
Accessibility
Security
Continuity
Reliability
Voltage (Power) Quality
Performance Parameters
The Big, Integrated, Macro Picture
6
The Big, Integrated, Macro Picture
Concepts and Issues
Techniques (software)Systems and ConceptsHardwareMeasuring and MonitoringComputer Modeling and SimulationDeregulation and Distributed GenerationStandardsManagement
Caution
Advanced Concepts
Techniques (software)
Wavelet Theory
Expert Systems
Fuzzy Logic
Genetic Algorithms
Neural Network
Real Time Digital Simulation
Chaos Theory
Multi-Agents
7
Advanced Concepts
Systems and Concepts
PQ Parks
Custom Power / FACTS / Transfer Switches
Higher Immunity
Special Contracts
Power Management Companies
Macro-Economic Analysis
Advanced Concepts
Hardware
Active Harmonic Filters
Micro SMES for Power Quality
Large SMES for Transmission / Distribution
PWM Based Higher Power Compensators
FACTS Controller, Custom Power Devices
Transfer Switches
8
Advanced Concepts
Measuring and Monitoring
Artificial Intelligence Instruments
Remote Access (Internet)
Integrated Diagnostic
Comprehensive System Monitoring
Centralized Monitoring (GPS)
Advanced Concepts
Computer Modeling and Simulation
Graphical Environment
Inclusion of Artificial Intelligence (fuzzy / neural, wavelets)
Integrated Economic Analysis
Real Time Digital Simulation(Hardware-in-the-Loop)
9
Advanced Concepts
Deregulation and Distributed Generation
Impact of Deregulation and DG on PQ
Impact of PQ on Deregulation and DG
Advanced Concepts
Standards
Flexibility
Compatibility
Commonality (IEEE / IEC)
Increased Immunity
10
Advanced Concepts
Management
Integrated PQ
Integrated Self-Healing Network and Communication Systems
Integrated Consumers, Agents Communication Interface
Integrated / Comprehensive PQ Database
Advanced Concepts
Caution
Useless research
Unnecessary technical sophistication
Pet subjects
Be aware of the increasing complexity of the system
Keep an integrated (global) perspective
11
VSI CSI
Natural Forced
Synchronous PWM
Hard Soft
Two-Level Multi-Level
SCR GTO IGBT MCT MTO
System
CommutationApproach
SwitchingTechnology
TransitionApproach
CircuitTopology
DeviceType
Power Electronics - Semiconductor DevicesDecision-Making Matrix
Example of aA Multifaceted Decision Process
An Integrated Perspective is necessary
Example
General Guidelines
General Philosophy: Main Function
Within each power quality category, the PQ Program defines the following aspects.
Philosophy
•Problem Definition – Why is it important to ----?
•Responsibilities – What needs to be done? By whom? (individual, global limits to be respected by ONS / Agents)
•Flexibility to allow for different system characteristics
Management
•Data Collection (Format, etc.)
•Duration, Management, etc.
•Tracking system performance
•Where, When, How?
12
General Guidelines
General Philosophy: Main Function
Within each power quality category, the PQ Program defines the following aspects.
Technical•Indices (definitions)
•Monitoring (functional Specs, etc)
•Standards
What is Power / Voltage Disturbance / Quality?
Definitions
“Any power problem manifested in voltage, current, or frequency deviations that results in the failure or misoperation of customer equipment."
IEEE PES Working GroupP1433 Power Quality Definitions
Of all power quality problems, approximately 60% are internally generated within the home or business. Twenty percent(20%) are the result of neighboring customers.Fifteen percent(15%) arethe result of natural phenomenon such as lightning, tree limbs, and animal contacts. And five(5%) are normal utility operations such as the operation of a circuit breaker.
13
Power Disturbance
Any deviation from the nominal value (or from some selected thresholds based on load tolerance) of the input ac power characteristics.
When monitoring electric power, with many devices, thresholds are established to define what constitutes a power disturbance. Often, these thresholds are determined by the type of problem that is occurring. For example, if a certain piece of equipment is failing, device specific thresholds will be used (i.e. voltage limitations and noise limitations from the manufacturer) to establish the definition of a power disturbance.
What is Power / Voltage Disturbance / Quality?
Definitions
“Any power problem manifested in voltage, current, or frequency deviations that results in the failure or misoperation of customer equipment."
Power Quality
The concept of powering and grounding sensitive equipment in a manner that is suitable to the operation of that equipment.
NOTE—Within the industry, alternate definitions or interpretations of power quality have been used, reflecting different points of view. Therefore, this definition might not be exclusive, pending development of a broader consensus.
What is Power / Voltage Disturbance / Quality?
Definitions
“Any power problem manifested in voltage, current, or frequency deviations that results in the failure or misoperation of customer equipment."
14
Power Quality
A point of view of an equipment designer or manufacturer might be that power quality is a perfect sinusoidal wave, with no variations in the voltage, and no noise present on the grounding system. A point of view of an electrical utility engineer might be that power quality is simply voltage availability or outage minutes.
Finally, a point of view of an end-user, is that power quality or “quality power”is simply the power that works for whatever equipment the end-user is applying. While each hypothetical point of view has a clear difference, it is clear that none is properly focused.
What is Power / Voltage Disturbance / Quality?
Definitions
“Any power problem manifested in voltage, current, or frequency deviations that results in the failure or misoperation of customer equipment."
Power Quality
An environment where the equipment designer or manufacturer clearly states the equipment needs, and the electrical utility engineer indicates the system delivery characteristics, and the end-user then predicts and understands the equipment operational disturbances that will likely be encountered on a yearly basis is a better scenario. This allows a cost justification to be performed by the end-user to either improve equipment operation by installing additional components or improve the electrical supply system through installation of additional, or alteration of existing components.
What is Power / Voltage Disturbance / Quality?
Definitions
“Any power problem manifested in voltage, current, or frequency deviations that results in the failure or misoperation of customer equipment."
15
What is Power / Voltage Quality?Definitions
IEEE Power Quality StandardsIEEE SCC-22: Power Quality Standards Coordinating Committee
IEEE 1159:Monitoring Electric Power Quality
IEEE 1159.1: Guide For Recorder and Data Acquisition Requirements
IEEE 1159.2: Power Quality Event Characterization
IEEE 1159.3: Data File Format for Power Quality Data Interchange
IEEE P1564:Voltage Sag Indices
IEEE 1346:Power System Compatibility with Process Equipment
IEEE P1100: Power and Grounding Electronic Equipment (Emerald Book)
IEEE 1433: Power Quality Definitions
IEEE P1453: Voltage flicker
IEEE 519: Harmonic Control in Electrical Power Systems
Padrões De Qualidade de Energia
Perspective GlobalDefinições, Índices, Medições, Comprovações, etc.Filosofia: Níveis de Compatibilidade (sistema / equipamento, fontes de desvios)Implementação Prática
16
Os Padrões de Qualidade existem num contexto global e, são sujeitos a função objetivo dos sistemas de suprimento elétrico, o qual é providenciar suprimento adequado, tecnicamente compatível, confiável, e econômico da energia elétrica.
Uma Perspective Global
Padrões de Qualidade de Energia
© 2004 Power Standards Lab. All rights reserved.
Electricity Price - World-wide
Source: © 2004 EPRI
Uma Perspective Global – Preço
17
© 2004 Power Standards Lab. All rights reserved.
Major Power Outages Around the World
Source: © 2004 EPRI
Uma Perspective Global - Apagões
© 2004 Power Standards Lab. All rights reserved.
Distribution Reliability Index – SAIFI
Source: © 2004 EPRI
Uma Perspective Global - Confiabilidade
18
PSL
© 2004 Power Standards Lab. All rights reserved.
Distribution Reliability Index – SAIDI
Source: Mark Lauby, EPRI, Fukuoka. © 2004 EPRI
Uma Perspective Global - Confiabilidade
© 2004 Power Standards Lab. All rights reserved.
Voltage sags can have the same effect as outages for industrial customers.
Source: Mark Lauby, EPRI, Fukuoka. © 2004 EPRI
SARFI70
Uma Perspective Global - Impacto
19
Teorias e Princípios de Ética e Padrões Sociais
Aplicados a Utilização de Padrões de Qualidade
Lei Natural – Consistente com a funcionalidadeUtilitarianismo – Maior valor para a comunidadeFormalismo – Independente de Interesses
Autonomia - Liberdade de EscolhaNão – maleficência – Evitar problemasBeneficência – Promover melhoramentoJustiça – Retribuir infratores
Virtude – Ação responsável em situações difíceis e complexas
Heresias Morais
Aplicados a Utilização de Padrões de Qualidade
Subjetivismo – Muito complexo ...Emotivismo – Deve ser a culpa dele ...Positivismo – Tudo vai dar certo no fim ...Pragmatismo – Com tanto que funcione...Otimismo - Nada vai acontecer ...Relativismo - Não se pode dizer nada ...Ceticismo – Essas medições não valem...Egoísmo – É o problema dele ...
Virtude – Ação responsável em situações difíceis e complexas
20
Mas o Porquê de Padrões?
•Estabelece Expectativas
• Melhora a Compatibilidade Entre Sistemas
• Permite Melhor Comunicação Entre Engenheiros de Potencia e Engenheiros de Equipamento
O Porquê de Problemas Com Padrões
• Escrito por seres humanos. Erros
• Aplicados por seres humanos. Erros.
•Exemplo: IEEE 519 aplicado a terminais de equipamento
• Desencorajam inovações .
• Normas contem suposições não claramente definidas.
• Normas podem tornar-se peso para alguns.
• Normas tolhem / impedem inovações.
21
Compatibility level
Assessed level
Disturbance magnitude
time
Equipment immunity test levels
Utility planning levels
Perspectivas: Social, Ética, Etc.
IEC, IEEE, CIGREXIndustria
Uma Perspective GlobalEstabelecendo Padrões
Generation
Transmission
PQ Performance Parameters
Planning
Operation
Economic Feasibility
DistributionConsumersConsumers
22
Accessibility
Security
Continuity
Reliability
Voltage (Power) Quality
Performance Parameters
The Big, Integrated, Macro Picture
Uma Perspective GlobalEstabelecendo Padrões
Compatibility Levels
Customer System Impact Limits
System Performance Expectations
Measurement and Assessment
Methods
Customer System and Equipment
Immunity Requirements
Equipment PQ Limits
System Solutions and their implementation
Customer and equipment solutions
to limit impact on system
Customer and equipment solutions
for immunity improvement
23
Desenvolvimentos de Padrões
International Standards Groups – IEC (mostly SC 77A)– CENELEC – CIGRE (AG 4.1) UIE, UNIPEDE, CIRED.....
Standards Groups in North America– IEEE (mostly PES & IAS)– ANSI, CSA
– UL, NEMA, NEC, NIST.....
IEC Power Quality Standards
Numbering61000-1-X - Definitions and methodology 61000-2-X - Environment (e.g. 61000-2-4 is compatibility levels in industrial plants) 61000-3-X - Limits (e.g. 61000-3-4 is limits on harmonics emissions) 61000-4-X - Tests and measurements (e.g. 61000-4-30 is power quality measurements) 61000-5-X - Installation and mitigation 61000-6-X - Generic immunity & emissions standards
IEC SC77A: Low frequency EMC Phenomena -- essentially equivalent of "power quality" in American terminology
TC 77/WG 1: Terminology (part of the parent Technical Committee)SC 77A/WG 1: Harmonics and other low-frequency disturbances SC 77A/WG 6: Low frequency immunity tests SC 77A/WG 2: Voltage fluctuations and other low-frequency disturbances SC 77A/WG 8: Electromagnetic interference related to the network frequency SC 77A/WG 9: Power Quality measurement methods SC 77A/PT 61000-3-1: Electromagnetic Compatibility (EMC) - Part 3-1: Limits -Overview of emission standards and guides. Technical Report
24
IEEE Power Quality StandardsIEEE SCC-22: Power Quality Standards Coordinating Committee IEEE 1159:Monitoring Electric Power Quality
IEEE 1159.1: Guide For Recorder and Data Acquisition Requirements IEEE 1159.2: Power Quality Event Characterization IEEE 1159.3: Data File Format for Power Quality Data Interchange
IEEE P1564:Voltage Sag Indices IEEE 1346:Power System Compatibility with Process Equipment IEEE P1100: Power and Grounding Electronic Equipment (Emerald Book) IEEE 1433: Power Quality Definitions IEEE P1453: Voltage flicker IEEE 519: Harmonic Control in Electrical Power Systems IEEE Harmonics Working Group
Single-phase Harmonics Task Force IEEE P519A Guide for Applying Harmonic Limits on Power Systems Interharmonics Task Force Harmonics Modeling and Simulation Task Force Probabilistic Aspects of Harmonics Task Force
Surge Protective Devices CommitteeSeventeen sub-committee links can be found at the "Sub-committee pages" link... IEEE P446: Emergency and standby power IEEE P1409: Distribution Custom Power IEEE P1547: Distributed Resources and Electric Power Systems Interconnection
Other Power Quality Standards
UIE: International Union for Electricity Applications
CENELEC: European Committee for Electrotechnical Standardization
UNIPEDE: International Union of Producers and Distributors of Electrical Energy
ANSI: American National Standards Institute
ANSI C62: Guides and standards on surge protection
ANSI C84.1: Voltage ratings for equipment and power systems
ANSI C57.110: Transformer derating for supplying non-linear loads
CIGRE: International Council on Large Electric Systems
CIRED: International Conference on Electricity Distribution
CBEMA / ITIC curve
25
Two Basic Types of PQ Variations
Steady State PQ– Voltage regulation– Unbalance– Frequency– Harmonics– Flicker
Disturbances– Outages and interruptions– Voltage sags (rms variations)– Transients
IEC – Estrutura Geral
Part 1: General (IEC Pub 61000-1)– fundamental principles, definitions, terminology
Part 2: Environment (IEC Pub 61000-2)– description, classification and compatibility levels
Part 3: Limits (IEC Limits 61000-3)– emission and immunity limits, generic standards
Part 4: Testing and measurement (IEC Pub 61000-4)– techniques for conducting
Part 5: Installation and mitigation (IEC Guide 61000-5)– installation guidelines, mitigation methods and devices
26
Working Group 1 – Harmonics and other Low frequency Disturbances. Focus on limits and methods of measurement for harmonics and interharmonics.
Working Group 2 – Voltage Fluctuations (flicker) and other Low Frequency Disturbances. Develops limits for voltage fluctuations caused by end user equipment and methods of measurement as appropriate. This working group will be working on an update to the document on reference impedances that can be used for evaluatingthe impact of equipment on the system.
Working Group 6 – Low Frequency Immunity Tests. Develops testing procedures for evaluating equipment immunity from power quality variations.
Working Group 8 – Electromagnetic Interference Related to the Network Frequency. This group is addressing the full range of power quality phenomena on the network and the interaction issues with consumers.
Working Group 9 – Power Quality Measurement Methods. Currently developing IEC 61000-4-30, an overall guide defining the requirements for power quality monitoring equipment.
IEC – Atividades
CIGRE Study Committee C4 Input Para Normas
JWG C4.1.01 Power Quality General Aspects E. Gunther (US) 1977 2006 TF C4.1.02 Voltage Dip Prediction Tools J.M. Vlasco (SP) 2003 2005 JWG C4.1.03 Emission Limits for Disturbing Loads G. Beaulieu (CA) 2003 2006 JWG C4.1.04 Power Quality Indices and Objectives G. Beaulieu (CA) 2000 2004 JWG C4.1.05 Technical Performance Benchmarking Guidelines M. McGranaghan (US) 2005 2008 JWG C4.1.06 PQ Instrument Test Protocols E. Gunther (US) 2005 2007 JWG C4.1.07 Economic Framework for Voltage Quality JL Gutierrez Iglesias (ES) 2005 2008 TF C4.1.08 Review Of Flicker Objectives - HV,MV&LV Systems A. Detmar (DE) 2005 2007 TF C4.1.09 Emission Assessment Techniques E de Jaeger (BE) 2005 2007 WG C4.1.10 Dip Immunity of Equipment - Customer Installations To be appointed 2005/6 2008 ActiveCompletedScope & proposed convener reviewed and approved by Study Committee C4Scope under preparation
27
Recentes Desenvolvimentos
CIGRE C4.07 (C4.1.04) – Recommended Indices and Benchmarking Results for PQ and ReliabilityIEC 61000-4-30 provides specifications for pq monitoring and provides the basis for IEEE coordinationIEC 61000-4-15 provides flickermeter specifications. It was amended to include 120 volt and 100 volt lamps and has been adopted by IEEE 1453.IEC 61000-3-2 provides harmonic limits for equipment. This approach has not been adopted in North America.IEC 61000-3-6 and 61000-3-7 provide guidelines for harmonic and flicker emissions from customer facilities. They are undergoing revision in parallel to a revision of IEEE 519.
Some important recent developments
CIGRE C4.07 (C4.1.04) – Recommended Indices and Benchmarking Results for PQ and ReliabilityIEC 61000-4-30 provides specifications for pqmonitoring and provides the basis for IEEE coordinationIEC 61000-4-15 provides flickermeter specifications. It was amended to include 120 volt and 100 volt lamps and has been adopted by IEEE 1453.IEC 61000-3-2 provides harmonic limits for equipment. This approach has not been adopted in North America.IEC 61000-3-6 and 61000-3-7 provide guidelines for harmonic and flicker emissions from customer facilities. They are undergoing revision in parallel to a revision of IEEE 519.
28
IEEE Standards Coordinating
1159 – Measurements1453 – Flicker519 – Harmonics1564 – Voltage Sags…
Voltage sags and interruptions –What is needed?
Common method of measurement and assessment (indices)Benchmark performance as a function of system characteristicsStatistical methods of characterizing performance (1564)Application guidelines for performance improvement options (e.g. IEEE 1409)Equipment performance standards (e.g.IEC 61000-4-11, 4-34)Economic evaluation with a system perspective
29
Possible Problems
Caution SevereDistortions
DangerousLevels
NormalLevels
A B C D E F G RTL0
1
Norm
alB
elowN
ormal
Over
Heating
Very
Hot
Below
Norm
alab
cd
e
Equi
pmen
t Ma l
fun c
tion
Mag
nitu
de $
Pha
se
An g
le
Individual Harmonics (Vh)Equipment Malfunction
Fuzzy - Color Code Criteria
No Problem
Caution
Possible Problems
Imminent Problems
Normas Flexíveis e Criativas
( ) ( ) ( )( ) ⎟⎟
⎠
⎞⎜⎜⎝
⎛ −=
kUrefkUrefkUkRTL ,0max
Relative Trespass Level (RTL)
Uk - measured or calculated harmonic voltage
Uref - harmonic voltage limit (standard or particular equipment)
k - harmonic order
2 4 6 8 10 12 140
2
4
6
88
0
RTL k
132 k
0 0.05 0.10
2
4
6
88
0
RTL k
.10 Uk
30
( )∑=
=50
2
22
kkRTLHDD
Harmonic Distortion Diagnostic Index
Exponent = 2 or 4 ?k = 50 or less ?
Total Harmonic Distortion Diagnostic Index
⎟⎠⎞
⎜⎝⎛ −
=Vthd
VthdVTHDTHDD ,0max
VTHD - total harmonic distortion measure or calculated
Vthd - total harmonic distortion limit
31
2 4 6 8 10 12 140
0.02
0.040.03
1103−×
Uk
Urefk
132 k
Uk
0.0010.0150.0010.030.0010.0150.0010.0090.0010.020.0010.015
:= Urefk
0.010.010.010.010.010.010.010.010.010.010.010.01
:=
RTL
2
2
34
56
78
9
1011
1213
0
0.50
20
0.50
0
01
00.5
=
T
Example 1
VHDD2
13
k
RTLk( )2∑=
:=
VHDD 2.398=
VTHD2
13
k
Uk( )2∑=
⎡⎢⎢⎣
⎤⎥⎥⎦
100⋅:=
VTHD 4.541=
THDD max 0VTHD Vthd−( )
Vthd,⎡⎢
⎣⎤⎥⎦
:=
THDD 0=
Example 1
Vthd=5%
32
Example 2
2 4 6 8 10 12 140
0.01
0.02
0
Uk
Urefk
132 k
Uk
0.0010.010.0010.0
0.0010.010.0010.010.0010.010.0010.01
:= Urefk
0.010.010.010.010.010.010.010.010.010.010.010.01
:=
RTL
223
456
789
101112
13
00
000
000
000
0
=
VHDD2
13
k
RTLk( )2∑=
:=
VHDD 0=
VTHD2
13
k
Uk( )2∑=
⎡⎢⎢⎣
⎤⎥⎥⎦
100⋅:=
VTHD 2.249=
THDD max 0VTHD Vthd−( )
Vthd,⎡⎢
⎣⎤⎥⎦
:=
THDD 0=
Example 2
Vthd=5%
33
Example 3
2 4 6 8 10 12 140
0.02
0.040.05
1 10 3−×
Uk
Urefk
132 k
Uk
0.0010.0010.0010.020.0010.020.0010.0010.0010.050.0010.04
:= Urefk
0.010.010.010.010.010.010.010.010.010.010.010.01
:=
RTL
2
2
34
5
6
7
89
10
11
12
13
0
00
1
0
1
00
0
4
0
3
=
Example 3
VHDD2
13
k
RTLk( )2∑=
:=
VHDD 5.196=
VTHD2
13
k
Uk( )2∑=
⎡⎢⎢⎣
⎤⎥⎥⎦
100⋅:=
VTHD 7.006=
THDD max 0VTHD Vthd−( )
Vthd,⎡⎢
⎣⎤⎥⎦
:=
THDD 0.401= Vthd=5%
34
0 5 10 15 20 25 300
0.01
0.020.025
0.01
Uk
Urefk
292 k
Uk
0.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.01
:= Urefk
0.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.010.01
:=
RTL
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
=
VHDD2
n
k
RTL k( )2∑=
:= VTHD2
n
k
U k( )2∑=
⎡⎢⎢⎣
⎤⎥⎥⎦
100⋅:= Vthd 5:=
VHDD 0= VTHD 5.292=
THDD max 0VTHD Vthd−( )
Vthd,⎡⎢
⎣⎤⎥⎦
:= THDD 0.058=
Example 3
Example 1: HDD>0, THDD=0Example 2: HDD=0, THDD=0Example 3: HDD>0, THDD>0Example 4: HDD=0, THDD>0
Pattern
35
•Indices may provide additional insight on diagnosing harmonic problems
•HDD provides information on individual harmonic distortion compatibility
•THDD provides information on total harmonic distortion compatibility
•Reference values can be adjusted to individual equipment or standard
•When equipment is more sensitive to waveform distortion use HDD
•When equipment is more sensitive to heating effects THDD use THDD
Steady State Grades of Power Quality
Reduced level of quality that may be the result of particular equipment connected at the site but is still adequate for this equipment operation. This level may cause problems of heating or misoperation for some equipment (e.g. motors).C - Industrial
Basic quality that should be adequate for the great majority of equipment without causing problems. This quality is designed to be consistent with the majority of industry standards.B - Basic
Highest quality for equipment with strict voltage quality and voltage regulation requirements, conditioned quality.A - Premium
DescriptionGrade
36
Qualidade de Energia – Regime Permanente – Valores Básicos
São Satisfatórios ???
Voltage THD - 95% of 10 minute values - IEC 61000-4-78%Harmonic Distortion
Max deviation for motor starting or other switching occurrences more than once per week (min single cycle rms voltage)10%Motor Starting
Pst 95% over one week period<1.0Flicker
99% 10 minute values in one week<2%Unbalance
99% 10 minute values in one week+/- 10%Voltage Regulation
Evaluation MethodRequirementCategory
Qualidade de Energia
Solução Integrada
• Matching Customer Needs with Utility Services.
• Establish An Open Environment
• Optimize Economics
37
Normas devem ajudar a determinação de níveis de compatibilidade ótima com objetivos de desempenho e econômicos
Optimizing the Investments in Reliability and Quality
Level of Quality and Reliability Provided
Cos
t
Objective - Determine optimum investment strategies from global cost perspective
Customer PQ & reliability impact costs and investment
Supply system investments to improve PQ and reliability
PowerQuality A B C dPd= + +∫∫ ( ) $A - Electric parametersB - Economic ParametersC – Society’s Infrastructure
• A Qualidade de Energia continuará a ser um aspecto de grande importância dentro da operação de sistemas elétricos, mas deve ser visto como parte de um contexto bem mais amplo do que a pureza analítica e platônica de condições ideais (abaixo a senoide pura).• Normas precisam ser contextualizadas dentro de cada sistema e comunidade.•Participação ampla de todos setores é essencial para obtenção de normas mais úteis.•Encontros como esse devem ocorrer mais freqüentemente para assegurar o sucesso desses desenvolvimentos.•Geração Distribuída irá contribuir sensivelmente para o aumento da complexidade e importância desse tópico. Precisamos nos preparar.
38
What is Power / Voltage Quality?
What is Power / Voltage Quality?
39
http://www.ece.umr.edu/courses/w03/ee304/Def/transients.htm
http://www.ece.umr.edu/courses/w03/ee304/Def/shortduration.htm
http://www.ece.umr.edu/courses/w03/ee304/Def/longduration.htm
http://www.ece.umr.edu/courses/w03/ee304/Def/interrup.htm
http://www.ece.umr.edu/courses/w03/ee304/Def/waveform.htm
http://www.ece.umr.edu/courses/w03/ee304/Def/flicker.htm
http://www.ece.umr.edu/courses/w03/ee304/Def/frequency.htm
What is Power / Voltage Quality?
Why are we concerned with PQ?
$$$$$$$$$$$$$$$$$$$$$$$$$$$
Cost Categories
Lost production
Scrap
Restart costs
Labor
Repair and replacement costs
Process inefficiency
40
Why are we concerned with PQ?
Costs Cost
Intangible Costs
Increased Business Risk
Lost Business Opportunity
Microeconomics Framework for Assessing PQ Benefit Cost
The Utility Perspective
The following block diagrams describe the proposed steps for the microeconomics of the cost assessment of power quality problems. The structure or framework is based on a four step procedure.
Step 1 - Assessment of power Disturbance Cost. This should be done based on the type of industry/process, etc. and type of disturbance. Boundary conditions should be specified to determine the actual effect of power disturbance. Direct and indirect costs, varying from production loss to reduced efficiency, should then be calculated. Step 2 - Assessment of the Cost of Mitigation. This step should compute the total cost of mitigation varying from initial monitoring and analysis to final testing of performance. Alternative options should be suggested. Step 3 - Assessment of Benefit due to Mitigation. This step should compute the direct/indirect benefits plus energy savings due to mitigation. Step 4 - Financial Computation of the Benefit-Cost - With the input from steps 1 to 3, the final assessment of the benefit-cost and payback period should be determined for the different options.
Why are we concerned with PQ? Costs Cost
41
Why are we concerned with PQ? Costs Cost
kWh not Distributed Investiment in PQuality Legal
Assessing the PQ Costfor The Utility
Total Cost Utility
Assessing The Costof Mitigation for The Utility
Total Cost of Mitigation
Level of Quality
Types of Disturbance
ImpulsesDistortions, etc.
Filtering, Power Conditioners, Motor-generator, etc.,
B
Why are we concerned with PQ? Costs Cost
42
Market Effects Return on Investiment Reduced Losses
Assessing the PQ Benefitfor The Utility
Total Benefit - Utility
Improved EfficiencyNew Customers
C
Why are we concerned with PQ? Costs Cost
Cost of Disturbance Cost of Mitigation
Financial Analysis
Option 1 Option 2
Net Benefit
Payback
A B B
Benefit due to Mitigation
Option 1 Option 2
C C
Why are we concerned with PQ? Costs Cost
43
I n t e g r a t e d M a c r o e c o n o m i c / F i n a n c i a l A n a l y s i s
Benefit CostSensitive Customer
Benefit Cost Benefit CostDistuurbing Customer Utility
Cost Benefit CurvesSensitive Customer
Cost Benefit Curves Cost Benefit CurvesDisturbing Customer Utility
Integrated Macroeconomic/Financial Analysis
Cost
Quality
Cost
Quality
Cost
Quality
Invst
Payback
Invst
Payback
Invst
Payback
Why are we concerned with PQ? Costs Cost
How does the deregulated environment affects PQ?
Reduced Investment (Operation, Maintenance, etc)
Responsibilities
Power Electronics Penetration (T, D, and User-End)
Distributed Generation (DG): Trends, Interconnection Issues
Regulating Control / Coordination Issues
Randomly Varying Sources (PV, Wind)
What is New in PQ?Instrumentation, Modeling, etc., Initiatives
44
Challenges
Distribution and Power Quality Strategic - EPRI – Roadmap - Difficult Challenges
Improved Transmission Capacity, Grid Control, and Stability
Maintain and Strengthen Portfolio of Generation Options
Accelerated Development of Carbon Capture and Storage Technologies
Achieving Low/Zero Emissions of Key Pollutants
Improved Power Quality and Reliability for Precision Electricity Users
Increasing Robustness, Resilience, and Security of Energy Infrastructure
Creation of the Infrastructure for a Digital Society
Advances in Enabling Technology Platforms
Exploiting the Strategic Value of Storage Technologies
High Efficiency End Uses of Energy
Maintaining and Improving Water Availability and Quality
Global Electrification
Development of Electricity-Based Transportation Systems
Harmônicos
Philosophy – Harmonics need to be monitored to assure that the system does not see levels of distortion that are unacceptable. The harmonic limits are established in a simplified manner, and they allow for flexibility. It is suggested that the limits should be specified in ranges indicating acceptable, requiring investigation, and unacceptable conditions. The basic system must also consider the possibility of resonance conditions due to capacitors.
Management Considerations – The system must do periodic monitoring of various locations to verify that levels are acceptable. The agent must react to situations where the harmonics are approaching unacceptable levels. Objectionable situations are to be handled on a case-by-case basis using a knowledge of the load characteristics and a study.
Technical Implementation – Various international standards exist for harmonics, but the system requires a simplified approach to allow for flexibility of various instruments. The main goals of the instrumentation are simply to flag areas of concern. When specific problems are found, then advanced instrumentation and harmonics penetration studies will be used to evaluate the best course of action.
45
Harmônicos
Breve Introdução
Nonlinear loads, such as power electronic equipment, produce non-sinusoidal current waveforms when energized with a sinusoidal voltage. They inject currents at harmonic (integer multiple of the fundamental frequency) frequencies into the system. Harmonic currents, and the voltage distortion they create as they flow through the system impedance, can reduce equipment operating reliability and service life (0-100th harmonic).
Harmônicos
Breve Introdução
Modelagem (Sources)
-Current injection model.
-Frequency- or time-domainNorton equivalent circuit model.
-Harmonic coupling matrix model.
-Time- or frequency-domaindevice model used with frequency-domain network model.
-Time-domain model.
46
Harmônicos
Breve Introdução
Modelagem (System and Loads)
Sensitivity Analysis
Harmônicos
Breve Introdução
Modelagem (System and Loads)
47
Harmônicos
Breve Introdução
Modelagem (System and Loads)
Harmônicos
Breve Introdução
Modelagem (Solution)
Harmonic Power Flow Solutions:
In this analysis, the harmonic sources are also represented as current sources. However, their magnitudes and phases are updated using an iterative scheme based on detailed (voltage-dependent) harmonic source models. Inter-phase coupling of the harmonic-sources can be modeled with good accuracy. The harmonic iteration scheme solves the network one frequency at a time. The calculated nodal voltages are then used to update the current source model. In theory, simultaneous solutions of all harmonic orders like those used in the HARMFLO program can also be developed for the multiphase analysis, but the algorithm would be extremely complex.
48
Harmônicos
Breve Introdução
Modelagem (Solution)
Harmonic Power Flow Solutions:
In this analysis, the harmonic sources are also represented as current sources. However, their magnitudes and phases are updated using an iterative scheme based on detailed (voltage-dependent) harmonic source models. Inter-phase coupling of the harmonic-sources can be modeled with good accuracy. The harmonic iteration scheme solves the network one frequency at a time. The calculated nodal voltages are then used to update the current source model. In theory, simultaneous solutions of all harmonic orders like those used in the HARMFLO program can also be developed for the multiphase analysis, but the algorithm would be extremely complex.
Harmônicos
Breve Introdução
Modelagem (System and Loads)
Geração Distribuída
Fontes e Aspectos Probabilísticos
49
Harmônicos
Breve Introdução
Aspectos Probabilísticos
Time-Varying Nature of Harmonics
THDV
0.0%
0.4%
0.8%
1.2%
2/2 2/3 2/4 2/5 2/6 2/7 2/8
THDV
The causes of variations are the continuous changes in system configurations, linear load demands and operating modes of non linear loads
An Inevitable Reality
“The variations generally have a random character and the only way one can describe the behavior of such characteristics is in statistical terms”
Harmonic Indices
Probability Functions
Statistical measures
Summation Laws
Harmonic Impedances
Time-dependent Limits
Aspects to be Considered
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
50
Harmonic phases angles are randomly varying:
Im(V5)
Re(V5)
Im(V23)
Re(V23)
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
Marginal probability density function
-4 -3 -2 -1 0 1 2 3 40
0.1
0.2
0.3
0.4
fX
X
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
51
Time ranges involved (hours, day, etc.)
Multimodal patterns
Time interval between readings and the window width
Application to estimate the thermal effects of harmonics
The time factor is completely lost and the same pdf can correspond to different time varying harmonics, with consequent different thermal responses of electrical components
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
Example: pdf of the 5th Harmonic Voltage given that its amplitude is greater than or equal to 6%
0
0.5
1
1.5
2
V5
fV5
5V 6%V
Conditional probability density functions
to reduce the volume of data to be analyzed
to represent extreme events
to introduce intriguing new statistical measures
00.5
11.5
22.5
33.5
44.5
V5
f*V5
6%V 5V
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
52
standard deviation σ
95% probability value PC95%
99% probability value PC99%
maximum value MAX
The IEC 1000-3-6 and EN 50160 refer to PC95% and MAX
average value µStatistical Measures
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
Harmonic pdfs with the same PC95% and MAX can cause different effects
µ = 0.70 σ = 0.27 µ = 0.27 σ = 0.16
x0.95 x0.95
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
53
hh
αj
αhjh UU ∑=
∑=j
hjhjh IkIαh = summation exponent dependent on harmonic order
Two semi-empirical approaches have been proposed in literature in order to allow easy and fast evaluation in practical applications such as standards
Summation Laws
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
The laws should be continuously verified to take into account:
new electronic components
the presence of unbalanced conditions
the influence of the network supplying the harmonic sources
Summation Laws
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
54
Usually, the network harmonic impedances are assigned with reference to deterministic values and without taking into account the correlation with disturbing currents
Harmonic Impedances
The network harmonic impedance has statistical behavior due to:
• network component uncertainties
• load variability (including power factor correction capacitors)
• supply system variability
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
Equipment
THDV
0.0%
0.4%
0.8%
1.2%
2/2 2/3 2/4 2/5 2/6 2/7 2/8
THDV
Up to now the studies on harmonic effects mainly (but not only) refer to static distortions
Studies are needed on harmonic effects when time-varying distortion is applied
Time-Dependent Limits
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Time-Varying Nature of Harmonics
55
IEEE 519-1992 introduced the concept of probability distribution plots to characterise variations in harmonic levels.
•A reasonable method of using these types of plots to evaluate harmonic levels would be to compare the steady state harmonic limits with the measured harmonic level that is not exceeded 95% of the time (the 95% probability point). This is consistent with the evaluation of compatibility levels in IEC standards.
•In order to further develop this topic the IEEE Probabilistic Aspect of Harmonics Task Force is preparing a proposal for the Std. 519 in which the time-varying nature of harmonics voltages are considered in the establishment of the limits. •Any limits on the short duration harmonic levels should be based on the possible impacts of these harmonic levels. Effects such as metering error and equipment ageing are the accumulated result of harmonic levels over time. Other effects include the sensitive electronics to short burst of high harmonic levels or certain types of waveform distortions.
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Proposition For IEEE 519
Recommendations are being prepared, with suggested procedures and values to be discussed by the members of the Std. 519 Revision Task Force. These recommendations will be consistent with the 519 Application Guide.
Probability distributions and short-term disturbance limits shall be established.
The “continuous limits” could be taken as, for example, the 95% probability limit.
The values will be established based on the impact of short-term harmonics on different equipment.
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Proposition For IEEE 519
Recommendations are being prepared, with suggested procedures and values to be discussed by the members of the Std. 519 Revision Task Force. These recommendations will be consistent with the 519 Application Guide.
Probability distributions and short-term disturbance limits shall be established.
The “continuous limits” could be taken as, for example, the 95% probability limit.
The values will be established based on the impact of short-term harmonics on different equipment.
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Proposition For IEEE 519
56
T H D B i n s ( % )
Freq
uenc
y
0
5
1 0
1 5
2 0
2 5
3 0
3 5
4 0
4 5
5 0
0 . 7 0 . 8 0 . 9 1 1 . 1 1 . 2 1 . 3 1 . 4 1 . 5 1 . 6 1 . 7 1 . 8 1 . 9
0 . 0 0 %
1 0 . 0 0 %
2 0 . 0 0 %
3 0 . 0 0 %
4 0 . 0 0 %
5 0 . 0 0 %
6 0 . 0 0 %
7 0 . 0 0 %
8 0 . 0 0 %
9 0 . 0 0 %
1 0 0 . 0 0 %S i t e 1 0 9 2 T H D H i s t o g r a mJ u n e 1 9 - J u n e 2 6 , 1 9 9 2
C o u n t = 3 0 5M i n i m u m = 0 . 7 3 9
M a x i m u m = 1 . 9 4 9R a n g e = 1 . 2 1 1
M e a n = 1 . 4 0 6M e d i a n = 1 . 4 8 9
S t a n d a r d D e v i a t i o n = 0 . 3 1 8S t a n d a r d E r r o r = 0 . 0 1 8 2
V a r i a n c e = 0 . 1 0 1S k e w n e s s = - 0 . 5 2 1
K u r t o s i s = - 0 . 7 7 7
Table 1 – Short-Term Limits Short-Time
Limits
Duration of Disturbance
A x Continuous Limits
a1 sec < T < b1 sec
B x Continuous Limits
b1 sec < T< a2 min
C x Continuous Limits
a2 min < T< b2 min
THD V
0.0%0.4%0.8%1.2%
2/2 2/3 2/4 2/5 2/6 2/7 2/8
THDV
Harmônicos
Breve Introdução
Aspectos Probabilísticos - Proposition For IEEE 519
Histogram and cumulative distribution of THD levels for a week long measurement.
138kV bus voltage THD as a function of time
Harmônicos
Breve Introdução
Aspectos Probabilísticos
57
Drawing of cumulative distribution (Ttotal) and the maximum duration and maximum duration of individual burst (Tmaximum) for a harmonic measurement. The curve also includes a conceptual limit for short term harmonic levels.
Harmônicos
Breve Introdução
Aspectos Probabilísticos
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Monitoring and Analysis to Evaluate Compliance
Monitoring to characterize system performance
Monitoring to characterize specific problems
Monitoring as part of an enhanced power quality service
58
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Monitoring Program Components
Power quality and/or energy demand monitors
Data storage
Download computers
Web or company Intranet server
Some viewgraphs used with permission of Mark McGranaham and
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Why monitor power systems?
Benchmark system performance levels (understand power quality that can be expected, Allows option for expanded power quality services)
Reliability reporting (reliability defined based on customer impacts)
Prioritize system investments
Information service for customers
Identify and solve problems
Improve system operations and reliability
59
Example of SystemMonitoring Concept
Transmission
DistributionSubstation
SubstationMonitoring
System
CustomerMonitoring
System
CustomerMonitoring
System
MonitoringDatabase
Local Network
Data Collection Data Collection
Database Management/Local Data Analysis
CorporateIntranet
Internet/World Wide Web
Power Quality/Energy
Information Service
Power Quality/Reliability
Performance andData Analysis
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Harmônicos
Breve Introdução
Important components for a system Open architecture
Systems should allow integration of different technologies within utility and customer networks
Power Quality Data Interchange Format (PQDIF)IEEE Standard 1159.3
Web-based access to the informationIntelligent applicationsAutomated reporting functions
60
Harmônicos
Breve Introdução
Benchmarking – First we need to understand existing PQ and reliability
Reliability is more than SAIFI and SAIDI for many customers.
We have to understand the expected system performance before establishing regulations or developing contracts.
Harmônicos
Breve Introdução
Documenting performance for continuous PQ variations
Voltage regulationUnbalanceFlickerHarmonics
Compatibility level
Assessed level
Disturbance magnitude
time
Equipment immunity test levels
Utility planning levels
61
Harmônicos
Breve Introdução
The concept of compatibility levels
Harmônicos
Breve Introdução
Monitoring to improve operations & reliability
Fault locationCapacitor bank performance assessment Voltage regulator performance assessment DG performance assessment Cable fault identifier Arrester failure identifierTransformer loading assessment
This is where the real financial return for system monitoring comes in
62
Example –Identifying harmonic problems
Power factor correction equipment can result in resonances that magnify harmonic levels. The monitoring system can identify and alarm based on these conditions before they cause equipment failures.
-600
-400
-200
0
200
400
600
0.00 0.02 0.04 0.06 0.08
Example Voltage Waveform showing Voltage Distortion Problem
Vol
tage
( V
)
Time ( s)
0
20
40
60
80
100
120
0 2 4 6 8 10
Harmonic Components of the Voltage Waveform
Vol
tage
(%)
Harmonic Component
Harmônicos
Breve Introdução
Monitoring to improve operations & reliability
Prioritizing new applicationsFaults
Fault locationFault typeCauses of faultsTrends of fault locations indicating problemsIncipient faults for cable and arrester failures
Protective Device OperationsTimingCoordination problems (fuses, reclosers, sectionalizers, etc.)Misoperation identification
BreakersPole spanTimingDuties and maintenance requirement
Harmônicos
Breve Introdução
Monitoring to improve operations & reliability
63
Capacitor operations
Capacitor location
Identification of blown fuses or unbalanced operation
Severity of transients
Breaker restrikes
Operation of transient control technology (e.g. synchronous closing)
Magnification concerns
Impacts on customers
Transformer evaluation
Loading issues
Harmonic impacts
Regulator performance and maintenance requirements
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Distributed generation applications
Energy monitoring
Operation of protection systems and coordination with power system protection
Harmonic impacts
Impacts on voltage regulators
Power factor issues
System performance assessment and control
Power factor control
Harmonic resonance identification and control
Feeder loading
Voltage regulation
Harmônicos
Breve Introdução
Monitoração and Instrumentação
64
Prioritizing new interfaces – Integrating with current systems
Smart RelaysSchweitzerABB…
Reclosers (Cooper)Digital Fault Recorders
HathawayRochester…
Transformer MonitorsSCADA Systems…
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Web interface to the substation -monitoring system
Harmônicos
Breve Introdução
Monitoração and Instrumentação
65
We can manage the data for you www.powermonitoring.com
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Harmônicos
Breve Introdução
Monitoração and Instrumentação
66
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Harmônicos
Breve Introdução
Monitoração and Instrumentação – System Configuration
67
Harmônicos
Breve Introdução
Monitoração and Instrumentação – Data Analysis
Harmônicos
Breve Introdução
Monitoração and Instrumentação – Analytical Methods
68
•Performance benchmarking is very important but difficult to justify economically
•Power system monitoring can have benefits in improving operational reliability and efficiency – these benefits can easily justify the monitoring system
•Reduces time to locate and repair faults
•Identification of equipment problems (possibly avoiding outages and improving reliability)
•More efficient scheduling
•Don’t cut too many corners – build the system so that it can take advantage of new technologies and applications (detailed waveform recording, communication systems, open architecture, etc.)
•Should be Internet-based for interfacing, ease of use, and ongoing support
Harmônicos
Breve Introdução
Monitoração and Instrumentação
Harmônicos
Breve Introdução
Normas / Recomendações (IEEE 519)
Current Distortion Limits (in % of IL) for General Distribution Systems (120-69,000 V)
Current Distortion Limits (in % of IL) for General Sub-Transmission Systems (69,001-161,000 V)
69
Current Distortion Limits (in % of IL) for General Transmission Systems (>161,000 V)
Voltage Distortion Limits (in % of V1)
Harmônicos
Breve Introdução
Normas / Recomendações (IEEE 519)
GENERAL PROCEDURE FOR APPLYING HARMONIC LIMITS
Step 1: Choose the point of common coupling,
Step 2: Characterize the harmonic-producing loads,
Step 3: Assess power factor correction needs,
Step 4: Calculate expected harmonics at the PCC,
Step 5: Design and implement solutions (if needed), and
Step 6: Verify performance with measurements.
Harmônicos
Breve Introdução
Normas / Recomendações (IEEE 519)
70
2.5 > Wi >0.5
Harmônicos
Breve Introdução
Normas / Recomendações (IEEE 519)
1. Modeling of network components such as overhead lines, cables, transformers, etc. (The analyst has some flexibility in selecting the level of detail needed; sensitivity studies should be considered to determine which degrees of detail can be avoided in any particular study.)
2. Modeling of various nonlinear loads including predefined models and the capability for user-defined models based on measured or typical data. (It is left to the analyst to determine what degree of sophistication is required, especially if time-domain simulation techniques are to be used.)
3. Modeling of power factor correction capacitors should be “built in” to any software being considered. (The representation of the equivalent capacitance is the most important requirement; other details are somewhat insignificant for limit compliance evaluations.)
4. Modeling of utility system equivalents should be straightforward. (In an advanced study, the analyst should consider the capability to represent the frequency dependence of network equivalents.)
Harmônicos
Breve Introdução
Normas / Recomendações (IEEE 519)
71
519 Revisions
Update sponsors– PES T&D Committee– IAS IPC CommitteeIntroduction– Establish applicability of 519– Demonstrate PCC via single-line diagramDefinitions– Update according to content modifications as
appropriateChapter 4 “Harmonic Generation”eliminated– Include bullet list of “causes” in introduction
72
Chapter 5 “System Response Characteristics” eliminated– Add cautions in introduction regarding the
possibility of resonances creating compliance problems
– Also caution that customer-side modifications that create undesirable resonances are customer’s responsibility to fix
This is part of the “shared responsibility” flavor of 519
Chapter 6 “Effects of Harmonics”significantly reduced (to general information) and moved to an annex– Update TIF based on Std. 776-1992 (R2003)– Include this material in 519.1 “next time” and
then remove from future 519 revisions
Chapter 7 “Reactive Power Compensation and Harmonic Control” eliminated– Information is either well understood now,
widely documented in other literature, or not necessary for a “limits” document
73
Chapter 8 “Analysis Methods” mostly eliminated– Provide up-to-date bibliography– Move Section 8.5 “Notching” into annex– Use Figure 8.7(a) (or similar) in introduction
to define PCC and related conceptsChapter 9 “Measurements” completely re-written– Endorse IEC 61000-4-7 (2ed) and 4-30– Provide sufficient material to understand
meter outputs and on-line statistics– Harmonize with 1159 as necessary
Chapter 10 “Recommended Practices for Individual Consumers”– Make sure PCC is clear in introduction and
again here519 is an interface standard, not an equipment standard
– Section 10.3 moved to annexUpdate with additional info from 519-1981
– Section 10.4: remove “value added” for higher pulse order
If 5th, 7th (11th, 13th, etc.) are below 25%, then user gets credit (1.5x, 1.75x, 2.0x, etc) regardless of how the <25% levels were obtained
74
Chapter 10 “Recommended Practices for Individual Consumers”– Section 10.4: Make sure that definition of load
current (IL) is clear– Current limit tables
Justify limits for generation to avoid the “negative load” conceptDo not eliminate even-order limitsMake each table a full page with common and consistent footnotes, explanations, and disclaimers…Interharmonics should not create objectionable lamp flicker or other undesirable or damaging effects
– Interharmonic limit curve based on flicker in annex
Chapter 10 “Recommended Practices for Individual Consumers”– Express limits using 4-7 & 4-30 measurement
protocol95th percentile of the 10 minute values less than the given limits over a period of one week99th percentile of the 10 minute values less than 1.5 times the given limits (over one week)99th percentile of the 3 second values less than 2.0 times the given limits over one (each) day
– Section 10.4.1 “Transformer Heating” reduced to a table footnote
75
Chapter 10 “Recommended Practices for Individual Consumers”– Section 10.4.2 “Probabilistic aspects”
eliminatedCaptured using 4-7 & 4-30 protocols
– Section 10.5 “flicker” eliminated
Chapter 11 “Recommended Practices for Utilities”– Put chapter in front of “customer limits”
chapterEmphasize that voltage problems are what are trying to be avoidedCurrent limits depend on system and economics
– Section 11.2 “addition of harmonics”eliminated
– Section 11.3 “short duration” eliminatedCaptured using IEC protocol
– Section 11.4 eliminated
76
Chapter 11 “Recommended Practices for Utilities”
– Section 11.5 “voltage limits” focused on compatibility concept
Refer to “effects” material that was moved to annex
– Limit table (Table 11.1)Add new row for <1kV (5% & 8%)Remind about PCC, especially for <1 kV case95th percentile of 10 minute values less than limit values over one week99th percentile of 3 second values less than 1.5 times the limit over one dayAdd new limits for h>13 for <1kV and 1-69 kV rows
– 0.5 times existing limits for these higher orders
Chapter 11 “Recommended Practices for Utilities”– Possible additional modification
Changing rows from 69-161 kV and >161 kV to 69-230 kV and > 230 kV???
– Section 11.6 “interference with communications” moved to annex with other TIF material
77
Chapter 12 “Recommended Practices for Utilities”– Almost all 519.1 material– Capture philosophy in introduction
New Structure– Expanded introduction focusing on why 519 is needed
(effects) and where it is to be applied (PCC definition)Very limited information on “what is required” and “how” to apply it
– This is the domain of 519
– Measurement protocol (should majority be in annex?)IEC 61000-4-7 & 61000-4-30
– Voltage distortion limits– Current distortion limits– Multiple annexes with “good, old” and “good, new”
material– Expanded bibliography
78
Harmônicos
Breve Introdução
Índices Harmônicos
Harmônicos
IEC 61000-3-6 Voltage Harmonic Planning Levels
79
At the PCC, system owners or operators should limit harmonic voltages as follows:
• Daily 99th percentile very short time (3 second) values should be less than 1.5 times the values given in Table 5-1.
• Weekly 95th percentile short time (10 minute) values should be less than the values given in Table 5-1.
All values should be in percent of the rated power frequency voltage at the PCC. Table 5-1 applies to voltage harmonics whose frequencies are integer multiples of the power frequency.
Interharmonics – IEEE 519For harmonic components which are not integer multiples of the power frequency, system owners or operators should limit the weekly 95th percentile short time harmonic voltages to the values shown graphically in Figure 5-1 up to 120 Hz. Depending on the voltage level, the integer harmonic limits in Table 5-1 may be more restrictive and should be used. The portions of the 0-120 Hz range where the integer harmonic limits of Table 5-1 are more restrictive are appropriately labeled in Figure 5-1. The numerical values corresponding to Figure 5-1 are given in Table 5-2 for voltages at the PCC less than 1 kV. It is important to note that the recommended voltage interharmonic limits are based on lamp flicker assessed using the measurement technique described in IEEE Std. 1453 and IEC Std. 61000-4-15. These voltage interharmonic limits correlate with a short-term flicker severity Pst value equal to 1.0. The recommended limits in Figure 5-1 are not based on the effects of interharmonics on other equipment and systems such as generator mechanical systems, signaling and communication systems, and filters. Due consideration should be given to these effects and appropriate limits should be developed on a case-by-case basis using specific knowledge of the supply system and connected user loads.
80
81
COMPARISON AND CONTRAST: IEEE VS. IEC LIMITS
A. Driving principle
The basic premise of the IEEE harmonic limits is a shared responsibility between utility and customer. All customers are granted some reasonable share of the system’s ability to absorb harmonics.
If voltage distortion problems exist with all customers within their current limits, the utility is responsible for taking action to restore voltage quality.
The IEC approach is based on assigning current limits that are more rigorously derived from voltage quality targets and is designed to insure that if all customers are within their individual limits, then system-level voltage quality problems will not exist.
COMPARISON AND CONTRAST: IEEE VS. IEC LIMITS
B. Voltage harmonic limits
Both standards provide voltage harmonic limits. The IEEE voltage harmonic limits are constant across all frequencies whereas the permissible voltage harmonic magnitudes decrease with frequency in the IEC.
C. Current harmonic limits
Current harmonic limits are the centerpiece of IEEE 519-1992, but the limit values are only loosely correlated with system voltage targets. The IEC avoids giving current harmonic limits in a general sense, preferring that these limits be more rigorouslyderived based on voltage limits and system impedance characteristics.
82
COMPARISON AND CONTRAST: IEEE VS. IEC LIMITS
D. Even-order harmonics
IEEE 519-1992 does not specifically address even-order harmonics for voltage (all voltage harmonics are treated equally), but does recommend that even-order current harmonics be limited to 25% of the values for corresponding odd-order harmonics. The IEC specifically addresses evenorder voltage harmonics and appears to allow greater evenordercurrent harmonic emission (depending on system impedance characteristics) than IEEE.
E. Non-characteristic harmonics
Both IEEE and IEC consider harmonics in a general sense, without regard to characteristic harmonics generated by certain types of equipment (e.g., six-pulse rectifiers generating characteristic harmonics at the 5, 7, 11, 13, etc., frequencies). IEEE does, however, offer a “credit” for higherpulseorder equipment provided that non-characteristic harmonics (for the equipment in question) remain low.
COMPARISON AND CONTRAST: IEEE VS. IEC LIMITS
F. Time-varying harmonics
IEEE suggests that the current harmonic limits may be exceeded by 50% for short periods of time. IEC rigorously addresses time-varying aspects of harmonics by utilizing percentiles (e.g., 95th and 99th) for very short time (3 second) and short time (10 minute) aggregated measurements. In addition, IEC provides a multiplyingfactor by which harmonic limits may be increased when considering very short time emissions.
G. Interharmonics
IEEE 519-1992 does not address interharmonics. IEC 61000-3-6 addresses interharmonic voltage limits by recommending a frequency-independent limit of 0.2% so as to avoid problems with lamp flicker and ripple control, signaling, and communications equipment.
83
IEEE P1547.1 Standard for Conformance Tests Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems
Scope This standard specifies the type, production, and commissioning tests that shall be performed to demonstrate that the interconnection functions and equipment of a distributed resource (DR) conform to IEEE Standard P1547.
Purpose Interconnection equipment that connects distributed resources (DR) to an electric power system (EPS) must meet the requirements specified in IEEE Standard P1547. Standardized test procedures are necessary to establish and verify compliance with those requirements. These test procedures must provide both repeatable results, independent of test location, and flexibility to accommodate a variety of DR technologies
Standards currently under development are:•P1547 - Draft Standard for Interconnecting Distributed Resources with Electric Power Systems •P1547.1 - Draft Standard for Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems •P1547.2 - Draft Application Guide for IEEE P1547 Draft Standard for Interconnecting Distributed Resources with Electric Power Systems •P1547.3 - Draft Guide for Monitoring, Information Exchange and Control of DR Interconnected with EPS
84
Harmônicos
Debates – Mesa Redonda
Harmônicos
Contratos e Seguros
Harmonic Distortion.IEEE 519-1992 describes the responsibility between the customer and the distribution system supplier in controlling harmonic distortion levels. The distribution company is responsible for the voltage distortion and the customer is responsible for harmonic currents being created by nonlinear loads within the facility.
Involvement of Multiple Entities
Transmission Provider
Local Distributor
Independent Power Producers
Retail Marketers, Energy Companies
End User
85
Harmônicos
Contratos e Seguros
Requirements for Power Quality Contracts
· Reliability/power quality concerns to be evaluated
· Performance indices to be used
· Expected level of performance (baseline)
· Penalty for performance outside the expected level and/or incentives for performance better than the expected level (financial penalties,performance-based rates, shared savings, etc.)
· Measurement/calculation methods to verify performance
· Responsibilities for each party in achieving the desired performance
· Responsibilities of the parties for resolving problems
Harmônicos Contratos e Seguros
Power Quality Contracts in a Restructured Competitive Electricity Industry, Barry W. Kennedy – Bonneville Power, Administration, Portland, OR 97209, Mark McGranaghan – Electrotek Concepts, Knoxville, TN 37923 -http://www.dranetz-bmi.com/pdf/contracts.pdf
86
Harmônicos
Contratos e Seguros
Harmônicos
- Aspectos Econômicos / Custos
87
Debates – Mesa Redonda
Questions for Discussion and Deliberation
What is Really Power Quality? Evaluate Definitions
How Should Harmonics Be Treated (Rigid / Flexible Approach)?
How should the probabilistic nature be incorporated?
What about costs?
How does the deregulated environment affects PQ?
Topics for future research and development.
Other Questions and Issues?
Example – What was causing this event?
Debates – Mesa Redonda
Quiz
88
More clues from the current waveform
Debates – Mesa Redonda
Quiz
Problem -- found before failure!
Transformer tap changing mechanism
Debates – Mesa Redonda
Quiz
89
Distúrbios na Tensão-Breve Introdução
-Definições (Sags, Swells, Flutuações de Tensão, etc)
-Instrumentação
Voltage sags are typically characterized by the minimum rms voltage and the duration of the sag.
Distúrbios na Tensão
-Breve Introdução
- Definições (Sags, Swells, Flutuações de Tensão, etc)
- Instrumentação
Benchmarking voltage sag performance
Basis for evaluating ongoing system performanceBasis for evaluating economics of power quality improvement
options Basis for implementing PQ-based contractsBasis for attracting customers that are concerned about PQ levelsCan be basis for standards
90
Distúrbios na Tensão
- Breve Introdução
- Definições (Sags, Swells, Flutuações de Tensão, etc)
- Instrumentação
Voltage sag performance on medium voltage systems
Benchmarking Project SARFI-70 SARFI-80 SARFI-90
Power Grid - Singapore 7.8 10.6 13.2
United States (DPQ Project) 17.7 27.3 49.7 Europe – Mixed Systems (UNIPEDE) 44.0 NA 103.1 Europe – Cable Systems (UNIPEDE) 11.0 NA 34.6
South Africa (NRS-048 indicative levels) 47.0 78.0 153.0
Distúrbios na Tensão
-Sources of Voltage Sags and Interruptions
-Estimating the Voltage Sag Performance
-Area of Vulnerability
-Equipment Sensitivity
-Magnitude
-Magnitude and Duration
-Other than Magnitude and Duration
-Transmission System Performance
-Utility Distribution Systems Sag Performance Evaluation
91
Voltage SagsVoltage sags and other system disturbances are emerging as important power quality concerns, due chiefly to the economic problems that they cause for consumers. Voltage sags can be caused by faults on the distribution systems or on the transmission system (basic grid). It is important to understand how faults on the basic grid contribute to the overall voltage sag performance experienced by an end user.
F a u l t s o n O w n C i r c u i t
2 3 %
F a u l t s o n P a r a l l e l C i r c u i t s
4 6 %
F a u l t s o n T r a n s m i s s i o n
S y s t e m3 1 %
Example of the breakdown of voltage sag performance at an end user location illustrating the relative causes of voltage sags between the transmission system and the distribution system.
Voltage Sags and Momentary Interruptions
With regards to voltage sags, the basic principles are:
Philosophy – The system should track and evaluate faults on the system that cause voltage sags on the basic grid. There is a need for a methodology both to measure sags and to calculate voltage sag performance from a historical data base of the system faults, in order to get benchmarking data for the system and inform the results to the customers/agents.
Management Considerations – The system is able to track the number of faults (per 100 km of line) as the most meaningful control action. This is similar to the continuity issue. It can also provide information to customers/agents. This is the best measure of the transmission system performance since it is not dependent on the system topology.
Technical Implementation – Issues regarding the specific characterization procedures for voltage sags, the monitoring equipment requirements, the location of monitors, and the analysis of the data are all being studied in the international community at this time
92
SARFI
The “System Average RMS (Variation) Frequency Index” or “SARFI” was developed by EPRI to describe voltage sag performance. It has been adopted by several U.S. utilities, and also utilities in the U.K. and Singapore. It is recommended for the basic grid in Brazil.
The SARFI index is usually expressed as a function of equipment sensitivity (or minimum phase magnitude). For example a
SARFI70 Indicates the annual number of voltage sags where the retained voltage (on the minimum phase) is less than 70%. This is equivalent to an event when the voltage is 30% below the nominal (prefault voltage).
SARFI90 Indicates the annual number of voltage sags where the retained voltage (on the minimum phase) is less than 90%. This is equivalent to an event when the voltage is 10% below the nominal (prefault voltage).
SARFICBEMA Indicates the annual number of voltage sags where magnitude and duration of the event is outside the CBEMA equipment sensitivity tolerance curve.
What are the monitor requirements? What is the required sampling rate for the waveform (e.g. 16 samples per cycle)?
The general requirements are that the monitor must have good time synchronization. It should establish a “floating nominal” for the triggering of events – given the nature of the system. It must cross-trigger all phases during an event. It should aggregate the phase measurements. It should provide the data in a format (IEEE 1159.3) that allows software programs to exchange and analyze the data.
The instrument could have as few as 16 samples per cycle to do a good job of trending rms voltage versus time. This would be enough for voltage sag characterization. However, many utilities find that the waveforms from the sag help identify the cause of the fault or the performance of the system protection operation. A faster sampling rate (say 128 sample per cycle) will give this extended information.
93
What are the central data analysis requirements?
1That the data is secure. Data storage and archiving are important.
2That the data is accessible. The internet/intranet technologies are important for access.
3That the data is up to date. Data retrieval from the instrument must be considered, especially if there is a wide system event when all of the sites will be reporting.
4That the data is summarized in a meaningful way. This process may or many not be automated.
5That system alarms or e-mails or pages can be sent. Many instruments will natively have this capability in the future.
Should voltage sag limits be developed for the system?
This is not recommended. There have been a number of attempts todevelop limits for voltage sag performance that can be applied to the power system at both transmission and distribution levels. These are very problematic to develop and they have limited benefit to the customer. Any limits that must be developed will necessarily be based on the worst performing parts of the system. This will result in a very pessimistic assessment of the voltage sags to be expected.
Guidelines for the transmission system in terms of expected fault performance of transmission lines and transmission systems is a much better idea. These guidelines would be expressed as expected numbers of faults/100 km/year.
94
What are the important parameters affecting voltage sag performance?
Fundamentally, voltage sag performance is affected by end user equipment sensitivity. From a utility perspective, the performance is affected by the nature and location of faults. The pattern of generation at the time of the fault is also a factor in voltage sag levels. The number of phases involved in the fault is very important. Sag shifting transformations (such as delta-wye transformer banks) between the fault and the measurement point will change the characteristics of the voltage sag.
Estimating voltage sag performance based on fault performance levelsThe voltage sag performance for a given customer facility will depend on whether the customer is supplied from the transmission system or the distribution system. For a customer supplied from the transmission system, the voltage sag performance will depend on only the transmission system fault performance. On the other hand, for a customer supplied from the distribution system, the voltage sag performance will depend on the fault performance on both the transmission and distribution systems. Voltage sag performance at a system location can be estimated using records of the system fault performance and accurate short circuit models of the system. The analysis starts with the determination of the “area of vulnerability”. This is the area where faults on the system can cause voltage sags that may result in equipment misoperation. Short circuit programs such as ASPEN One Liner can calculate the voltage throughout the system resulting from faults around the system, essentially providing the area of vulnerability information.
Example of the area of vulnerability concept.
95
TLine Disturbances Vs Voltage Level
0 2 4 6 8 10 12 14
69 kV
110-138 kV
220-230 kV
440-500 kV
Events per 100 mile / Year
Example of fault performance statistics (from recent survey of transmission system fault performance levels from around the world).
Example of summarizing expected voltage sag performance at a system interface point.
96
0
10
20
30
40
50
60
70
Num
ber o
f Eve
nts
per Y
ear
Interruptions < 50% < 60% < 70% < 80% < 90%Minimum Sag Voltage
Expected Voltage Sag Performance
Distribution
Transm ission
Example of summarizing voltage sag performance at typical SARFI threshold values.
Example of characterizing voltage sag events with actual waveforms.
97
Example of characterizing voltage sag events with rms vs. time plots for the event.
Example of characterizing voltage sag events by summarizing magnitude and duration of events with respect to equipment sensitivity (ITIC curve).
98
0 to 10
30 to 40
60 to 7090 to 100
1 cy
c2
cyc
3 cy
c4
cyc
5 cy
c6
to 1
0 cy
c10
to 2
0 cy
c20
to 3
0 cy
c30
to 6
0 cy
c
050
100150200250300350400450500
Cou
nt
Magnitude
Duration
Magnitude Duration RMS Events
Example of characterizing voltage sag performance using a three dimensional chart showing the count of events with magnitude and duration.
S a g T y p e DO n e - p h a s e f a u l t , p h a s e s h i f t
S a g T y p e BO n e - p h a s e f a u l t , n o p h a s e s h i f t
S a g T y p e CT w o - p h a s e f a u l t , p h a s e s h i f t
S a g T y p e ET w o - p h a s e f a u l t , n o p h a s e s h i f t
S a g T y p e AT h r e e - p h a s e f a u l t
Characterization of voltage sag events according to the sag type. The magnitudes of the voltage on each phase and the phase shift must be determined for each voltage sag event in order to determine the sag type. This information helps to identify the fault location and the type of fault that caused the sag.
99
Managing system disturbances
It is not recommended to establish limits for voltage sags. Limits have the effect of establishing mediocre performance for the entire system, and not to improve performance. Rather it is recommended that the system be monitored for the causes of faults, and those cause addressed by maintenance action. The lines that have a high incidence of faults be investigated for ways to improve their fault performance. The equipment that has a higher failure rate be replaced or new specifications may be developed. This process involves the establishment of a database to detect these problems, and aggressive maintenance action to resolve those causes.
Some useful tools of the PQMS for implementing the management system include the following:
Trends of voltage sag performance over time.Reports of voltage sag performance across the system.Correlation of voltage sag events with important system parameters and system conditions (e.g. lightning events, breaker operations, equipment failures, tree contacts, other causes, etc.)Summaries of voltage sag performance by region, voltage level, short circuit capacity, etc.
Example of trends illustrating voltage sag performance over time (SARFI indices).
100
Comparison of UI Substation's SARFI 70 performance of the last 12 months vs. their 3 year average
0
2
4
6
8
10
12
14
16
ALLINGS CROSSIN
G
ANSONIA
ASH CREEK
BARNUM
BROADWAY
CONGRESS
EAST SHORE
ELMWEST
HAWTHORNE
INDIA
N WELL
JUNE ST.
MILL RIV
ER 1
MILL RIV
ER 2
MILVON
MIX A
VENUE
NORTH HAVEN
OLD TOWN
PEQUONNOCK
QUINNIPIA
C
SACKETT
TRAP FALLS
WATER ST.
WOODMONT
BAIRDA
BAIRDB
CONGRESS NEW
Substation Name
Num
ber
of ti
mes
whe
n Su
bsta
tion'
s Bus
Vol
tage
was
less
th
an 7
0% o
f Nom
inal
per
365
day
s
SARFI70 from Distribution Events 3 years average SARFI70 from Trasmission Events 3 years averageSARFI70 from Distribution Events during the last four Quarters SARFI70 from Trasmission Events during the last four Quarters
Example of comparing voltage sag performance at different substations. The chart shows the breakdown of events caused by transmission faults vs. distribution faults and compares the three year average performance with the last year’s performance for each substation.
ENV SENOKO INCINERATOR
SENOKO
QUEENSTOWN
LABRADOR
LABRADOR
ADMIRALTY WEST
PULAU BUKOM
PIONEER SECTOR
UPPER JURONG
GUL CHANNEL
PIONEER RD
TUAS P/S
NORTHERN TUAS
S ERAYA CHEMICALS
PANDAN
PULAU SERAYA
PULAU SERAYA S/H
PULAU SAKRA
PULAU AYER CHAWAN
NEW MOBIL
PULAU AYER MERBAU I
PULAU AYER MERBAU II
PULAU MERLIMAU
JURONG HARBOUR
JURONG PIER
JURONG PIER
JURONG WEST
INTERNATIONAL RD
CHOA CHU KANG
UPPER JURONG
JLN BAHAR
NTU
BUONA VISTA
NUS AYER RAJAH
BUKIT PANJANG
AYER RAJAH
JURONG EAST
CLEMENTI
BUKIT BATOK
CHOA CHU KANG
DUNEARN
CHOA CHU KANG NEW TOWN
MARSILING
MANDAI
230kV SUPPLY ZONES
OCTOBER 1999
ALJUNIED
MARINA CENTRE
KALLANG BASINKG JAVA
OUTRAM
NEW ARMENIAN ST
SOMERSET
STAMFORD RD
ΣΕΝΤΟΣΑ
TK BLANGAH
ΠΥΛΑΥ ΒΡ ΑΝΙ
KG BAHRU
ST JAMES
GRANGE RD
HENDERSON
ANN SIANG HILL
TRAFALGAR
GEORGE ST
RAFFLES
CRAWFORD
CHANDERRD
SUNTEC CITY
THOMSON
BRIGHT HILL
KALLANG BASIN
KG JAVA
TOA PAYOH
SERANGOON NORTH
ANG MO KIO
BISHAN
MARINE PARADE
TG RHU
YASIN
PAYA LEBAR
AIRPORT
EUNOS
PAYA LEBAR
HOUGANG
AIDA
BEDOK
TAMPINES
TAMPINES
YISHUN
ADMIRALTY WEST
CHANGI AIRPORT
CHANGI
TAMPINES NEW TOWN
PASIR RIS
PAYA LEBAR
SOXAL
NISM
TAMPINES AVE 10
PANDAN LOOP
TUAS SOUTH AVE 3
WOODLANDS LINK
TUAS INCINERATOR
SenokoSARFI 90 – 11.2SARFI 80 – 6.1SARFI 70 – 4.6
Paya LebarSARFI 90 – 13SARFI 80 – 12.1SARFI 70 – 7.1
TampinesSARFI 90 – 13.2SARFI 80 – 10.9SARFI 70 – 9.2
Kallang BasinSARFI 90 – 13.2SARFI 80 – 11SARFI 70 – 6.6
Kg JavaSARFI 90 – 12.9SARFI 80 – 10.7SARFI 70 – 6.5
LabradorSARFI 90 – 14.7SARFI 80 – 11.1SARFI 70 – 6.8
Ayer RajahSARFI 90 – 13.4SARFI 80 – 10.9SARFI 70 – 8.0
P SerayaSARFI 90 – 13.3SARFI 80 – 11SARFI 70 – 9.5
Jurong PierSARFI 90 – 13.7SARFI 80 – 10.7SARFI 70 – 10.6
Upp JurongSARFI 90 – 12.9SARFI 80 – 11SARFI 70 – 6.5
Choa Chu KangSARFI 90 – 13.3SARFI 80 – 10.8SARFI 70 – 10.7
22kV SARFI MAP
Example of presenting expected voltage sag performance as SARFI indices for different parts of the system (SARFI Map).
101
We recommend that an annual report of expected voltage sag performance (and reliability performance) be developed that can be used by distribution companies and other agents to incorporate into overall expected voltage sag performance at customer locations. Seminars and workshops should be held on an annual basis to discuss various topics related to power quality concerns:
--Problems being experienced by customers as a function of specific types of power quality variations.
--Costs of power quality impacts.
--New solutions available to help improve performance (with economics).
--System performance expectations.
--System interaction issues.
Distúrbios na Tensão
-Fundamental Principles of Protection
102
Quality of Supply Guarantee
Outage– Complete loss of ac power (voltage
less than 10% of nominal) for 1 minute or more.
– Used past five years of outage data to obtain an average
Utility Payments to Customer
Every outage over the target number– Target: ½ an outage every year– after four years, one outage every four
years– rolling twelve month period
Payments will vary by facility– $2,000 - $326,000 per outage
103
DefinitionsCustomer “definition” of an outage– Includes voltage sags
Magnitude vs Duration Scatter Plot with CBEMA Overlays
10-1 100 101 102 103 104 0
25
50
75
100
125
150
Duration (Cycles)
Voltage Magnitude (%)
Total Events:Events Below:Events Above: Below CBEMA: Above CBEMA:
31 31 0 3 0
Voltage sag (dip) agreement
Had to monitor the system for two years before voltage sags could be included Had to determine how to count events such as circuit reclosing, multiple phases, or minor events
104
Electric utility deregulationRe-regulation ? – Privitisation– Corporatization
Financial returns instead of the “public good”Need for minimal standards (benchmarking)
3 - OverallProtection
Inside Plant
CONTROLS
MOTORS
OTHER LOADS
32
1
2 - ControlsProtection
1 - EquipmentSpecifications
INCREASING COST
UtilitySource
4
4 - Utility Solutions
Feeder or Group of Machines
Where is the best solution?
105
Some significant international benchmarking efforts
DPQ Project - USA– 300 sites, 24 utilities, 2 years of
monitoring
UNIPEDE Benchmarking Project -Europe– 85 substation sites, European utilities, 1
year of monitoring
Benchmarking for development of NRS 048 Standard - South Africa– 200 sites 2 years of monitoring
Utility participantsBoone Electric CooperativeChattanooga Power BoardCincinnati Gas & Electric CompanyDelmarva Power & Light CompanyDuke Power CompanyEast Kentucky Power CooperativeElizabethan Electric SystemEmpire District Electric CompanyFlorida Power CorporationGeorgia Power CompanyGibson County Electric MembershipHouston Lighting & PowerIllinois Power Company Kansas City Power & Light CompanyLong Island Lighting CompanyLos Angeles Department Of Water & PowerMassachusetts Electric CompanyNortheast Utilities ServicePacific Gas & Electric CompanyPublic Service Electric & Gas CompanyRochester Gas & Electric CorporationSierra Pacific CompanySnohomish Public Utility District #1Western Resources
Multi-phase, multi-year projectwhich involved 24 EPRI member utilities.
106
Voltage sags
Focus now on voltage sags because these are the most important power quality variations affecting industrial customers.
DPQ voltage sag performance
Average Yearly Rate Substations Only
Feeders Only
Feeder Average
Interruptions V<10% 3.65 5.08 4.58Sags 10%<V<90% 43.60 46.22 45.31Sags and Interruptions 47.25 51.30 49.90
Note: these results arebased on the minimumvoltage and one minuteaggregation.
Sag and Interruption Rate Magnitude Histogram
0.00
0.25
0.50
0.75
1.00
1.25
0 to
5
5 to
10
10 to
15
15 to
20
20 to
25
25 to
30
30 to
35
35 to
40
40 to
45
45 to
50
50 to
55
55 to
60
60 to
65
65 to
70
70 to
75
75 to
80
80 to
85
85 to
90
RMS Voltage Magnitude (%)
Sags
and
Inte
rrup
tions
per
Site
pe
r 30
Day
s
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
Cum
ulat
ive
Freq
uenc
ySag and Interruption RateCumulative Frequency
All Sites, One-Minute Aggregate Window
107
UNIPEDE benchmarking results -EuropeCable Systems
Mixed Systems
Summary comparison of major benchmarking projects
SARFI – System average rms frequency indexSARFI-70 – The expected annual number of
voltage sags with a retained voltage of less than 70% of nominal
108
Categories of system voltage sag performance
Category 1 - Best Systems or Systems with Low Fault Exposure– SARFI-70 less than 10– SARFI-90 less than 30
Category 2 - Typical or Average Systems– SARFI-70 between 10 and 30– SARFI-90 between 30 and 100
Category 3 - Rural Systems or Systems with High Fault Exposure– SARFI-70 greater than 30– SARFI-90 greater than 100
Using simulations to study performance
109
Newman
Blackwater
West MesaB-A
NortonLos Alamos
Ojo
Santa Fe
Albuquerque
Roswell
Las CrucesDeming
Clovis
Arroyo
Sandia
Luna
FarmingtonFour Corners
Gallup AmbrosiaPlains (PGT) Tap
345kV230kV
Area of vulnerability<90% voltage retained
345kV230kV
West MesaB-A
NortonLos Alamos
Santa Fe
Albuquerque
Roswell
Las CrucesDeming
ClovisSandia
FarmingtonFour Corners
Gallup
Area of vulnerability<70% voltage retained
110
Expected annual voltage sag profile
Voltage Sags(Percent Normal Voltage)
Events Per
Year
0
5
10
15
20
25
30
35
40
<50% <60% <70% <80% <85% <90%
46kV
115kV
230kV
345kV
1.85.0
10.315.2
23.3
33.9Fault
Location
Voltage Class Median Performance (Faults/100mi/year)
345/500kV 1.8 230kV 4.0 115/138kV 6.5 46/69kV 18
Key parameter – transmission line fault performance
111
Panel Session PN13Non-periodic Currents:
Causes, Effects and Identification
Interharmonics in Power Systems
Interharmonics in Power Systems
DefinitionStandardsSourcesImpactsSolutions
112
Interharmonics -Definition
IEC-61000-2-1 defines Interharmonics as:
“Between the harmonics of the power frequency voltage and current, further frequencies can be observed which are not an integer of the fundamental. They can appear as discrete frequencies or as a wide-band spectrum”
Standards and Working Groups
IEC 61000-4-7 - MeasurementsIEEE Task Force on InterharmonicsIEEE 519 - under revision - adds interharmonicsCigre 36.05 - Voltage Quality Working Group
113
IEC Harmonic / InterharmonicMeasurement Standard: IEC 61000-4-7
Number of cycles to sample chosen to provide 5 Hz frequency bins– 10 Cycles for 50 Hz Systems– 12 Cycles for 60 Hz Systems
Grouping concept– Harmonic factors calculated as the square root of the sum of
the squares of the harmonic bin and two adjacent bins.– Interharmonic factors calculated as the square root of the
sum of the squares of the bins in between the harmonic bins (not including the bins directly adjacent to the harmonic bin).
Frequency Bin Grouping
114
Frequency Bin Grouping
Interharmonic Sources
Arc furnaces CycloconvertersPower line carrier communicationsPWM power electronic systemsInteraction of controls and power system components
115
Example Case Where dc Arc Furnace Caused Unacceptable Flicker Levels
Converter control problems result in increased interharmonic generationSystem resonance magnifies the interharmonic component (186 Hertz)Result is 6 Hertz modulation that causes light flicker over a wide area
Example System One Line Diagram for Harmonic and Flicker Evaluations
Customer
Customer
116
Frequency Response with Initial Filter Design
0 200 400 600 800 0
25
50
75
100
125
150
Frequency (Hz)
Driving Point Impedance (Ohm)
186 hertz
Voltage at the 26 kV Bus
117
Current at the 26 kV Bus
Effect of the Rolling MillModern rolling mills will typically use cycloconverters. They also generate significant interharmonic components.Example waveform and spectrum used for design purposes:CASE41>S35K3A-FEED3A(Type 9)
270 280 290 300-2000
-1000
0
1000
2000
Time (mS)
Current (A)
Max:Min:Avg:Abs:RMS:CF :FF :
1536.08 -1498.02 821.937 1536.08 940.961 1.63245 1.14481
DERIVED>S35K3A-FEED3A(Type 9)
0 6 12 18 24 0
10
20
30
40
Frequency (Hz pu)
Current (A)
Freq :Fund :THD :TID :TD :RMSh :RMSi :RMSfh:RMS :ASUM :TIF :IT :
1 966.448 6.40455 0 6.40455 61.8967 0 968.428 968.428 1349.88 146.679 142048
118
Impacts
Similar to impact of harmonic distortion– Heating– Altered/multiple zero crossing– Telecommunications interference
Unique impacts– Light flicker– Torsional oscillation excitation
Light Flicker due to Interharmonics
119
SolutionsFix control problems to reduce level of interharmonic generation.Non-characteristic harmonics and interharmonics must be considered in the filter design for dc arc furnaces and other interharmonic producing loads.Resonances created by the filters in parallel with the system inductance can magnify interharmonic components causing high distortion and flicker.Damping should be included in filter designs to avoid interharmonic problems.
Conclusions
Interharmonics have always been around, they are just becoming more important and visible.Power electronic advances are resulting in increasing levels of interharmonic distortion.Traditional filter designs can result in resonances that make interharmonic problems worse.Light flicker is the most common impact.Measurement is difficult, but standards make them possible and the results comparable.
120
Procedimentos para Campanhas de Medição de Indicadores de
QEE e Ensaios de Instrumento de Medição
239
MÉTODO DE AVALIAÇÃO UFU
Nenhum instrumento recebeu apenas conceitos B/E nos módulos;
Apenas 1 instrumento apresentou todos conceitos R/I nos módulos;
Cinco instrumentos apresentaram apenas 1 conceito R/I nos cinco módulos;
Constatações Quanto aos Resultados da Avaliação
121
MÉTODO DE AVALIAÇÃO UFU
Número de instrumentos com conceitos B/E nos vários módulos:• Harmônica: 12• Desequilíbrio: 7• Flutuação: 3• VTCD: 9• Veficaz: 20
Número de instrumentos com conceitos B/I nos vários módulos:• Harmônica: 9• Desequilíbrio: 14• Flutuação: 18• VTCD: 12• Veficaz: 1
Constatações Quanto aos Resultados da Avaliação
MÉTODO DE AVALIAÇÃO UFU
Combinando-se módulos de VTCD e Veficaz (avaliação via SMF), resulta o seguinte número de instrumentos com conceito B/E:• VTCD / Vef: 9
Combinando-se os módulos de Harmônicas, Desequilíbrio e Flutuação (avaliação via campanha), resulta os seguintes números de instrumentos com conceitos B/E:• H / D / F: 1• H / D: 5• H / F: 3• D / F: 1
Constatações Quanto aos Resultados da Avaliação
122
MÉTODO DE AVALIAÇÃO PROF. PAULO RIBEIRO
Critérios Utilizados na Avaliação (Preliminar):
• Eliminação Simples (incluindo todos os testes)O instrumento será aprovado caso apresente em todos os testes do módulo erro inferior ou igual a 10% (o valor de 10% procura para acomodar inúmeras condições de imprecisão, variações nos proticolos de medicao, etc. ).
• Média Notas Desempenho (baseado critério UFU)O instrumento será aprovado caso obtenha desempenho médio no módulo considerado B ou E.
Constatações Quanto aos Resultados da Avaliação
MÉTODO DE AVALIAÇÃO PROF. PAULO RIBEIRO
Critérios Utilizados na Avaliação (Preliminar):
• Eliminação Simples (regime permanente)Nesta avaliação adotou-se o mesmo critério de 10%, contudo não foram considerados, por módulo de testes, as variações abruptas dos sinais, bem como sinais compostospor mais de uma perturbação. Apenas foram incluídas as avaliações de distorção harmônica, flutuação e desequilíbrio.
• Eliminação Simples (sem variações de freqüência)Nesta avaliação, além do critério anterior, não foram considerados os testes com freqüência diferente de 60 Hz.
Constatações Quanto aos Resultados da Avaliação
123
Eliminacao Simples (incluindo todos os testes)
A, B, C, D, E, F, G, H, I, L, M, N, O, P, Q, R, S, T,U, V
Variacao de Tensao em Regime PermaneneteEnsaios 67-74
QVariacao de Tensao de Curta Duracao (Voltage Sags)Ensaios 35-66
BFlutuacao de Tensao (Flicker)Ensaios 29-34
-Desequilibrio de TensaoEnsaios 22-28
-Tensoes HarmonicasEnsaios 01 - 21
Instrumento que satisfizeram o critério de erro relativo igual ou menor que 10%
Grandeza Medida
Media de Notas de Desempenho(baseado no Criterio UFU – B/E)
A, B, C, D, E, F, G, H, I, L, M, N, O, P, Q, R, S, T,U, V
Variacao de Tensaoem Regime PermaneneteEnsaios 67-74
C, D, F, G, J, L, M, N, O, Q, T, UVariacao de Tensaode Curta Duracao(Voltage Sags)Ensaios 35-66
B, Q, NFlutuacao de Tensao(Flicker)Ensaios 29-34
A, B, D, G, H, O, VDesequilibrio de TensaoEnsaios 22-28
A, B, C, D, F, G, L, M, N, O, Q, UTensoes HarmonicasEnsaios 01 - 21
Instrumento que satisfizeram o criterioGrandeza Medida
124
B, Q, NFlutuacao de Tensao (Flicker)Ensaios 29-34
B, D, G, H, O, VDesequilibrio de TensaoEnsaios 22-28
B, C, D, G, M, O, QTensoesHarmonicasEnsaios 01 - 21
Instrumento que satisfizeram o critério de erro relativo igual ou menor que 10% (regime permanente)
Grandeza Medida
Eliminacao Simples (Regime Permanente)
Eliminacao Simples(Sem Variações de Frequencia)
B, Q, NFlutuacao de Tensao(Flicker)Ensaios 29-34
A, B, D, G, H, O, VDesequilibrio de TensaoEnsaios 22-28
A, B, C, D, F, G, L, M, O, Q, UTensoes HarmonicasEnsaios 01 - 21
Instrumento que satisfizeram o critério de erro relativo igual ou menor que 10%
Grandeza Medida
125
Eliminacao Simples (incluindo todos os testes)
Número de instrumentos aprovados
20
1
1
0
0
Todos os testes
20
12
3
7
12
Criterio UFU
--
--
3
6
7
Regime
--Variacao de Tensao em Regime PermaneneteEnsaios 67-74
--Variacao de Tensao de Curta Duracao (Voltage Sags)Ensaios 35-66
3Flutuacao de Tensao (Flicker)Ensaios 29-34
7Desequilibrio de TensaoEnsaios 22-28
11Tensoes HarmonicasEnsaios 01 - 21
S/ Frequencia
Grandeza Medida
MÉTODO DE AVALIAÇÃO PROF. PAULO RIBEIRO
Baseado na Eliminacao Simples (regime permanente, sem variacoes de frequencia e sem variacoes abruptas e desequilibrios para testes 01 a 28):
Instrumentos Selecionados (Selecao Preliminar):
Harmonicos: B, C, D, G, M, O, Q
Desequilibrio de Tensao: B, D, G, H, O, V
Flutuacao de Tensao: B, Q, N
Em caso de medicoes com significantes variacoes rapidas no tempo, desequilbrio, etc., medicoes adicionais devem ser realizadas.
Contatar fabricantes de instrumentos que ultrapassaram criterios e realizar novostestes quando novos protocolos forem implementados.
Proposta preliminar e RecomendaçõesQuanto a seleção de instrumentos
126
Proposta preliminar e RecomendaçõesQuanto a seleção de instrumentos
MÉTODO DE AVALIAÇÃO PROF. PAULO RIBEIRO
Os ensaios de laboratório realizados foram capazes de proporcionar uma comparacao precisa (com relacao a valorespadroes de desvios da tensao) e relativa entre os diversosinstrumentos testados de forma a selecionar os equipamentostestados segundo o seu desempenho. Tal seleção permite inferirque os instrumentos classificados como aceitaveis/adequados, deverão apresentar melhores resultados em situações de campo.
Adicionalmente, os equipamentos de um mesmo grupo deverãoapresentar resultados de mesma qualidade, desde quesubmetidos a sinais com grau de perturbação semelhante aostestados.
Proposta preliminar e RecomendaçõesQuanto a seleção de instrumentos
MÉTODO DE AVALIAÇÃO PROF. PAULO RIBEIROConsiderando as condições que normalmente se apresentam emsistemas de transmissão, considera-se que os equipamentosconsiderados adequados na avaliação do tipo Avaliação Simples (regime permanente) devem satisfazer as necessidades de acompanhamento dos niveis de qualidade na rede basica. A excessão ocorre em pontos de medição que apresentem forte desequilíbrio ou que estejam suprindo cargas que apresentemvariações abruptas importantes. Nesta situação, considerandoque os equipamentos não responderam de forma conveniente, deve-se buscar uma evolução tanto nos testes de avaliação, emlaboratório e em campo, como uma melhoria nos protocolos de medição utilizados pelos instrumentos de forma a avaliar taissituações.
127
MÉTODO DE AVALIAÇÃO PROF. PAULO RIBEIROFinalmente, recomendamos ao ONS continuar esse projeto de afericao dos instrumentos de qualidade de energia ao mesmo tempo que deve acompanhar os desenvolvimentos nos orgaostecnicos internacionais para estabelecimento de protocolos de medicao.
Os resultados obtidos nesse projeto tem um potencial significante de influenciar tanto os orgaos tecnicos internacionais como os fabricantes de instrumentos no sentido de deteminar a compatibilidade de procedimentos e protocolos que facilitem o processo de genrenciamento da qualidade de energia .
Proposta preliminar e RecomendaçõesQuanto a seleção de instrumentos
Gerenciamento da Qualidade de Energia Elétrica
- Breve Introdução
- Consumidores na Transmissão / Distribuição
- Interface Transmissão / Distribuição
- Programas de Qualidade de Energia
- Aspectos Econômicos / Custos
- Contratos / Seguros de Qualidade
- Planejamento da Distribuição
128
Gerenciamento da Qualidade de Energia Elétrica- Breve Introdução
- Consumidores na Transmissão / Distribuição
- Interface Transmissão / Distribuição
Gerenciamento da Qualidade de Energia Elétrica
- Programas de Qualidade de Energia
- Aspectos Econômicos / Custos
- Contratos / Seguros de Qualidade
- Planejamento da Distribuição
129
Programas de Qualidade de Energia
ViolaçãoReportada
Obter Dados Detalhados, Caracterizar Fenômeno
Modelar Simular, Analisar
SistemaAvaliar Desempenho
InvestigarSoluções
Alternativas
Executar Solução
AvaliarSolução
MonitoraçãoVh, V2, ∆V
Determinar Responsabilidades
SatisfazParâmetros deDesempenho?
Objetivo:Operação Ótima
sim
OperaçãoÓtima
Parâmetros deDesempenhoVh, V2, ∆V
Resolver Aspectos Legais
Especificar Solução
Determinar Impacto Econômico
ViolaçãoSeria?
sim
não
Acompanhar
Performance Indices
MonitorMeasure
StudySimulate
CompareWith
IndicesSatisfactory
Possible SolutionsResponsibility
Assessment
Implementing Solutions
Reporting
VerificationEnforcement
FutureSystem/Agents
ExistingSystem/Agents
EducationInformation
PQ Program
Unsatisfactory
130
Why is a PQ Program Needed?
Power quality characteristics on the transmission system are a very important component of the overall power quality delivered to the end user, whether the end user is supplied directly from the transmission system or from a distribution company. A few specific examples of concerns are listed here:
Harmonic distortion on the transmission system can excite local resonances on the distribution system or within customer facilities, causing excessive voltage distortion at lower voltages. This can result in equipment failures (transformers, motors, capacitor banks) and interference problems. Coordinated solutions are required.Voltage fluctuations on the transmission system can propagate down to lower voltages resulted in light flicker for large numbers of customers. This can be very annoying and many customers may complain of these conditions.
Why is a PQ Program Needed?
Capacitor switching operations on the transmission system (not currently a problem in Brasil) can cause transient voltages that get magnified at lower voltages, resulting in equipment misoperation and even failures. Specific requirements for capacitor switching have been implemented in England and by many transmission companies.Voltage sags are caused by faults on the transmission system, as well as faults on distribution systems. Many times, 50% or more of the voltage sags that cause problems for industrial customers are associated with faults at the transmission level. Fault performance and the resulting voltage sags should be evaluated on an ongoing basis and an objective of continuous improvement in performance should be established, similar to the objectives for reliability improvement at the distribution level. Customers require information about the expected performance in order to optimize the design of their facilities and evaluate the economics of power conditioning systemsUnbalanced voltages or harmonic distortion on the transmission system can cause excessive heating in generators, resulting in tripping of the generators. Flicker can also be a concern for generators due to low frequency resonances that can result in torque oscillations that damage the turbine.
131
Specific Functions of the PQMS
Important functions of the PQMS include the following:Benchmarking the system performance (expected power quality levels). This may involve a combination of monitoring of system power quality levels over time and analysis of expected power quality levels using simulation tools.Assessing the actual performance with respect to established benchmarks, compatibility levels, system performance guidelines, and planning levels. This will primarily be a function of the monitoring system.Managing the database of transmission power quality performance information. The monitoring system database is the resource that will be used to assess ongoing performance, identify power quality trends, identify possible problem areas, and provide performance information for distribution companies and end users.Reporting on transmission power quality levels and concerns. Standard reports of system performance with respect to guidelines should be provided. Problem areas should be identified specifically for resolution.
Specific Functions of the PQMS
Developing recommended solutions for improving performance where there are problem conditions. The PQMS should incorporate the tools for evaluating the causes of problem conditions and should be used to develop recommended solutions to improve performance. This function of the PQMS will involve analysis and simulation tools that work in conjunction with the monitoring systems. This function of the PQMS will involve assigning responsibilities for improving performance at various levels of the system (transmission operators, distribution companies, end users, generators).Planning for new loads, distribution system connections, generators, andtransmission system changes. All changes to the transmission system infrastructure can impact the power quality levels. The PQMS should support evaluation of prospective changes and new connections to assure that they will not result in power quality problems. This is especially important for connections that can result in increased flicker or harmonic levels.Educating the various agents impacted by transmission power quality. Reporting functions of the PQMS should be used to educate the generators, distribution companies, and end users about power quality levels and their respective responsibilities in maintaining compatibility of the overall system.
132
D/A
Tested hardware
Simulator (computer)
A/D
Inputs tohardware
Outputs fromhardware
Outputs from simulatorsInputs to simulators
An Advanced Power Quality AssessmentUsing RT-HIL Approach
The Need for Integrated Laboratories and Research Centers
Example
Firing pulseboard
Power grid6-pulse
thyristor rectifier
YYVL-L=12.47 kV
Lline=0.05 p.u.Rline=0.005 p.u. LT=0.05 p.u.
RT=0.005 p.u.
Distribution transformer12.47 kV/480 V
IndustryDC load
-
+
RL=0.48 ohmLL=1 mH
PQ phenomena Simulation results
THD • Tolerate THD up to 14.8% and higher • Tolerance has no impact on distribution systems
Voltage sag • Tolerance depends on not only the time duration and voltage reduction, but also phase shift • Tolerance results in DC voltage drop or blackout
Frequency change • Tolerate system frequency from 30 Hz to 80 Hz
An Advanced Power Quality AssessmentUsing RT-HIL ApproachExample
133
Debates – Mesa Redonda
Power Quality Evolving Environment
How To Interpret This?
134
Power Quality Evolving Environment
How To Interpret This?
135
No definite indices
Indices short-time
95%95%95%Indices
Shipboard
Transmission Supply voltage characteristics
Supply voltage characteristics
Planning levels for controlling emissions
Supply voltage characteristics
Minimum standard used by the regulator
Planning Levels
PQ measurement methods
Emissions and Supply Voltage
Supply Voltage
Purpose
USABrazilQuebecEnglandFranceSouth Africa
International
International
USA and other countries
19 European Countries
Where
Military Standard
National Standard
VoluntaryNational Standard
Premium Power
National Standard
Technical Report
Technical Report
ANSI Standard; Recommended Practice
European Standard
Status
MIL Std 1399-300A
ONS -Brazil
HQ Voltage Charact
ER G5/4EDF Emerald Contract
NRS048-2 :96
IEC 61000-3-6 :1996
IEC 61000-4-30
IEEE-519
EN50160:2000
Standard
330 20 20 20 50 321
330.20.20.20.50.3820
331.21.51.21.51.7619
330.20.20.20.50.3918
331.621.62217
330.20.20.20.50.4116
330.30.30.30.50.415
330.20.20.20.50.4314
332.532.53313
330.20.20.40.50.4612
3333.533.53.511
330.40.50.40.50.510
331.21.51.21.51.59
330.40.50.40.50.58
33454557
330.50.50.50.50.56
33564665
33111114
33454553
331.621.6222
MIL 1399IEEE 519
IEC 61000-3-6
NRS 048-2ER G5/4EN50160IEC 61000-4-30Order
136
Proposed Voltage Harmonic Limits For Shipboard Systems
0.521
0.520
319
0.518
317
0.516
0.515
0.514
413
0.512
411
110
19
18
57
16
55
14
53
22
Recommended LimitsEven Odd TripleOrder
Proposed Voltage Harmonic Limits For Shipboard Systems
Recommended Action - > 9%Possible Problems – 7 - 9%THDCaution – 5 - 7%
1>25
225
0.524
223
0.522
Recommended LimitsEven Odd TripleOrder
137
5 10 15 20 250
2
4
6
Harmonic Voltages
Har
mon
ic O
rder
7
0
Veveni
Vtriplei
Voddi
IEEE519i
271 i
Proposed Voltage Harmonic Limits For Shipboard Systems
IEEE 519 Vh Limits (odd components) Limits
0 5 10 15 20 250
5
10
15
20
Time (Minutes)
Vol
tage
TH
D (%
)
20
0
THDProblems2i
THDCaution2i
THDShortTermi
IEEE519THDi
251 i
IEEE 519 THD Limit
Proposed Short-Term Limits
Proposed Max 95% THD Limit
Proposed Voltage Harmonic Limits For Shipboard Systems
138
0 0.01 0.02 0.03 0.04 0.052
1
0
1
21.25
1.25−
y1 t( )
y2 t( )
y3 t( )
y11 t( )
0.050 t
Upper Boundary
Lower Boundary
Zero Crossing Restrictions
Peak Variation
Waveform Distortion Limitation: An Alternative ApproachVia Envelop Boundaries
139
Generation Delivery Conversion Processing
CentralStation
T&D AC-ACSupplies
Motion
EnvironmentalMaintainability
AvailabilitySafety
EfficiencyReliability
PerformancePrice
Power Quality
Power System Value Chain
Power Electronics Systems and Components
SMESBatteries
FACTSSMESPQ Parks
UPS Appliances
INPUTS OUTPUTS
Valu
e Di
men
sions
Energy Power Communication
Light / Motion
Utility User
The Integrated Quality Environment
140
Technology Transmission Line Transfer Enhancement
Cost Range Operating principle Procurement Availability
Reconductor lines Increase thermal capacity $50K to $200K per mile
Increases thermal limit for line Competitive
Fixed or Switched Shunt Reactors
Voltage reduction – Light Load Management
$8-$12 kVAR Compensates for capacitive var-load
Competitive
Fixed or Switched Shunt Capacitors
Voltage support and stability
$8-$10 kVAR Compensates for inductive var-load
Competitive
Fixed or Switched Series Capacitors
Power flow control, Voltage support and Stability
$12-$16 kVAR Reduces inductive line impedance
Competitive
Static VAR Compensators Voltage support and stability
$20-$45 kVAR Compensates for inductive and/or capacitive var-load
Competitive
Thyristor Controlled Series Compensation (TCSC)
Power flow control, Voltage support and stability
$25-$50 kVAR Reduces or increases inductive line impedance
Limited competition
STATCOM Voltage support and stability
$80-$100 kVAR Compensates for inductive and capacitive var-load
Limited competition
STATCOM w/SMES Voltage support and stability
$150-$300 kW Compensates for inductive and/or capacitive var-load plus energy storage for active power
Limited
Unified Power Flow Controller (UPFC)
Power flow control, Voltage support, and Stability
$150-$200 kW SVC and TCSC functions plus phase angle control
Sole source
Unified Power Flow Controller (UPFC) w/SMES
Power flow control Voltage support and Stability,
$250-$350 kW SVC and TCSC functions plus voltage regulator, phase angle controller and energy storage
Sole source
Shaded area indicates technologies that are either permanently connected or switched on or off with mechanical switches. (i.e. these are not continuously controllable)
Cost Considerations
Summary Comparison of DG Technologies
On grid windfarms, off-grid telecom, instruments and other sites
700-1,200
Not configured for this capabilityNA0.2 kW up
to 5 MWWind
Turbines
Residential offgrid, net metered residential on-grid, green power, offgrid telecom and
instruments
4,000-6,500
Not normally configured for this capability – some products are available
NA1 W up to 10 MWPhotovoltaics
Industrial/commercial facilities, critical power, low emissions niche markets
4,000-50,000
Good potential for cogeneration (can be up to
90% efficient)35-60%<1 kW up to 10 MWFuel Cells
Small commercial and industrial applications
700-1,000
Good potential for cogeneration (can be up to
90% efficient)22–30%27-400 kWMicroturbine
Industrial/commercial facilities application/islanded power plants/standby
power300-900
Good potential for cogeneration (can be up to
90% efficient)25-38%1 kW up to
10 MW IC Engine
Industrial facilities/small utility peaking plants
500-1,000
Good potential for cogeneration (can be up to
90% efficient)25-40%1-50 MW
Industrial Combustion
Turbines
large utility owned central station power plants400-500
Not normally an application with this type of plant but
could be done50-60%50-500 MW
Combustion Turbine
CombiinedCycle
Common Applications
Current Installed
Cost($/kW)
Viability and Efficiency In Cogeneration Application
Electrical Efficiency (%LHV)
Applied Size Range
Generation Technology
141
Modeling of Linear Components for Harmonic Studies
Paulo F. Ribeiro
Task Force on Harmonic Modeling and Simulation
IEEE Transactions on Power Delivery, PRD 18-2, April 2003, pp. 625-30
Impact of Aggregated Linear Load Modeling on Harmonic
Analysis:A Comparison of Common Practice and
Analytical Models
Task Force on Harmonic Modeling and Simulation
IEEE Transactions on Power Delivery, PRD 18-2, April 2003, pp. 625-30.
142
Outline
Introduction: Linear and Non-Linear Loads
Survey of Linear Load Models– Mostly resistive loads– Loads with significant Induction Motor participation– Treatment of network elements
Comprehensive Load Models– Inclusion of electronic and other harmonic loads– Inclusion of background distortion– Reactive power compensation elements
Sensitivity Studies
Load Model Classification
Apparatus
Non-LinearHarmonic Producing
(ASD’s, Arc Furnace, Electronics, etc)
LinearNot Producing Harmonics
(Impedance representation)
Resistive Motors(Other than ASD’s)
143
Sample Load Composition
Linear (Resistive)Non-linearLinear (Resistive)Linear (Motor)
Non-linearNon-linearLinear (Motor)
Linear (Motor)Non-linearLinear (Motor)Non-linear
Domestic• Incandescent lamps • Home electronics • Resistive heater• Air conditioningCommercial• Fluorescent lamps• Computers• Air conditioningIndustrial• Motors• ASD’s• Pumps• Arc Furnace
Electrical CharacteristicsType of Load
Description of Linear Loads
Aggregate Real and Reactive Power (P and Q) corresponding to the Linear Load:– Precise impedance representation at
fundamental frequency– Imprecise motor impedance representation at
harmonic frequencies
Motor Participation:– K, the fraction of motor load on a bus:
Fraction of Motor Load: KFraction of Resistive Load: 1-K
PPK M=
144
Model Complexity vs. the K-Factor
Low Motor Participation (K<0.1):– Mostly resistive load– Simple series or Parallel RL models– Obtain model parameters from P and Q
Significant Motor Participation:– Damping at harmonic frequencies– Obtain model parameters from P and Q,
and typical motor characteristics
Mostly Resistive Loads (K<0.1)
Series RL
R
jhX
22
2
22
2
QPVQX
QPVPR
+⋅=
+⋅=
145
…Case K<0.1
Parallel RL
R jhX
QVX
PVR
2
2
=
=
…Case K<0.1
Inclusion of Skin Effect
R(h) jhX(h)
9.01.0)(
)()(
)()(
2
2
+⋅=
⋅=
⋅=
hhm
QhmVhX
PhmVhR
146
Significant Motor Participation
Treat Resistive and Motor Loads separately:1) Resistive load: (1-K)P2) Motor load: KP
• Additional Motor InformationQuality factor K3=X/RPU Locked rotor reactance XM
Install factor Km=1/(power factor)
…Significant Motor Load
Simple Parallel Model
R2 jhX1
Resistive Motive
PKKVXX
PKVR
mM ⋅⋅
⋅=
⋅−=
2
1
2
2 )1(
147
…Significant Motor LoadCIGRE-EDF Model
PQ
PKVX
RX
PKVR
=
−⋅⋅⋅=
⋅=
⋅−=
φ
φ
tan
)74.0tan7.6(
073.0
)1(
2
1
22
22
R2
jhX2jhX1
Resistive Motive
…Case with K>0.7
Inclusion of Damping
R1
jhX1
R2
jhX2
Resistive Motive
311
22 1.0KXRRX
=⋅=
PKKVXX
PKVR
mM ⋅⋅
⋅=
⋅−=
2
1
2
2 )1(
Skin Effect:R1,skin(h)=R1(1+0.05(hfo)0.5), X1,skin(h)=2X1(hfo)0.15
148
Network Elements
Power Lines and Cables– Thevenin Source, PI-sections, FDE– Detail representation at the points of
interest
Transformer Representation– Series RL, Skin Effect
PFC Capacitors
Comprehensive Load Representation
Electronically Controlled Load– Harmonic source
Background Distortion– Thevenin source at harmonic
frequencies
Reactive Power Compensation, PFC
149
Comprehensive Load Model
Electronic Load: KE
Motor Load: K
Resistive Load: 1-K-KE
e.g. Ih=I1/h
Sensitivity Studies
Load Composition
Reactive Power Compensation
Background Distortion
150
System Studied
0.001Ω
0.0107H
11 kVSystemSource
HarmonicSource
Load
PFC
Harmonic Source (A):I5 = 0.840I7 = 0.601I11=0.382I13=0.323
Linear Load: 743 kW
PFC: 741 kVAR
Varying Load Composition
2 4 6 8 10 12 14 16 18 2010
1
102
103
Frequency (x60Hz)
Impe
danc
e (O
hm)
7
8
9
Case 7: K=0.25Case 8: K=0.75Case 9: K=0.90
020406080
100120
7 8 9
Case #
Volta
ge (V
) 5th7th11th13th
151
Adjusting PFC
1. Vary Load CompositionK=0.25,0.75,0.90
2. Adjust PFC for Full CompensationMotor power factor: cosφM=0.83Motor reactive consumption:QM=QPFC=KPtanφM
Adjusted PFC
2 4 6 8 10 12 14 16 18 2010
0
101
102
103
Frequency (x60Hz)
Impe
danc
e (O
hm)
10 11
12
0
20
40
60
80
10 11 12
Case #
Volta
ge (V
) 5th7th11th13th
Case 10: K=0.25Case 11: K=0.75Case 12: K=0.90
152
Background Distortion
A 0.5% distortion at 5th, 7th, and 11th.
020406080
100120
16 17 18
Case #
Volta
ge (V
) 5th7th11th13th
Case 16: K=0.25 Case 17: K=0.75 Case 18: K=0.90
Conclusions
P and Q are Inadequate for Harmonic Studies.
Load Composition affects Damping and resonance frequency of harmonic impedance.
Background distortion can interact with a local harmonic source.
153
ConclusionsPQ will continue to grow in importance as the electric sector
operates within a truly free economy.
Utilities, customers and manufacturers will have to cooperate toestablish a stable model for the power quality industry sector
An integrated Approach Is EssentialVision, Philosophy/Strategy and Initiative
Initiatives:Grupos de QE ou Compatibilidade Eletromagnética (GCEM)
Promoção de Uma Visão IntegradaContinuem o excelente trabalho:
Cooperação: Consumidores, Concessionárias, Industria,Outros centros.
"No man who values originality will ever be original. But try to tell the truth as you see it, try to do any bit of work as well as it can be done for the work's sake, and what men call originality will come unsought.“
C.S. Lewis
154
Preperar declaração conjunta.
O instrutor e participantes do Curso Avancado de Qualidade de Energia Eletrica realizado …. PUCRS …… durante o period de …… apos intensos debates e avaliacoes sobre os possiveis impactos dessa qualidade no desempenho da rede eletrica concluiem que:-o setor eletrico acompanha de perto os desenvolvimentos a niveis internacionais…- investimentos adicionais precisam ser ……- pesquisas e desenvolvimentos ….----