atuador belÍmo

Post on 07-Aug-2018

212 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

TRANSCRIPT

8/20/2019 Atuador BelÍ mo

http://slidepdf.com/reader/full/atuador-belimo 1/2

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

N 4 0 0 1 3 0

6 / 1 1

S u b j e c t t o c h a n g e ©

B e l i m o A i r c o n t r o l s ( U S A ) I n c

AR...24-3 Actuators, On/Off, Floating Point

ModelsR 24-RB24-3-S w/built-in Aux. SwitchRB24-3-T Flexible

RX24-3 Flexible w/built-in Aux. SwitchRX24-3-SRX24-3-T

Technical Data

Control on/o , oating point

Power supply 24 VAC ± 20% 50/60 Hz24 VDC ± 10%

Power consumption running 2.5 W

holding 0.2 W

Transformer sizing 5.5 VA (class 2 power source)

Electrical connection

AR 24-3...ARX24-3...

½” conduit connector18 GA plenum rated cable3 ft. [1m]3 ft. [1m] 10 ft. [3m] 16 ft. [5m]

Overload protect ion electronic throughout 0° to 95° rotation

nput impedance 600 Ω

Angle of rotation 90°, adjustable with mechanical stop

Direction of rotation reversible with protected

Position indication handle

anua overr e externa pus utton

Running timeARB24-3...ARX24-3...

90 seconds300, 150, 90 seconds,constant independent of load

Humidity 5 to 95% RH non-condensing (EN 60730-1)

Ambient temperature -22°F to 122°F [-30°C to 50°C]

Storage temperature -40°F to 176°F [-40°C to 80°C]

Housing NEMA 2/IP54

Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,CAN/CSA E60730-1:02, CE according to2004/108/EC and 2006/95/EC for line voltageand/or –S versions

Noise level <45 dB(A)

Quality standard ISO 9001

AR...24-3-S

Auxiliary switch (-S models) 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,ad ustable 0 to 90

Rated impulse voltage 800V, Control pollution degree 3, Type of action 1(1.B for -S models)

Dimensions

8/20/2019 Atuador BelÍ mo

http://slidepdf.com/reader/full/atuador-belimo 2/2

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA

N 4 0 0 1 3 - 0

6 / 1 1 -

S u b j e c t t o c h a n g e .

© B

e l i m o A i r c o n t r o l s ( U S A ) , I n c .

Wiring Diagrams

2 CAUTION quipment damage Actuators may be connected in parallel.Power consumption and input impedance must be observed.

3

For end position indication, interlock control, etc.,

ARB24-3-S incorporates one built-in auxiliary switches:1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.

Actuators may also be powered by 24 VDC.

Meets cULus or UL and CSA requirements without theneed o an electrical ground connection.

ARNIN Live Electrical omponents During installation, testing, servicing and troubleshooting of this product, it may

be necessary to work with live electrical components. Have a quali ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.

424 VAC Transformer

a opena closed

The indication of directionis valid for switch position 1.

Blk (1) Common

Red (2) +

Wht (3) +

ARB24-3

a

Line

Volts

1 0

On/Off control

424 VAC Transformer

The indication of directionis valid for switch position 1.

Blk (1) Common

Red (2) +

Wht (3) +

ARB24-3

Line

Volts

1 0

Floating Point or On/Off control

ARB24-3-S

3S1

S2

S3

NC

NO0° to 95°

Auxiliary switch

AR...24-3 Actuators, On/Off, Floating Po

top related