atuador belÍmo
TRANSCRIPT
8/20/2019 Atuador BelÍ mo
http://slidepdf.com/reader/full/atuador-belimo 1/2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
N 4 0 0 1 3 0
6 / 1 1
S u b j e c t t o c h a n g e ©
B e l i m o A i r c o n t r o l s ( U S A ) I n c
AR...24-3 Actuators, On/Off, Floating Point
ModelsR 24-RB24-3-S w/built-in Aux. SwitchRB24-3-T Flexible
RX24-3 Flexible w/built-in Aux. SwitchRX24-3-SRX24-3-T
Technical Data
Control on/o , oating point
Power supply 24 VAC ± 20% 50/60 Hz24 VDC ± 10%
Power consumption running 2.5 W
holding 0.2 W
Transformer sizing 5.5 VA (class 2 power source)
Electrical connection
AR 24-3...ARX24-3...
½” conduit connector18 GA plenum rated cable3 ft. [1m]3 ft. [1m] 10 ft. [3m] 16 ft. [5m]
Overload protect ion electronic throughout 0° to 95° rotation
nput impedance 600 Ω
Angle of rotation 90°, adjustable with mechanical stop
Direction of rotation reversible with protected
Position indication handle
anua overr e externa pus utton
Running timeARB24-3...ARX24-3...
90 seconds300, 150, 90 seconds,constant independent of load
Humidity 5 to 95% RH non-condensing (EN 60730-1)
Ambient temperature -22°F to 122°F [-30°C to 50°C]
Storage temperature -40°F to 176°F [-40°C to 80°C]
Housing NEMA 2/IP54
Housing material UL94-5VAAgency listings† cULus according to UL 60730-1A/-2-14,CAN/CSA E60730-1:02, CE according to2004/108/EC and 2006/95/EC for line voltageand/or –S versions
Noise level <45 dB(A)
Quality standard ISO 9001
AR...24-3-S
Auxiliary switch (-S models) 1 x SPDT, 3A (0.5A) @ 250 VAC, UL Listed,ad ustable 0 to 90
Rated impulse voltage 800V, Control pollution degree 3, Type of action 1(1.B for -S models)
Dimensions
8/20/2019 Atuador BelÍ mo
http://slidepdf.com/reader/full/atuador-belimo 2/2
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA
N 4 0 0 1 3 - 0
6 / 1 1 -
S u b j e c t t o c h a n g e .
© B
e l i m o A i r c o n t r o l s ( U S A ) , I n c .
Wiring Diagrams
2 CAUTION quipment damage Actuators may be connected in parallel.Power consumption and input impedance must be observed.
3
For end position indication, interlock control, etc.,
ARB24-3-S incorporates one built-in auxiliary switches:1 x SPDT, 3A (0.5A) @250 VAC, UL listed, adjustable 0° to 95°.
Actuators may also be powered by 24 VDC.
Meets cULus or UL and CSA requirements without theneed o an electrical ground connection.
ARNIN Live Electrical omponents During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a quali ed licensed electricianor other individual who has been properly trained in handling live electrical componentsperform these tasks. Failure to follow all electrical safety precautions when exposed to liveelectrical components could result in death or serious injury.
424 VAC Transformer
a opena closed
The indication of directionis valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
ARB24-3
a
Line
Volts
–
1 0
On/Off control
424 VAC Transformer
The indication of directionis valid for switch position 1.
Blk (1) Common
Red (2) +
Wht (3) +
ARB24-3
Line
Volts
–
1 0
Floating Point or On/Off control
ARB24-3-S
3S1
S2
S3
NC
NO0° to 95°
Auxiliary switch
AR...24-3 Actuators, On/Off, Floating Po