Download - ESPECIFICAÇÃO COMPLETA
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
1/30
Nº:
ET-2016-IBC-002CLIENT:
LIGTH S.A SHEET: 1 de 12 REA:
INTERNATIONAL BROADCAST CENTRE- IBC
Rio 2016 Olympic Games
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
REVISION LIST
REV. DESCRIPTION AND/OR CHANGED SHEETS
O Original version
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
2/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
2 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
SUMARY
1. OBJECTIVE ------------------------------------------------------------------------------------------------------------ 3
2. GENERAL SPECIFICATION --------------------------------------------------------------------------------------- 3
2.1. CONTAINER ---------------------------------------------------------------------------------------------------------------------------------- 3
2.2. DIESEL MOTOR ------------------------------------------------------------------------------------------------------------------------------ 4
2.3. GENERATOR --------------------------------------------------------------------------------------------------------------------------------- 4
2.4. CONTROL MODULE ------------------------------------------------------------------------------------------------------------------------ 5
2.5.
GENERATOR BREAKER PROTECTION -------------------------------------------------------------------------------------------------- 7
2.6. RECTIFIER BATTERY CHARGER ---------------------------------------------------------------------------------------------------------- 7
2.7. FUEL TANK ----------------------------------------------------------------------------------------------------------------------------------- 7
2.8. ENGINE PRE-HEATING SYSTEM --------------------------------------------------------------------------------------------------------- 8
2.. INTERNAL RETAINING BASIN ------------------------------------------------------------------------------------------------------------ 8
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
3/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
3 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
1. OBJECTIVE
The purpose of this document is to describe the tehcnical specification of 1400 kVA generators.
2. GENERAL SPECIFICATION
Power Generation System type TWIN GEN, consisting of two generators of 700 KVA parallel in a
single container, providing a total capacity of 1,400 kVA on stand-by arrangements.
2.1. CONTAINER
ISSO Container of 20 feet, construction in carbon steel, prepared for outdoor installation, provided
with side access doors and acoustic treatment.
- Dimensions: A x B x C: 2,90 x 2,44 x 6,06 m;
- Noise Level : 75 db @ 7 meters
- Weight: 12T.
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
4/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
4 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
2.2. DIESEL MOTOR
− Brand: Volvo;
− Model: TAD 1642GE;
− Quantiity: 2;
− Cicle: 4 tempos;
− N° of cylinders: 6 cylinders in line;
− Induction: Turbo Powered;
− Power: 653 CV;
− Electric Start: 24 Vcc Starter;
− Fuel Injection: Electronic;
− Fuel: Diesel;
− Pre-heating: Through resistance interspersed in the water circuit;
− Cooling: Radiator with fan on the shaft;
− Lubrication: Forced by gear;
− Replaceble filter;
2.3. GENERATOR
− Brand: WEG;
− Excitation: Brushless (PMG);− Quantity: 2;
− Bearing: Double bearing;
− Mechanical Protection: IP-23/ABNT;
C S
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
5/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
5 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
− PRIME: 875 kVA T=150°C;
− CONTINUOUS: 803 kVA T= 125°C;
− Voltage regulation ± 1.0%;
− Enables rapid recovery of variations of transient loads;
2.4. CONTROL MODULE
Control module, containing all necessary functions for protection and control, including automation
logic, supervisory steps, start, stop, defects, cooling and control circuit breakers.
− Manufacturer: DEIF
− Model: AGC-4
− Quantity:02
Operation modes:
− Emergency;
− Island;
− Load base;
− Demand control;
− Parallelism up to 16 generators with active and reactive load sharing, and PF control when in
parallel with the utility;
− Power management.
Control:
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
6/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
6 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
Visualization:
− Line and phase voltages (V);
− Frequency (Hz);
− Current in three phases (A);
− Active power (kW);
− Apparente power(kVA);
− Reactive power (kVAr);
− Consumed active power (kWh);
− Consumed reactive power (kWArh);
− Power fator (cos ϕ);
− Lubricant oil pressure;
− Engine speed;
− Number of starts;
− Operating time (h);− Maintenance remain time (h);
− Battery voltage (V);
− Coolant temperature (ºC).
Protection:
− Undervoltage (27);
− Power surge (59);
− Under frequency (81);
O
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
7/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
7 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
− Inverse Power (32 R);
− Phase sequence (47);
− Sync Check (25);
− Emergency button.
2.5. GENERATOR BREAKER PROTECTION
− Manufacturer: SCHNEIDER
− Model: NT- 16
− Quantity: (02) Dois;− Protection functions: Overload (L), short-circuit (S),
instantaneous short circuit Adjustable (I); earth fault;
− Rated uninterrupted current: 1.600 A;
− Maximum Interruption capacity under short-circuit: 40 kA /
690 Vca;
− Opening coils, closing and motorization (24 Vcc);
2.6. RECTIFIER BATTERY CHARGER
Automatic Rectifier with the following characteristics:
− Manufacturer: DEI
− Mo!el: D"#$% 24&'
− uantit: (&2) Dois;
− *u++l Voltage (neutral , +hase) ---------- 22& Vca
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
8/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
8 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
2.8. ENGINE PRE-HEATING SYSTEM
Engines equipped with coolant pre-heating systems.
2.9. INTERNAL RETAINING BASIN
Tight inner containment basin, made of carbon steel, capable of holding up to 110% of all fluid in
equipment.
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
9/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
9 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
UNIFILAR POWER DIAGRAM
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
10/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
10 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
MOTOR DATA SHEET
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
11/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
11 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
GENERATOR DATA SHEET
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
12/30
Nº ET-2016-IBC-002 REV. 0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
12 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
CONTAINER DIMENSIONS
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
13/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
2 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
SUMARY
1. OBJECTIVE ------------------------------------------------------------------------------------------------------------ 3
2. GENERAL SPECIFICATION --------------------------------------------------------------------------------------- 3
2.1. CONTAINER ---------------------------------------------------------------------------------------------------------------------------------- 3
2.2. DIESEL MOTOR ------------------------------------------------------------------------------------------------------------------------------ 4
2.3. GENERATOR --------------------------------------------------------------------------------------------------------------------------------- 4
2.4. CONTROL MODULE ------------------------------------------------------------------------------------------------------------------------ 5
2.5. GENERATOR BREAKER PROTECTION -------------------------------------------------------------------------------------------------- 7
2.6. RECTIFIER BATTERY CHARGER ---------------------------------------------------------------------------------------------------------- 7
2.7. FUEL TANK ----------------------------------------------------------------------------------------------------------------------------------- 7
2.8. ENGINE PRE-HEATING SYSTEM --------------------------------------------------------------------------------------------------------- 8
2.. INTERNAL RETAINING BASIN ------------------------------------------------------------------------------------------------------------ 8
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
14/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
3 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
1. OBJECTIVE
The purpose of this document is to describe the tehcnical specification of 1400 kVA generators.
2. GENERAL SPECIFICATION
Power Generation System type TWIN GEN, consisting of two generators of 700 KVA parallel in a
single container, providing a total capacity of 1,400 kVA on stand-by arrangements.
2.1. CONTAINER
ISSO Container of 20 feet, construction in carbon steel, prepared for outdoor installation, providedwith side access doors and acoustic treatment.
- Dimensions: A x B x C: 2,90 x 2,44 x 6,06 m;
- Noise Level : 75 db @ 7 meters
- Weight: 12T.
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
15/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
4 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
2.2. DIESEL MOTOR
− Brand: Volvo;
− Model: TAD 1642GE;
− Quantiity: 2;
− Cicle: 4 tempos;
− N° of cylinders: 6 cylinders in line;
− Induction: Turbo Powered;
− Power: 653 CV;
− Electric Start: 24 Vcc Starter;
− Fuel Injection: Electronic;
− Fuel: Diesel;
− Pre-heating: Through resistance interspersed in the water circuit;
− Cooling: Radiator with fan on the shaft;
−
Lubrication: Forced by gear;− Replaceble filter;
2.3. GENERATOR
− Brand: WEG;
−
Excitation: Brushless (PMG);− Quantity: 2;
− Bearing: Double bearing;
− Mechanical Protection: IP-23/ABNT;
C S
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
16/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
5 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
− PRIME: 875 kVA T=150°C;
− CONTINUOUS: 803 kVA T= 125°C;
− Voltage regulation ± 1.0%;
−
Enables rapid recovery of variations of transient loads;
2.4. CONTROL MODULE
Control module, containing all necessary functions for protection and control, including automation
logic, supervisory steps, start, stop, defects, cooling and control circuit breakers.
− Manufacturer: DEIF
− Model: AGC-4
− Quantity:02
Operation modes:
− Emergency;
− Island;
− Load base;
− Demand control;
− Parallelism up to 16 generators with active and reactive load sharing, and PF control when in
parallel with the utility;− Power management.
Control:
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
17/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
6 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
Visualization:
− Line and phase voltages (V);
− Frequency (Hz);
− Current in three phases (A);
− Active power (kW);
− Apparente power(kVA);
− Reactive power (kVAr);
− Consumed active power (kWh);
− Consumed reactive power (kWArh);
− Power fator (cos ϕ);
− Lubricant oil pressure;
− Engine speed;
− Number of starts;
−
Operating time (h);− Maintenance remain time (h);
− Battery voltage (V);
− Coolant temperature (ºC).
Protection:
− Undervoltage (27);
− Power surge (59);
− Under frequency (81);
O
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
18/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
7 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
− Inverse Power (32 R);
− Phase sequence (47);
− Sync Check (25);
−
Emergency button.
2.5. GENERATOR BREAKER PROTECTION
− Manufacturer: SCHNEIDER
− Model: NT- 16
− Quantity: (02) Dois;
− Protection functions: Overload (L), short-circuit (S),
instantaneous short circuit Adjustable (I); earth fault;
− Rated uninterrupted current: 1.600 A;
− Maximum Interruption capacity under short-circuit: 40 kA /
690 Vca;
− Opening coils, closing and motorization (24 Vcc);
2.6. RECTIFIER BATTERY CHARGER
Automatic Rectifier with the following characteristics:
− Manufacturer: DEIF
− Moel: D!"#$ 24%&
− 'uantit: (%2) Dois;
− u**l Voltage (neutral + *hase) ,,,,,,,,,, 22% Vca
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
19/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
8 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
2.8. ENGINE PRE-HEATING SYSTEM
Engines equipped with coolant pre-heating systems.
2.9. INTERNAL RETAINING BASIN
Tight inner containment basin, made of carbon steel, capable of holding up to 110% of all fluid in
equipment.
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
20/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
9 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
UNIFILAR POWER DIAGRAM
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
21/30
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
22/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
10 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
MOTOR DATA SHEET
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
23/30
General
litre
in3
mm
in
mmin
Dry weight kg
lb
kg
lb
Wet weight kg
lb
kg
lb
r/min 1500 1800
without fan kW 496 551
hp 675 749
with fan kW 485 532
hp 660 724
without fan kW 547 604
hp 744 821
with fan kW 536 585
hp 729 796
Torque at: Nm 3158 2923
lbft 2329 2156
Nm 3482 3204
lbft 2568 2363
m/s 8,3 9,9
ft/sec 27,1 32,6
MPa 2,5 2,3
psi 357 331
MPa 2,7 2,5
psi 394 362
MPa 17,5 18
psi 2538 2611
Issue Index
03TAD1642GE
Document No
21388261
Effective mean pressure at:
Max combustion pressure at:
Prime Power
Standby Power
Effective mean pressure at: Prime Power
5,67
165
In-line four stroke diesel engine with direct injection. Rotation direction, anti-clockwise viewed towards flywheel.
Turbocharged
Number of cylinders 6
16,12
Prime Power
Standby Power
Standby Power
Mean piston speed
Prime Power
Engine only, excluding cooling
system
GenPac
Engine only, excluding cooling
system
GenPac
2020
3417
Performance
Displacement, total
983,7
1-5-3-6-2-4Firing order
1480
3263
Bore
Stroke
144
Compression ratio 16,5:1
4453
1910
4211
1550
6,50
NºET 2016 IBC 002
REV
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
24/30
Nº ET-2016-IBC-002
REV.
0
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
11 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
GENERATOR DATA SHEET
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
25/30
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
26/30
Nº ET-2016-IBC-002
REV.
0
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
27/30
ET-2016-IBC-0020
CLIENT:
INTERNATIONAL BROADCAST CENTRE- IBC
SHEET:
12 de 12
TITLE:
1.400 KVA GENERATOR – TECHNICAL SPECIFICATION
‘
CONTAINER DIMENSIONS
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
28/30
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
29/30
-
8/17/2019 ESPECIFICAÇÃO COMPLETA
30/30