front face1 opening push-button (O)
2 closing push-button (I)3 keylock for "connected",
"disconnected" or "test" position4 door interlock5 stored-energy-mechanism charging
handle6 operations counter7 "open" position keylock8 racking handle storage9 functional position indicator:
"connected", "test" and "disconnected"10 controls on fixed chassis (accessible
with cubicle door closed)11 padlocking facilities for "connected",
"disconnected" or "test" position
12 stored-energy-mechanism statusindicator
c"charged"
c"discharged"
13 main-contact position indicator
c"OFF" (O);
c"ON" (I).
14 fault-trip indicator/breaker reset buttonLV circuit-breaker: blue figuresEnclosure: red figures
Masterpact: presentation
Masterpact circuit breakers are used toprotect and control low-voltage distributionsystems. They may be installed in main LV
switchboards (incoming units, main andsecondary outgoers). Masterpact is acomplete range offering a large selection ofperformance levels:
cratings from 800 to 6300 A AC,
from 1000 to 8000 A DC;cbreaking capacity from 40 to 150 kA rms;coperational voltages 690 V AC,1000 V DC.
2 Merlin Gerin
Many versions
c3 or 4 poles;
cfixed or drawout versions;
ccurrent-limiting version up to 2500 A;
cwide range of control units offeringmultiple functions.
Circuit breakers designed for allapplications
c1000 V AC version;
cDC version;
canti-corrosion version;
csource-changeover version;cmerchant-marine and military versions.
Masterpact circuit breakers comply with allmajor international standardsand meetT2 tropicalisation criteria.
Reduced dimensionscAC circuit breakers:va single frame size from 800 to 3200 A,vcommon height and depth from 800 to
6300 A;
cDC circuit breakers:
vcommon height and length from 1000 to8000 A for operational voltages of up to 500V DC,
vcommon height and length from 1000 to
4000 A for operational voltages greater than500 V DC.
push to reset
I
I1 I2I3
90%
50%
20%
STR 58 UE
0.63
IoIr
0.8
0.51
xIn
90
105
%Ir
.88
.9 .9 2.95
.981
.8.85
xIo
Imtm
3
4 56
8
101.52
xIo
.3
.4 . 3
.1
.1.2
on I2t off
.2
0
Ir fault
tr
Imfault
tm
I
faultIh
th
t
i
test
+ S
T +
T
F
Ihth
400
500 600
800
1000
1200250
320
A
.3
.4 .4
.2
.1.2
on I2t off
.3
.1
I
off2
xIn
Ir :
Im:
th :
I
IG L I
G
LLG
LIG
off
resetV
tr
60
120 2 40
480
1530
at 1,5Ir
4
6
8 12
17
22
Ic1Ic2
.86
.9 . 93
.95
.98
1.8
.85
.7
.8 .85
.95
.5.6
xIr
.9
1
R
xIr
test
Opush OFF
connected
test
disconnected
O OFFdischarged
I
push ON
MERLIN GERIN
M32H1masterpact
IEC947-2
00000
Ui
Ue
Icu
Ics
Icw
1000V
380/440V
100kA
100kA
75kA 1s
50/60Hz
480/69 0V
85kA
85kA
M63M50 M40
M08 M32
charged
discharged
O OFF
I ON
E28791
E28761
E28760
M08 to M32
035928PC
11
14
7
2
5
1
6
12
13
4
39 108
BTP207E-1.010-presentation 21/12/01, 9:342
-
8/11/2019 Catlogo Masterpact
4/114
3Merlin Gerin
drawout version1 arc chute cover2 auxiliary terminal shield
3 auxiliaries connection block4 fixed chassis
5 safety shutters6 arc chute7 remote control voltage release8 motor for electrical charging of
stored energy mechanism
9 control unit (AC system)10 front cover
1
2
3
6
7
8
10
9
5
4
015159
BTP207E-1.010-presentation 21/12/01, 9:343
-
8/11/2019 Catlogo Masterpact
5/114
Merlin Gerin4
Automatic source-changeover controller
Fixed circuit breaker
50%
20%
STR 58 U
0.63
IoIr tr
0.8
0.5 1
xIn
90
105
tr
%Ir
.88
.9 .92.95
.98
1.8.85
xIo
60120 240
480
1530
at1 .5Ir
Im tm
3
4 5
6
8
101.5
2
xIr
.3
.4 .3
.1
.1
.2
on I2t off
.2
0
Ir fault
tr
Imfault
tm
I
faultIh
th
i
test
+
+
T
R
test
Ih1200A Max th
400
500 600800
1000
1200250
320
A
.3
.4 .4
.2
.1.2
on I2t off
.3
.1
I
8
12 14
19
22
Max.2
4
xIn
Ic1 Ic2
.86
.9 .93
.95
.98
1.8.85
xIr
.7
.8 .85
.95
.5.6
.9
1xIr
Ir :
Im:
th:
min.
norm
overcurrent
ground
isolation renforceclasse II
sparation totaleentre chaque phase
dclencheurs voltmtriquesaccessibles l'avant
Masterpact: presentation
safety and reliabilitycreduced, simple maintenance (maincontacts easily accessible, with wearindication feature);cdouble insulation from the front face;cpositive contact indication;cauxiliary devices can be fitted on sitewithout adjustment;cfewer parts than conventional ranges (by afactor of 5-10);ca trip interlock ensures that the circuitbreaker is open during connection anddisconnection;cconnection to top or bottom terminals;cfully tropicalised as standard.
stored energy operating
mechanismMasterpact circuit breakers are operated viaa stored energy mechanism forinstantaneous opening and closing.The mechanism is charged either manuallyor electrically. Closing and openingoperations can be initiated either from thelocal pushbuttons on the circuit breaker frontface, or by remote control.
common auxiliariesfrom 800 A to 6300 AAuxiliariescaccessible from the front, mounted in aseparate compartment insulated from powercircuits;csecured by a single screw;cadjustment-free;ccan be fitted on site.
ccccc Source changeover systemFour solutions are available:vmechanical interlocking for 2 or 3 circuitbreakers, adaptable to various source-changeover configurations;vautomatic source-changeover controller,easy to implement on any two suitablyequipped circuit breakers (electricallycharged operating mechanism, etc.) (for 3circuit breakers, consult us);vcomplete assembly including 2 or3 mechanically (rod assembly) interlocked
circuit breakers, adaptable to varioussource-changeover configurations;vcomplete assembly including2 mechanically (rod assembly) interlocked
circuit breakers and an automatic source-changeover controller, adaptable to varioussource-changeover configurations. Readyfor connection.
other possibilities ccccc Fixed circuit breakerThe fixed circuit breaker is derived from themoving part of the drawout circuit breaker byadding a fixing bracket on each side.
ccccc Switch versionThe switch (unprotected) version is deriveddirectly from the standard circuit breaker, but
does not implement a control unit (or themagnetic trip units used with the DC circuitbreakers). Available models are:vstandard: type HI and NI;vhigh performance: type HF, equipped witha protection system that instantaneously
opens the circuit breaker in the event ofclosure under fault conditions.
ccccc Earthing switchA special short-circuit and earthing switch isavailable on request for the M08 to M32Hdrawout types, 3 or 4 poles. Please consult
us.
ccccc 1000 V AC circuit breakers
E
29490
voltage releasesaccessible from thefront
total phaseseparation
double insulation
035929
053061
053060
053058
BTP207E-1.015-presentation 21/12/01, 9:354
-
8/11/2019 Catlogo Masterpact
6/114
Merlin Gerin 5
Drawout Masterpact DC circuit breaker
Fixed Masterpact DC circuit breaker
device identificationM 20 H1
breaking capacity;cN1: standard;cH1: H2: high performance;cL1: current limiting;cDC: direct current.
ratingcrated current / 100.
familycMasterpact: LV power aircircuit breaker.
DC circuit breakersMasterpact DC circuit breakers are availablein fixed and drawout versions. They benefitfrom the AC range technology andadvantages.c5 available ratings from 1000 to 8000 A;c2 breaking capacities, 100 kA at 500 V,50 kA at 750 and 1000 V;
ca circuit-breaker version offeringinstantaneous short-circuit protection withan adjustable, magnetic trip unit (DINA);
ca switch (unprotected) version.note:up to 125 V DC, the devices in the AC
range (M08 to M63) may be used only in theswitch version, in which case a three-pole,type HI device should be used, with:c1 pole for the positive polarity;c
1 pole for the negative polarity;c1 pole not used.
Auxiliaries
All the auxiliaries designed for theMasterpact AC circuit breakers may be usedon the DC versions, with the exception of theposition switches, indicating the connected(CE), disconnected (CD) and test (CT)positions.Auxiliary connections are made via one ortwo manually disconnectable plugs thatremain accessible from the front.
AccessoriesStandard Masterpact DC range equipmentincludes an arc-chute cover (CC) and, on
drawout versions, safety shutters (VO).Interphase barriers (EIP) are not availablefor the DC range.
86094
86096
BTP207E-1.015-presentation 21/12/01, 9:355
-
8/11/2019 Catlogo Masterpact
7/114
Merlin Gerin6
Masterpact: presentation
Masterpact circuit breakers are the product
of Merlin Gerins vast experience in the fieldof power circuit breakers. They incorporateall the qualities of traditional air circuitbreakers while drawing on certain of theadvantages specific to moulded-case circuit
breakers. In particular, they require nopreventive maintenance.
ease of installationMasterpact is a complete and rationallydesigned range.c10 ratings;c4 breaking-capacity levels;c6 control units;ca complete range of auxiliaries andaccessories;
cnumerous versions (three and four-poledevices, fixed and drawout versions, etc.).
Masterpact circuit breakers are easy toincorporate in switchboards.ca single frame size from 800 to 3200 A,
thus making for standardised columns;can upper safety clearance equal to zerodue to the arc-chute cover, on both the fixedand drawout versions;cbuilt-in measurement functions in thecontrol units;cauxiliaries are the same for the entirerange and may be easily implemented (onlya screwdriver is required).
Masterpact circuit breakers are easy to
connect to the main distribution system.
call types of connections are available(horizontal and vertical terminals, front andmixed connections);cconnections are possible with bars of anythickness;cconnection to the input power source is
possible on the upper or lower terminals ofthe circuit breakers.
Due to their small size, Masterpact circuitbreakers can replace most existingcircuit breakers.
continuity of serviceMasterpact circuit breakers are designedwith continuity of service in mind. Theresult is:ctotal time discrimination on the N1 and H1circuit breakers and maximum discrimination
on H2 circuit breakers;cfactory pre-setting of Masterpact circuitbreakers which never require any periodicmaintenance;chigh electrical endurance: 10 000 cycles at1600 A and 30 cycles at 50 kA, withoutmaintenance;cpreventive indications: load-sheddingindication switch, long-time thresholdoverrun alarm, etc.;ceasy access to the main contacts fitted
with mechanical wear indicators. An optionalfunction on the STR68 control unit is theremote indication of contact wear, thus
making possible continuous monitoring ofcircuit breakers during their service life.
operating safetyThe insulating casing of Masterpactcircuit breakers provides for:cuser safety:vdouble insulation on the front face(class II),vauxiliary circuits in a compartmentinsulated from the power circuits;cswitchboard safety when the circuitbreaker is in the open position:
veach pole is effectively isolated in its ownhousing,vlimitation of external disturbances.
Positive contact indicationThe position indicator cannot indicateopen unless the poles are effectively
separated by the required distance.The circuit breakers automatically open
during racking in and out.
reliabilitycMasterpact circuit breakers comprise tentimes fewer parts than traditional devices.
They are easier to produce and morereliable.c
the Masterpact circuit-breaker factory iscertified ISO 9002;cthe design of Masterpact circuit breakers
is modular with delayed differentiation(highest possible number of common partson all models). The result is shorter deliverytimes and enhanced reliability.
,
0
36634
025179
2500 A Masterpact circuit breaker
Top: front connectionBottom: rear vertical connection
BTP207E-1.020-contents 21/12/01, 9:386
-
8/11/2019 Catlogo Masterpact
8/114
7
LV power air
circuit breakers and
switch-disconnectors
Masterpact
2/ functions andcharacteristics
page
generales characteristics 0
circuit breaker selection 0
switch-disconnectors 0
dimensions an weights 0
control unit selection 0
control unit accessories 0
electrical auxiliaries 0
mechanical accessories 0
source changeover systems 0
BTP207E-2.001-content 21/12/01, 9:397
-
8/11/2019 Catlogo Masterpact
9/114
Merlin Gerin8
MERLIN GERINmasterpact
M32 H2
Ui 1000V 50/60Hz
Ue 380/440V 480/690V
Icu 100kA 85kA
Ics 100kA 85kA
Icw 75kA 1s
IEC 947-2
Masterpact: functions and characteristics
general characteristics
Standardised characteristics indicated onthe rating plate:Ui: rated insulation voltageUe: rated operational voltage
Icu: ultimate breaking capacity, for variousvalues of the rated operational voltage UeIcs: service breaking capacityIcw: short-time withstand current
: suitable for isolation
Masterpact circuit breakers comply with allthe major international standards:
cInternational standard IEC 947-2;
cNorth American standards (please consult
us):UL 489, ANSI C37-50, CSA C22-2,NEMA AB1 et SG3;
cJapanese standards: JIS 160 and C 8372.
They also comply with the following national
standards:
cFrance NF C 63-120;
cGermany VDE 0660;
cUnited Kingdom BS 4752;
cAustralia AS ;
cItaly CEI.Masterpact circuit breakers comply with the
specifications of the marine classificationcompanies (Veritas, Lloyd's Register ofShipping, Det Norske Veritas, etc.).
IEC 947-2This standard replaces IEC 157-1,applicable since 1973.The circuit breaker selection criteria are
unchanged, but the new standard providesthe user with a better guarantee concerningquality and performance.Circuit breakers are subjected to tests thatare more representative of real operating
conditions.IEC 947-2 also clarifies the notion ofbreaking capacity.
cIcu :the ultimate breaking capacity, whichmust be greater than or equal to the 3-phase
short-circuit current at the point ofinstallation of the circuit breaker, a value
unlikely to be reached under real conditions;cIcs :the service breaking capacity,generally expressed as a percentage of the
ultimate breaking capacity (25, 50, 75 or100 % of Icu). It corresponds to a short-circuit current that is more likely to bereached under real conditions. The circuitbreaker must continue to operate normally
after having interrupted a current equal toIcs several times;
cIcw :short-time withstand current forcircuit breakers belonging to category B(category B refers to circuit breakers withtime discrimination and category A to thosewithout time discrimination).Furthermore, IEC 947-2 takes into accountrecent technological advances:
csuitability for isolation recognised for
circuit breakers having passed specialelectrical and mechanical tests;
cindustrial earth-fault circuit breakerscovered by an appendix;
cdefinition of tests designed to ensure
coordination between two circuit breakers.
conformity with standards
tropicalisationAs standard, Masterpact circuit breakerscomply with NF C 63-100 standard level 2
conditions (95 % relative humidity at 45 Cor 80 % at 55 C, hot and humid climateconditions). They also comply with thefollowing standards:
cIEC 68-2-30 damp heat;
cIEC 68-2-2 dry heat;cIEC 68-2-11 salt spray;cIEC 68-2-1 low temperatures during
storage.Corrosive atmospheres: Special grease or
other surface coatings available (pleaseconsult us).
pollution degreeMasterpact circuit breakers are certified foroperation in pollution degree IVenvironments as defined byIEC standard 947 (industrial environments).
E29049
BTP207E-2.020-gen. charact.. 21/12/01, 9:408
-
8/11/2019 Catlogo Masterpact
10/114
-
8/11/2019 Catlogo Masterpact
11/114
Merlin Gerin6
Masterpact: functions and characteristics
circuit breaker selection
(1) Defined for a power factor of 0.25 if 20 < kA rms 50 or 0.20 of kA rms > 50.(2) Closing at 6 x Ie and opening at 0.17 x Un.(3) For control unit STR 68 U, the minimum ratingIn is 400 A.
Masterpact circuit breakersnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
type of circuit breakerultimate breaking capacity (1) Icu AC 50/60 Hz 220/415 V(kA rms) 440 V
500/690 V
service breaking capacity Ics (% Icu)
short-time withstand current Icw AC 50/60 Hz 0.5 s
(kA rms) 1 s3 s
making capacity (kA peak) Icm AC 50/60 Hz 220/415 V
440 V
500/690 V
electrodynamic withstand (kA peak)
utilisation category
suitability for isolation
break time
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In
690 V - In
motor control (AC3-947-4) (2) 690 V
electrical characteristics as per standard Nema AB1breaking capacity (kA) 480 V
600 V
protection (see following pages)sensor ratings (A) (see page 12)
control unit instantaneous STR 18 Mprotection type distribution STR 28 D
selective STR 38 S
universal STR 58 U
STR 68 U
installation and connectionsconnection
version drawout
fixed
indication and measurement auxiliariesauxiliary switches
electronic trip unit related functions
control auxiliariesauxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessorieslocking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
0
35928
Masterpact M16 H1
BTP207E-2.060-M08...16 21/12/01, 9:416
-
8/11/2019 Catlogo Masterpact
12/114
7Merlin Gerin
M08 M10 M12 M163, 4 3, 4 3, 4 3, 4
800 1000 1250 1600
800 1000 1250 1600
1000 1000 1000 1000
8000 8000 8000 8000
690 690 690 690
N1 H1 H2 L1 N1 H1 H2 L1 N1 H1 H2 L1 N1 H1 H2 L140 65 100 130 40 65 100 130 40 65 100 130 40 65 100 130
40 65 100 110 40 65 100 110 40 65 100 110 40 65 100 110
40 65 85 65 40 65 85 65 40 65 85 65 40 65 85 65
100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 %
40 65 65 12 40 65 65 12 40 65 65 12 40 65 65 17
30 50 50 12 30 50 50 12 30 50 50 12 40 50 50 1722 32 32 12 22 32 32 12 22 32 32 12 22 32 32 12
84 143 220 286 84 143 220 286 84 143 220 286 84 143 220 286
84 143 220 242 84 143 220 242 84 143 220 242 84 143 220 242
84 143 187 143 84 143 187 143 84 143 187 143 84 143 187 143
84 143 143 24 84 143 143 24 84 143 143 24 84 143 143 34
B B B B B B B B B B B B B B B B
c c c c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms
20 20 20 20 20 20 20 20 20 20 20 15 20 20 20 15
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
10 10 10 3 10 10 10 2.7 10 10 10 2.5 10 10 10 2.2
10 10 10 3 10 10 10 2.7 10 10 10 2.5 10 10 10 2.2
10 10 10 - 10 10 10 - 10 10 10 - 10 10 10 -
40 65 100 - 40 65 100 - 40 65 100 - 40 65 100 -
40 65 65 - 40 65 65 - 40 65 65 - 40 65 65 -
200 to 800 (3) 200 to 1000 (3) 200 to 1250 (3) 200 to 1600 (3)
c c c c c c c c c c c c
c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
front and rear connections
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
BTP207E-2.060-M08...16 21/12/01, 9:417
-
8/11/2019 Catlogo Masterpact
13/114
Merlin Gerin8
Masterpact: functions and characteristics
circuit breaker selection (cont.)
Masterpact circuit breakersnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
type of circuit breakerultimate breaking capacity (1) Icu AC 50/60 Hz 220/415 V(kA rms) 440 V
500/690 V
service breaking capacity Ics (% Icu)
short-time withstand current Icw AC 50/60 Hz 0.5 s
(kA rms) 1 s3 s
making capacity (kA peak) Icm AC 50/60 Hz 220/415 V
440 V
500/690 V
electrodynamic withstand (kA peak)
utilisation category
suitability for isolation
break time
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In
690 V - In
motor control (AC3-947-4) (2) 690 V
electrical characteristics as per standard Nema AB1breaking capacity (kA) 480 V
600 V
protection (see following pages)sensor ratings (A) (see page 12)
control unit instantaneous STR 18 Mprotection type distribution STR 28 D
selective STR 38 S
universal STR 58 U
STR 68 U
installation and connectionsconnection
version drawout
fixed
indication and measurement auxiliariesauxiliary switches
electronic trip unit related functions
control auxiliariesauxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessorieslocking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
0
36635
Masterpact M50 H1
(1) Defined for a power factor of 0.25 if 20 < kA rms
50 or 0.20 of kA rms > 50.(2) Closing at 6 x Ie and opening at 0.17 x Un.(3) For control unit STR 68 U, the minimum ratingIn is 400 A.(4)83% if Ue i440 V.(5)Consult us for full rated neutral.
BTP207E-2.070-M20...63 21/12/01, 9:428
-
8/11/2019 Catlogo Masterpact
14/114
9Merlin Gerin
M20 M25 M32 M40 M50 M633, 4 3, 4 3, 4 3, 4 3, 4 3, 4
2000 2500 3200 4000 5000 6300
2000 2500 3200 4000 2500 (5) 3200
1000 1000 1000 1000 1000 1000
8000 8000 8000 8000 8000 8000
690 690 690 690 690 690
N1 H1 H2 L1 N1 H1 H2 L1 H1 H2 H1 H2 H1 H2 H1 H255 75 100 130 55 75 100 130 75 100 75 100 100 150 100 150
55 75 100 110 55 75 100 110 75 100 75 100 100 150 100 150
55 75 85 65 55 75 85 65 75 85 75 85 85 85 85 85
100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % (4) 100 % 100 % (4)
55 75 75 17 55 75 75 17 75 75 75 75 100 100 100 100
55 75 75 17 55 75 75 17 75 75 75 75 100 100 100 10050 57 57 17 50 75 75 17 75 75 75 75 100 100 100 100
121 165 220 286 121 165 220 286 165 220 165 220 220 330 220 330
121 165 220 242 121 165 220 242 165 220 165 220 220 330 220 330
121 165 187 143 121 165 187 143 165 187 165 187 187 187 187 187
121 165 165 34 121 165 165 34 165 165 165 165 220 220 220 220
B B B B B B B B B B B B B B B B
c c c c c c
25 to 30 ms without intentional time delay and 9 ms for type L1
70 ms 80 ms
15 15 15 15 15 15 15 15 15 15 10 10 10 10 10 10
10 10 10 10 10 10 10 10 10 10 5 5 5 5 5 5
9 9 9 2 8 8 8 1.8 4 4 3 3 3 3 2 2
7 7 7 2 6 6 6 1.8 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5
7 7 7 - 6 6 6 - 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5
55 75 100 - 55 75 100 - 75 100 75 100 100 125 100 150
55 75 75 - 55 75 75 - 75 75 75 75 100 100 100 100
200 to 2000 (3) 300 to 2500 (3) 600 to 3200 2000 to 4000 2000 to 5000 2000 to 6300
c c c c c c c c c c c c c c
c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
c c c c c c c c c c c c c c c c
front and rear connections rear connections
c c c c c c
c c c c c (3P only)
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c(3P only)
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
BTP207E-2.070-M20...63 21/12/01, 9:429
-
8/11/2019 Catlogo Masterpact
15/114
Merlin Gerin10
Masterpact: functions and characteristics
circuit breaker selection (cont.)Masterpact 1000 V AC
Masterpact 1000 V AC circuit breakersnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
type of circuit breakerultimate breaking capacity (1) Icu AC 50/60 Hz 220/415 V(kA rms) 440 V
500/690 V
1000 V
service breaking capacity Ics (% Icu)
short-time withstand current Icw AC 50/60 Hz 0.5 s(kA rms) 1 s
3 s
making capacity (kA peak) Icm AC 50/60 Hz 220/415 V
440 V
500/690 V
1000 V
electrodynamic withstand (kA peak)
utilisation category
suitability for isolation
break time
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In690 V - In
motor control (AC3-947-4) (2) 690 V
protection (see following pages)sensor ratings (A) (see page 12)
control unit instantaneous STR 18 Mprotection type distribution STR 28 D
selective STR 38 S
universal STR 58 U
STR 68 U
installation and connectionsconnection
version drawout
fixed
indication and measurement auxiliariesauxiliary switches
electronic trip unit related functions
control auxiliariesauxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessorieslocking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC) (as standard on the 1000 V version)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
(1) Defined for a power factor of 0.25 if 20 < kA rms 50 or 0.20 of kA rms > 50.(2) Closing at 6 x Ie and opening at 0.17 x Un.(3) For control unit STR 68 U, the minimum ratingIn is 400 A.
Masterpact M20 H1 1000 V
0
52380
BTP207E-2.080-M08...32 21/12/01, 9:4210
-
8/11/2019 Catlogo Masterpact
16/114
-
8/11/2019 Catlogo Masterpact
17/114
Merlin Gerin12
Masterpact: functions and characteristics
switch-disconnectors
Masterpact switch-disconnectorsnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
type of switch-disconnectorshort-time withstand current Icw AC 50/60 Hz 0.5 s(kA rms) 1 s
3 s
making capacity (kA peak) Icm AC 50/60 Hz 440 V
500/690 V
electrodynamic withstand (kA peak)suitability for isolation
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In
690 V - In
motor control (AC3-947-4) (1) 690 V
protectionSTR 08 dummy unit (no protection)
STR 18I (protection against short-circuits when closing)
installation and connectionsconnection
version drawout
fixed
indication and measurement auxiliariesauxiliary switches
control auxiliariesauxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessorieslocking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
(1) Closing at 6 x Ie and opening at 0.17 x Un.
Masterpact M10 NI
0
52384
BTP207E-2.082-inter M08 21/12/01, 9:4212
-
8/11/2019 Catlogo Masterpact
18/114
13Merlin Gerin
M08 M10 M12 M163, 4 3, 4 3, 4 3, 4
800 1000 1250 1600
800 1000 1250 1600
1000 1000 1000 1000
8000 8000 8000 8000
690 690 690 690
NI HI HF NI HI HF NI HI HF NI HI HF40 65 65 40 65 65 40 65 65 40 65 65
30 50 50 30 50 50 30 50 50 30 50 50
22 32 32 22 32 32 22 32 32 22 32 32
84 105 143 84 105 143 84 105 143 84 105 143
84 105 143 84 105 143 84 105 143 84 105 143
84 143 143 84 143 143 84 143 143 84 143 143c c c c
70 ms
20 20 20 20 20 20 20 20 20 20 20 20
10 10 10 10 10 10 10 10 10 10 10 10
10 10 10 10 10 10 10 10 10 10 10 10
10 10 10 10 10 10 10 10 10 10 10 10
10 10 10 10 10 10 10 10 10 10 10 10
c c c c c c c c
c c c c
front and rear connections
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
c c c c
BTP207E-2.082-inter M08 21/12/01, 9:4213
-
8/11/2019 Catlogo Masterpact
19/114
Merlin Gerin12
Masterpact: functions and characteristics
switch-disconnectors (cont.)
Masterpact switch-disconnectorsnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C
rating of 4th pole (A)
rated insulation voltage (V) Ui
rated impulse withstand voltage (V) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
type of switch-disconnectorshort-time withstand current Icw AC 50/60 Hz 0.5 s(kA rms) 1 s
3 s
making capacity (kA peak) Icm AC 50/60 Hz 440 V
500/690 V
electrodynamic withstand (kA peak)suitability for isolation
closing time
endurance (C-O cycles) x 1000 mechanical with maintenance
no maintenance
electrical no maintenance 440 V - In
690 V - In
motor control (AC3-947-4) (1) 690 V
protectionSTR 08 dummy unit (no protection)
STR 18 I (protection against short-circuits when closing)
installation and connectionsconnection
version drawout
fixed
indication and measurement auxiliariesauxiliary switches
control auxiliariesauxiliary releases (MN, MNR, MX, XF)
motor mechanism (MCH)
operation counter (CDM)
installation and connection accessorieslocking by padlock or keylock/mismatch protection
safety shutters (VO)
interphase barriers (EIP)
partitioning fixture (AC)
arc-chute cover (CC)
terminal-block cover (CB)
door frame (CDP)
transparent cover (CCP)
(1) Closing at 6 x Ie and opening at 0.17 x Un.
Masterpact M50 HI
0
52388
BTP207E-2.084-inter M20 21/12/01, 9:4312
-
8/11/2019 Catlogo Masterpact
20/114
13Merlin Gerin
M20 M25 M32 M40 M50 M633, 4 3, 4 3, 4 3, 4 3, 4 3, 4
2000 2500 3200 4000 5000 6300
2000 2500 3200 4000 2500 3200
1000 1000 1000 1000 1000 1000
8000 8000 8000 8000 8000 8000
690 690 690 690 690 690
NI HI HF NI HI HF HI HF HI HF HI HF HI HF55 75 75 55 75 75 75 75 75 75 100 100 100 100
55 75 75 55 75 75 75 75 75 75 100 100 100 100
50 57 57 50 75 75 75 75 75 75 100 100 100 100
84 105 165 84 105 165 105 165 105 165 187 220 187 220
84 105 165 84 105 165 105 165 105 165 187 220 187 220
121 165 165 121 165 165 165 165 165 165 220 220 220 220c c c c c c
70 ms 80 ms
15 15 15 15 15 15 15 15 10 10 10 10 10 10
10 10 10 10 10 10 10 10 5 5 5 5 5 5
9 9 9 8 8 8 4 4 3 3 3 3 2 2
7 7 7 6 6 6 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5
7 7 7 6 6 6 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5
c c c c c c c c
c c c c c c
front and rear connections rear connections
c c c c c c
c c c c c (3P only)
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c (3P only)
c c c c c c
c c c c c c
c c c c c c
c c c c c c
c c c c c c
BTP207E-2.084-inter M20 21/12/01, 9:4313
-
8/11/2019 Catlogo Masterpact
21/114
Merlin Gerin12
Masterpact: functions and characteristics
dimensions and weights
Masterpact circuit breakers and switch-disconnectorstype
dimensions and weightsdimensions W x H x D drawout 3P(mm) 4P
fixed 3P
4P
maximum weight drawout 3P(kg) 4P
fixed 3P
4P
Masterpact circuit breakers and switch-disconnectors
type
dimensions and weightsdimensions W x H x D drawout 3P(mm) 4P
fixed 3P
4P
maximum weight drawout 3P(kg) 4P
fixed 3P
4P
Masterpact 1000 V circuit breakers
type
dimensions and weightsdimensions W x H x D drawout 3P(mm) 4P
maximum weight drawout 3P(kg) 4P
sensor selectionIn (A) 200 250 320 400 500 600 630 800 1000 1200
Ir threshold 80 100 125 160 200 240 250 320 400 480
settings (A) to 200 to 250 to 320 to 400 to 500 to 600 to 630 to 800 to 1000 to 1200
In (A) 1250 1600 2000 2500 3000 3200 4000 5000 6000 6300
Ir threshold 500 640 800 1000 1200 1280 1600 2000 2400 2500
settings (A) to 1250 to 1600 to 2000 to 2500 to 3000 to 3200 to 4000 to 5000 to 6000 to 6300
The table above indicates:c all the available sensor ratings In;c the limits of the long time Ir settings.
BTP207E-2.090-M08...63 21/12/01, 9:4712
-
8/11/2019 Catlogo Masterpact
22/114
13Merlin Gerin
M08 M10 M12 M16 M20 M25 M32N1/H1/H2/L1 N1/H1/H2/L1 N1/H1/H2/L1 N1/H1/H2 L1 N1/H1/H2 L1 N1/H1/H2 L1 H1/H2
NI/HI/HF NI/HI/HF NI/HI/HF NI/HI/HF NI/HI/HF NI/HI/HF HI/HF
435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367
550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367
422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290
537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290
65 65 65 69 82 82 130 82 130 130
80 80 80 85 102 102 150 102 150 150
43 43 43 46 55 55 80 55 80 80
54 54 54 58 69 69 90 69 90 90
M40 M50 M63
H1/H2 H1/H2 H1/H2HI/HF HI/HF HI/HF
550 x 439 x 367 815 x 484 x 367 1045 x 484 x 367
815 x 484 x 367 1045 x 484 x 367 1045 x 484 x 367
537 x 356 x 290 802 x 356 x 290
801 x 356 x 290
150 215 245
200 230 265
90 110
110
M08 M10 M12 M16 M20 M25 M32
H1 H1 H1 H1 H1 H1 H1
435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367
550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367
65 65 65 69 82 82 130
80 80 80 85 102 102 150
BTP207E-2.090-M08...63 21/12/01, 9:4713
-
8/11/2019 Catlogo Masterpact
23/114
Merlin Gerin14
16080 1250 2000 2500 4000 6300500032001600400
STR 18 M
STR 28 D
STR 38 S
STR 58 U
STR 68 U
Masterpact: functions and characteristics
control unit selection
Masterpact M08 to M63 circuit breakers are
equipped with microprocessor-basedelectronic control units.
All the protection functions are powered by
the AC system and no auxiliary powersupply is required. The same is true for mostof the complementary functions.
Each control unit of the Masterpact rangecorresponds to a certain type of application(instantaneous, distribution, selective,universal).All the STR control units measure the truerms value of the current and are thereforenot affected by harmonics that may bepresent on the system.
current settings (A)
protectionSTR 18 M
3
I I
t
0
push to reset
STR 18 M
I
xIn
test
+
1
8
1214
19
22max2
4
2
5
3
4
5
Key:
1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuit
breaker can be closed again.
2 maximum protection rating.
3 instantaneous pick-up.
4 test connector.
5 holes for sealable cover plate screws.
instantaneous protection
distribution protection
selective protection
universal protection
E31218
E31219
E30703
other functionsc fault indication.
BTP207E-2.110-unit cont. 21/12/01, 9:4714
-
8/11/2019 Catlogo Masterpact
24/114
15Merlin Gerin
protectionSTR 28 DKey:
1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuit
breaker can be closed again.
2 ammeter digital display.
3 bar graph indicating load level (% Ir).
4 maximum protection rating.
5-6 long-time current setting as a function of:Io x Ir x In.
7 instantaneous pick-up.
8 overcurrent indicator LED.
9 noted settings.
10 test connector.
11 holes for sealable cover plate screws.
push to reset
II1 I2 I3
90%
50%
20%
STR 28 D
Io
xIn
90
105%Ir
xIo
Im
xIr
Ir
Im
t
i
test
+
Ir :
Im :
Ir
1
.88
.9 .92
.95
.981.8
.850.5
0.63 0.8
1
34 5
6
8101.5
2
2
3
4
11
5
6
7
9
8
10
11
protectionSTR 38 SKey:
1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuit
breaker can be closed again.
2 ammeter digital display.
3 bar graph indicating load level (% Ir).
4 maximum protection rating.
5 overcurrent indicator LED.
6-7 long-time current setting as a function of:
Io x Ir x In.8 short-time pick-up.
9 short-time delay.
10 noted settings.
11 instantaneous pick-up.
12 earth fault pick-up.
13 earth fault delay.
14 LEDs indicating tripping on long-time,short-time or earth fault.
15 test connector.
16 holes for sealable cover plate screws.
17 battery supplying backup power for faultindication.
18 fault indication reset and/or battery test.
19 re-indication of last fault.
push to reset
II1 I2 I3
90%
50%
20%
STR 38 S
xIn xIo
Im tm
xIr on I2t off
Ir fault
tr
Im faulttm
I
faultIh
th
t
i
test
+
+
T
F
test
Ih th
A on I2t off
I
xIn
Ir :
Im :
th :
overcurrent
ground
1
2
3
4
16
90
105
%Ir
Io
0.5
0.63 0.8
1
Ir
.88.9 .92
.95
.981.8
.85
34 5
6
8101.5
2
.3.4 .3
.2
.10.1
.2
max. off
400500 600
800
10001200250
320
.3.4 .4
.3
.2.1.1
.2
5
6
7
8 9
12
11
1314
16 15
19
18
17
10
7
6
I IIr
t
0
other functionsc fault indication;c indication of LT overrun;c ammeter;c self-monitoring (internal overheating).
11
Ir Im
8
I I
t
0
7
9
12
13
I2t ON
I2t OFF
other functionsc fault indication;c indication of LT overrun;c ammeter;c self-monitoring (internal overheating);c indication of type of fault (F).
E30704
E31220
E31221
E33950
BTP207E-2.110-unit cont. 21/12/01, 9:4715
-
8/11/2019 Catlogo Masterpact
25/114
Merlin Gerin16
Masterpact: functions and characteristics
control unit selection (cont.)
protectionSTR 58 U
push to reset
II1 I2 I3
90%
50%
20%
STR 58 U
tr
Ir fault
tr
Im faulttm
I
faultIh
th
t
i
test
+
+
T
R
Ftest
Ir :
Im :
th :
Max.
norm
overcurrent
ground
2
3
4
5
21
6
7
8
21
16
V
reset V II+T L+I
L+I+T
ToffL
L+T
xIn
Io
0.5
0.630.8
1
90
105%Ir .88
.9 .92
.95
.981.8
.85
Ir
xIo
60
120 240
480
1530
tr
at 1.5Ir
Im tm
xIr on I2t off
34 5
6
8101.5
2
.3.4 .3
.2
.10.1
.2
I
xInoff
22
191412
8
4
2
Ih 1200A Max th
A on I2t off
400500 600
800
10001200250
320
.3.4 .4
.3
.2.1.1
.2
Ic1 Ic2
xIr
.86.9 .93
.95
.9818
.85
.7.8 .85
.9
.951.5
.6
xIr
1
12
9
10
11
13
15
14
17
19
24 18
20
23
22
protectionSTR 68 U
STR 68 U
reset
1 2 3 max
A
Ir Im I
s
Ih
tm
th
fault
adjustments
24 V DC
test
KA
S
1
tr
A
trip no trip MEM
test
2%
load monitoringmaintenance
N 1 2 3
Hz
Cos
kW
MWh
+
685812
V
10
8
8
9
7
611
5
4
3
2
2
1Key:
1 reset button: pops out when the circuit
breaker has tripped on a fault and mustbe pressed (reset) before the circuitbreaker can be closed again.
2 selection of displayed value (voltage,power, energy, power factor, frequency).
3 display of current or interrupted current(when flashing).
4 local fault indication and indication reset.5 selection and indication of protection
parameter to be set.
6 selection and indication of loadmonitoring parameters.
7 adjustment and saving of parametersettings.
8 holes for sealable cover plate screws.9 test connector.10 test.11 maintenance indicator.
Ir Im I I
t
0
I2t ON
I2t OFFLT setting(Ir)
ST pick-up(Im)
ST time delay(tm)
instantaneouspick-up (I)
earth faulttime delay (th)
earth faultpick-up (Ih)
LT time delay(tr)
other functionsc fault indications and memorisation;c maintenance indicator;c ammeter;c integrated test;c power measurement;c load monitoring (R);c self-monitoring (internal overheating,
malfunction of the microprocessor);c zone selective interlocking for earth
faults.
other functionsc fault indication;
c indication of LT overrun;c ammeter;c self-monitoring (internal overheating);c fault type indication (F);c segregated alarm switch for selected
fault type (V);c zone selective interlocking (Z);c load monitoring (R);c communication (COM).
9
13
Ir Im
10
I I
t
0
8
11
14
15
I2t ON
I2t OFF
E30705
E31222
E31223
E33949
Key:
1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuitbreaker can be closed again.
2 selection of fault type for segregatedalarm: Ir and/or Im and/or IhL: long-time fault (Ir)I: short-time fault (Im/l)T: earth fault (Ih)
3 ammeter digital display.4 bar graph indicating load level (% Ir).5 maximum protection rating.6 overcurrent indicator LED.7-8 long-time current setting as a function of:
Io x Ir x In.
9 long-time trip delay10 short-time pick-up.
11 short-time delay.12 adjustment of thermal memory after
tripping.
13 instantaneous pick-up.14 earth fault pick-up.15 earth fault delay.16 noted settings.17-18 load monitoring settings.19 test connector.20 battery supplying backup power for fault
indication.21 holes for sealable cover plate screws.
22 fault indication reset and/or battery test.23 re-indication of last fault.24 LEDs indicating tripping on long-time,
short-time or earth fault.
BTP207E-2.120-unit cont. 21/12/01, 9:5016
-
8/11/2019 Catlogo Masterpact
26/114
17Merlin Gerin
I
t
0
Ih
Th
I2t ON
I2t OFF
options for STR control units
zone selective interlocking(Z)
"earth fault" protection(T or W)
This earth fault protection is designed to
protect the installation against the risks offire due to high earth faults (not to beconfused with schemes designed for the
protection of persons against electricalshock).Two types of earth protection are available
for Masterpact:c residual current type (T): the control unit
calculates the vector sum of the phase andneutral (if distributed) currents;c source ground return type (W): the control
unit acts directly on the signal received froman external current transformer installed onthe source earthing circuit.
earth fault curves for the STR 58
load monitoring (R) Remote indication of threshold overrun forload-shedding or load-reconnectionpurposes.
I
t
0
Ic2
Ic1
load monitoring curves for the STR 58
communication: STR 58 Utransmission: STR 68 U
Transmission of the control unit settings,circuit breaker position and current, voltageand power measurements.
indication andmeasurement
c ammeter (I):a digital displaycontinuously indicates the current of thephase with the greatest load (Imax). By
pressing a scroll button, it is also possible todisplay successively the readings of I1, I2,I3, Ineutral and Ih.
In addition, three bargraphs provide animmediate visual indication of the load oneach of the three phases.
E26037
E31225
A number of circuit breakers areinterconnected one after another by a pilot-
wire. In the event of a short-time or earthfault, the control unit applies the set timedelay only if it receives a signal from a
downstream circuit breaker. If not, it tripsinstantaneously (tripping time as 0.1 short-time setting). In this way, the fault is clearedrapidly by the nearest circuit breaker. Thethermal stresses in the installation areminimised while maintaining timediscrimination throughout the entire
installation.Opto-electronic outputsThe use of opto-transistors ensures totalisolation between the internal circuits of thecontrol unit and the circuits wired by theuser.
Other information that can be transmittedincludes the value of the interrupted current,the state of the thermal memory and themaintenance indications
c indication of type of fault (F);
c segregated alarm switch for selectedfault type (V), wired in parallel with theopening button (MX), it disables circuitbreaker closing for the selected type of fault.
BTP207E-2.120-unit cont. 21/12/01, 9:5017
-
8/11/2019 Catlogo Masterpact
27/114
Merlin Gerin18
Masterpact: functions and characteristics
control unit selection (cont.)STR 18 M to STR 58 U
control unittype of circuit breaker
basic protectionlong time protection LT
current setting (Ir) as a function of Io and Ir Io = In x ...
settings tripping between 1.05 and 1.20 x Ir Ir = Io x ...
time delay (tr)
accuracy: + 0 - 20 % tr at 1.5 Ir (s)
tr at 6 Ir (s)
tr at 7.2 Ir (s)
short-time protection ST
pick-up (Im) adjustable by Im sett ing Im = Ir x .. .
time delay (tm) tm setting with I2t OFF
tm setting with I2t ON
max. overcurrent time before tripping (ms)
max. break time (ms)
instantaneous protection I
pick-up setting
setting range
accuracy
OFF switch on front face
basic functionsfault indication
for tripping on a fault indicator button on front face
fault trip alarm contact (SDE)
for LT setting overrun LED (lights up at 0.9 Ir and flashes at 1.05 Ir)
LT overrun alarm contact (optional)
self-powered
self-monitoring internal overheatingoptional functionsammeter (I) display between 0.2 and 1.20 In
current readings with an accuracy of 1.5 % (1) (3)
bargraph indication of current levels with a resolution of 10 %
self-powered
earth fault protection: residual current(T)or source ground return (W) type on request
pick-up adjustable by Ih setting Ih = In x ...
time delay (th) th setting with I2t ON and I2t OFF
max. overcurrent time before tripping (ms)
max. break time (ms)
indication of type of fault (F)(LT - CT/Inst. - Earth) by LEDs on front face
power supply with battery module
with external power supply by AD module
segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth)output via relay contact
power supply by AD module
zone selective interlocking (Z)
by opto-electronic contact on ST and earth (T/W) fault
load monitoring (R)
adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ...
time delay tr1 at 1.5 Ic1
time delay tr2 at 1.5 Ic2
output via opto-electronic contact 0.1 A / 240 V
time delay for load reconnection
communication (COM)
2 outputs for data transmission to Dialpact module
transmitted values all control unit settings
alarms: Ir warning, fault type, self-monitoringload monitoring thresholds
current values I1, I2, I3, IN
power supply by AD module
STR 58 U
048449
(1) Plus the uncertainty of the built-in transformers:3 %.
(2) Max = In x ... N1/H1 H2 L1
630 A 22 28 14800 - 1000 A 22 28 101200 - 1600 A 22 24 82000 A 17 20 62500 A 12 14 63000 - 3200 A 10 12 4000 - 6300 A 8 10
(3) Continuous display for the phase with thegreatest load.
(4) 0.2 x In to 1200 A without external powersupply or 0.1 x In with external power supply.
(5) Accuracy with respect to the long time LTprotection.
(6) Resettable maximum ammeter.
BTP207E-2.130-STR1858 21/12/01, 9:5118
-
8/11/2019 Catlogo Masterpact
28/114
19Merlin Gerin
STR 18 M STR 28 D STR 38 S STR 58 UN1, H1, H2 N1, H1, H2 N1, H1, H2, L1 N1, H1, H2, L1
c c c
0.5 to 1 (4 settings) 0.5 to 1 (4 settings) 0.5 to 1 (4 settings)
0.8 to 1 (8 settings) 0.8 to 1 (8 settings) 0.8 to 1 (8 settings)
fixed fixed adjustable
120 120 15 30 60 120 240 480
7.5 7.5 0.94 1.88 3.75 7.50 15 30
5.2 5.2 0.65 1.30 2.60 5.20 10 21
c c
1.5 to 10 15 % 1.5 to 10 15 %
0 0.1 0.2 0.3 0.4 0 0.1 0.2 0.3 0.4
0.1 0.2 0.3 0.1 0.2 0.3
0 80 140 230 350 0 80 140 230 350
80 140 230 350 500 80 140 230 350 500
c c c c
Im = In x ... Im = Ir x ... I = In x ... I = In x ...
2 x In to Max (2) 1.5 to 10 x Ir fixed at high set (Max) (2) 2 x In to Max (2)
15 % 15 % 20 % 15 %
on types N1 and H1 on types N1 and H1 on types N1 and H1
c c c c
c c c c
c c c
c c c
c c c
c c c
c c c
I1, I2, I3, IN, Imax (6) I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3, IN, Ih, Imax (6)
I1, I2, I3 I1, I2, I3 I1, I2, I3
c c c
c c
0.1 at 1 (max 1200 A) (4)15 % 0.1 at 1 (max 1200 A) (4)15 %
0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4
60 140 230 350 60 140 230 350
140 230 350 500 140 230 350 500
c c
c c
c c
c
c
c
0.8 to 1 (8 settings) 1 % (5)
0.5 x tr
0.25 x tr
c
fixed at 10 s
c
c
c
c
c
c
BTP207E-2.130-STR1858 21/12/01, 9:5119
-
8/11/2019 Catlogo Masterpact
29/114
Merlin Gerin20
Masterpact: functions and characteristics
control unit selection (cont.)STR 68 U
presentationThe STR 68 U control unitoffersmeasurement, supervision and energy
management functions.Microprocessor technology, liquid crystaldisplay and function keys ensure highaccuracy and easy adjustment.
The standard STR 68 U control unit providesthe following:
c universal protection;
c ammeter function;
c indication of fault type;c values of interrupted currents;c maintenance indicator;
c integrated test.
The following options can be added:c power measurement module (P);c "earth fault" protection module;c control and indication modules (M) with or
without transmission to a supervisor.Certain M modules can provide loadmonitoring or zone selective interlocking forearth fault protection.
The STR 68 control unit provides:
c overload protection, with long timeprotection LT including:
v adjustable time delay and thermalmemory possibility;c short-circuit protection:v delayed, with short time function ST, forwhich the I2t curve can be disabled by the
user,
v instantaneous, with the INST function thatcan be disabled by the user;
protection
036630
c "earth" protectionwith timediscrimination or zone selective interlocking.The protection is of the residual current type(or source ground return type on request).
basic functions c ammeter;c maintenance indicator;
c fault indications and values of theinterrupted currents;
c self-monitoring: in the event of
overheating of the control unit or amalfunction of the microprocessor, an alarmsignal is transmitted. Unless the "servicecontinuity" option was ordered, the circuit
breaker will trip ;c test.
BTP207E-2.140-unit cont. 21/12/01, 9:5120
-
8/11/2019 Catlogo Masterpact
30/114
21Merlin Gerin
optional functions c power measurement (P);c indication and control (M)Thirty-one different modules offer variouscombinations of functions including:
v load monitoring,
v trip indication,
v self-monitoring,
v zone selective interlocking for "earth fault"protection,
v transmission of data to a supervisor(modules M17 to M31 only).Each STR 68 U control unit can be equippedwith only one M module.For the function offered by each M module,
(see page xxx).
c "earth fault" protection (T)
Of the residual current type (or sourceground return type on request), it is possibleto obtain zone selective interlocking bycombining the T option with the appropriate
M option.
BTP207E-2.140-unit cont. 21/12/01, 9:5121
-
8/11/2019 Catlogo Masterpact
31/114
Merlin Gerin22
Masterpact: functions and characteristics
control unit selection (cont.)STR 68 U
control unit STR 68 Utype of circuit breaker N1. H1. H2. L1basic protectionlong time protection LT c
current setting (Ir) adjustable in 2 % steps Ir = In x ... 0.4 to 1 (mini 160 A)
tripping between 1.05 and 1.20 x Ir
time delay (tr) adjustable
accuracy: + 0 - 20 % tr at 1.5 Ir (s) 15 30 60 120 240 480
tr at 6 Ir (s) 0.94 1.88 3.75 7.50 15 30
tr at 7.2 Ir (s) 0.65 1.30 2.60 5.20 10 21
thermal memory (30 mn) standard + OFF position
short time protection ST c
pick-up (Im) adjustable in 4 % steps Im = Ir x ... 0.4 to 15 10 %
time delay (tr) tm setting with I2t OFF 0.1 0.2 0.3 0.4
tm setting with I2t ON 0.1 0.2 0.3 0.4max. overcurrent time before tripping (ms) 60 140 230 350
max. break time (ms) 140 230 350 500
thermal memory (10 mn) standard
instantaneous protection I c
fixed pick-up I (kA) M08 to M16 : 65. M20 to M63: 75.
pick-up (I) adjustable in 8 % steps from In to fixed pick-up (mini at 1.6 kA)
accuracy 15 %
OFF switch on front face on types N1 and H1
basic functionsfault indication
for tripping on a fault button on front face c
fault trip alarm contact (SDE) c
for Ir setting overrun LED on front face c
self powered cindication of fault type LEDs on front face cand value of interrupted current display on ammeter c
power supply 110 V - 220 V - 380 V AC 50/60 Hz
self-monitoring internal overheating and microprocessor errors c
maintenance indicator c
displays degree of wear of main contacts between 0 and 655
ammeter c
current readings with an accuracy of 3 % I1. I2. I3. Imax (1)
self-powered c
integrated test c
(1) Current of the phase carrying the highest load.
BTP207E-2.160-STR68U 21/12/01, 9:5222
-
8/11/2019 Catlogo Masterpact
32/114
23Merlin Gerin
optional functionsearth fault protection: residual current (T) or source ground return (W) type on request c(zone selective interlocking with option M)pick-up (Ih) adjustable in 2 % steps Ih = In x ... 0.2 to 1 (maxi 1200 A. mini 160 A ) 15 %
time delay (th) th setting 0.1 0.2 0.3 0.4
max. overcurrent time before tripping (ms) 60 140 230 350
max. break time (ms) 140 230 350 500
thermal memory (10 mn) c
power measurement (P) (see opposite page for details) c
output characteristics opto-decoupled 0.2 A - 24 V DC
integrated power supply c
voltage measurements U12. U23. U31 160 to 690 1 %
V1N. V2N. V3N 90 to 400 V 1 %
frequency measurement: f 45 to 65 Hz 0.5 %
power factor measurement: cos - 1 to + 1 2.5 %
instantaneous active power measurement: P - 9000 to 9000 kW 5 %
instantaneous active energy measurement: EP 0 to 9999 MWh 5 %
indication and control (M): 31 modules (1 per control unit) providing the following combinations: c
load monitoring 2 possible options
option 1: 2 load limit pick-ups Ic1 and Ic2 Ic1 = In x ... 0.2 to 1 In 2 % steps
delay tr1 = 0.5 x tr 5 %
Ic2 = In x ... 0.2 to 1 In 2 % steps
delay tr2 = 0.25 x tr 5 %
option 2: 1 load limit pick-up Ic1 Ic1 = In x ... 0.2 to 1 In 2 % steps
1 load reconnection pick-up Ic2 delay tr1 = 0.5 x tr 5 %
Ic2 = In x ... 0.2 to 1 In 2 % steps
delay tr2 = 60 s fixed 5 %
zone selective interlocking for earth fault protection
trip indications
for type of fault long-time, short-time, earth
for self-monitoring (1) alarm
transmission
characteristics type RS 485
protocol JBus
speed 9600 bauds
max. number of addresses 255
values transmitted: type of fault tripping on Im, Ir, Ih
circuit breaker status self-monitoring alarm
settings all pick-ups and delays
circuit breaker status open or closed
values transmitted: ammeter currents I1, I2, I3 max
power system status voltmeter voltages U12, U23, U31
voltages V1N, V2N, V3N
power factor, frequency cos , f
instantaneous active power and energy: P. EP - 9000 to 9000 kW. 0 to 9999 MWh 5 %
instantaneous reactive power and energy: Q. EQ - 9000 to 9000 kVar. 0 to 9999 MVahr 5 %
power supply 24, 48, 125 V DC or 100, 240 V AC
(1)Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.
BTP207E-2.160-STR68U 21/12/01, 9:5223
-
8/11/2019 Catlogo Masterpact
33/114
Merlin Gerin24
option m selection Option M can be incorporated in control unitSTR68U to provide the following functions:cRS485 data transmission at 9600 bauds toJBUS protocol;cremote signal via opto-electronic output;czone selective interlocking for earth faultprotection.
The following table indicates the functions of
the different versions, designated m01 tom31.For terminal wiring see page xxxx.
without data transmissionoption m01 m02 m03 m04 m05 m06 m07 m08 m09 m10 m11 m12 m13 m14 m15 m16
remoting
load monitoring and control
pick-up Ic1 indication c c c c c c c c c c
load shedding c c c c c c c c c c c c c
pick-up Ic2 indication c c c c
load shedding c c c c c c c c c
load reconnection c c c c
fault indications
Ir c c c c c c c c c c c
Im/I c c c c c c c c c c c c c c c c(1)
Ih c c c c c c c c c c
self-monitoring c c c c c c c c c
zone selective interlocking
on the earth fault protection c c c c c
with data transmissionoption m17 m18 m19 m20 m21 m22 m23 m24 m25 m26 m27 m28 m29 m30 m31
data transmission
all parameters (see page xxxx) c c c c c c c c c c c c c c c
remoting
load monitoring and control
pick-up Ic1 indication c c c
load shedding c c c c c cpick-up Ic2 indication c
load shedding c
load reconnection c
fault indications
Ir c
Im/I c c c c c
Ih c c c c
self-monitoring c c c c
zone selective interlocking
on the earth fault protection c c c c
Masterpact: functions and characteristics
control unit selectionSTR 68 U (cont.)
(1)Two separate outputs for Im and I.
BTP207E-2.170-STR68U 21/12/01, 9:5224
-
8/11/2019 Catlogo Masterpact
34/114
25Merlin Gerin
Factory adjustments
The STR68U control unit is factory adjustedas follows:
LT setting Ir In
time delay tr 480 s
ST pick-up Im 4 In
time delay tm 0,2 s
INST pick-up I maxi
T earth fault pick-up Ih 0,2 In
time delay th 0,1 s
load monitor Ic1 In
Ic2 In
Earth fault protection (option T)
operating zones
Basic functions: long time LT,short time ST, instantaneous INST
2
5
Ir Im
3
I I
t
0
1
4
I2t ON
I2t OFF
I
t
0
T1
T2
I2t ON
I2t OFF
overcurrent settings1 : LT setting Ir (long time)2 : LT time delay tr (long time)3 : ST pick-up Im ( short time)4 : ST time delay tm ( short time)5 : INST pick-up I (instantaneous)
earth fault protection settingsT1 : earth fault pick-up IhT2 : earth fault time delay th
load monitoring and control(option M)
Operation with 2 load limit pick-ups
I
t
0
Ic2
Ic1
I
t
0
Ic2
Ic1
load monitoring and control settingsIc1 pick-up (load limit)Ic2 pick-up (load limit)
load monitoring and control settingsIc1 pick-up (load limit)Ic2 pick-up (load reconnection)
Operation with 1 load limit and 1 loadreconnection pick-up
E26
037
E26
038
E26039
E26042
BTP207E-2.170-STR68U 21/12/01, 9:5225
-
8/11/2019 Catlogo Masterpact
35/114
Merlin Gerin26
Masterpact: functions and characteristics
control unit accessories
battery module (PIL)Complementary to the local indication of thefaults (F option for STR 38 and STR 58 tripunits), the battery module avoids the need
for any external power supply to save frontface indications.
This module is equipped with a button for re-
activation, of fault indications that have beende-activated by the battery power-savingfeature. A test button is used to check thebattery status.
interface module ET44Compulsory with the data transmissionoption on the STR 68 trip unit, the ET44interface module allows:
c setting of the transmission speed;c definition of the address of the breaker(which will not be affected by any drawout
breaker manipulation);
c the direct remote control of the breaker,thanks to two outputs directly controlledthrough the data transmission.
Installation: on vertical plate or symmetricalrail.
Power supply: 24 V DC with galvanicisolation, or AD type power module.
0
48327
048321
relay module (MR6)For relaying of information from outputs ofmodules m01 to m32 of control unit STR 68via output changeover contacts10 A/220 V AC or 3 A/24 V DC.
Installation : on vertical plate or symmetrical
rail.Power supply module (AD) is required.
025172
power supply module (AD)These modules can be used to powercontrol unit complementary functions whichcannot be self-powered by the built-in
current transformers:cSTR 38 and STR 58: fault type indication(F);cSTR 58: segregated alarm switch (V);cSTR 58: communication option (COM);
cSTR 28, STR 38, STR 58: ammeter (I) forload less than 20% of In.cSTR 68: indication and saving of
025173 measurements, alarms, maintenance
indicator;cMR6 module.Moreover, these modules protect the trip unitfrom transient overvoltages thanks togalvanic isolation.
Available voltages:c AC 50/60 Hz: 110 V, 220 V or 380 V(20 %; +15 %) (consumption 10 VA);
cDC : 24/30 V, 48/60 V, 125 V (20 %)(consumption 10 W).
Installation: on vertical plate or symmetricalrail.
047035
052172
battery module (BAT)Providing a complement to the AD module,
the battery module provides backup powerfor display indications and maintenanceindicator data in the event of a power failure.
Float connected between the power supplyand the control unit, it ensures a backup
time of approximately:
c 12 h with STR 38 and STR 58 controlunits;c 1.5 h with STR 68 control unit.
Installation: on vertical plate or symmetricalrail. (ambient temperature from: 0 C to+50 C).
mini test kit (BU)This self-contained portable unit is used tocheck STR 18 M to STR 58 U control unitsoperations and breaker tripping.Power supply: five 9 V alkaline batteries (notsupplied).
This test kit is common to the Masterpact,Compact NS, C, CM ranges.
025171
portable test kit for STR 18to STR 58The portable test kit is used:cfor control unit STR 68, to power, check
and carry out adjustments and tests on thebreaker/control unit assembly (control unitwithout auxiliary power supply connected);
cfor other control units, to check theoperation of the trip unit by measuring theactual trip time:
vlong-time protection,vshort-time protection,vinstantaneous protection,
vearth-fault protection.
Power supply: 110, 220 V AC 50/60 Hz.This test kit is common to the Masterpact,Compact NS, C, CM ranges.
BTP207E-2.180-unit cont 21/12/01, 9:5626
-
8/11/2019 Catlogo Masterpact
36/114
27Merlin Gerin
Masterpact: functions and characteristics
auxiliary power supplies
The protection functions and most of the
options available for the STR control unitsare self-powered. An auxiliary power supplyis nevertheless required for certain uses.
(1)Not recommended: possible with a 24 V DC source, class 2, 5 Watt, ripple factor < 10%.(2)Display will in this case be "". Auxiliary supply allows to save maximeter information.(3)Ih pick-ups for which protection is not self-powered are printed in red on the trip unit front face.
self-powered auxiliary power supply
direct AD + BAT terminals battery
connection modules
STR 28 / 58
protection : LT, ST, INST yes
option I if I u20% In yes
if I < 20% In no no (1) yes (2) F1/F2 noor single phase load
option F no no (1) yes F1/F2 yes
option FV no no (1) yes F1/F2 no
option ALR yes
option R yes
option T/W if Ih u0.2 x In yes
if Ih < 0.2 x In no (3) no (1) yes F1/F2 no
STR 68
protection : LT, ST, INST, T, W yes
other functions : see drawings page 71
BTP207E-2.180-unit cont 21/12/01, 9:5627
-
8/11/2019 Catlogo Masterpact
37/114
Merlin Gerin14
Masterpact: functions and characteristics
auxiliaries
electrical operatingmechanismAdded to the manual charging mechanism,a motor charges and automaticallyrecharges the stored-energy spring uponbreaker closing making possible fastO-C-O cycles.Opening and closing operations areinstantaneous.The manual mechanism remains availablefor emergency use.
The electrical operating mechanismincludes:
cthe gear motor(MCH);
ca closing release (XF);ca shunt release (MX) or an undervoltagerelease (MN) for opening;
c"springs charged" limit switch changeovercontact (CH).
The addition of the electrical operatingmechanism does not alter circuit breakerdimensions.
characteristics geared motor MCH
power supply 50/60 Hz (V) 100/127 - 200/240 - 250/277 - 380 - 415 - 440 - 480
consumption (VA) 180
DC (V) 24/30 - 48/60 - 100/125 - 200/250 consumption (W) 180
motor start-up surge 2 to 3 In for 0.1 s
charging time 3 to 4 s
013282
BTP207E-2.202-circuit-breaker 21/12/01, 9:5814
-
8/11/2019 Catlogo Masterpact
38/114
15Merlin Gerin
operation counter(CDM)With gear-motor option only. The operationcounter is read from the front and gives thetotal number of breaker operating cycles.
035932
BTP207E-2.202-circuit-breaker 21/12/01, 9:5815
-
8/11/2019 Catlogo Masterpact
39/114
Merlin Gerin16
Masterpact: functions and characteristics
auxiliaries(cont.)
Shunt release (MX)
This release instantaneously opens thebreaker when energised. The supply can bemaintained or automatically disconnected. In
the latter case, the user can series connectan internal auxiliary contact (OF).
releasesTwo types of voltage releases can be usedfor remote opening of Masterpact circuitbreakers.
Undervoltage releases
cinstantaneous (MN)This release instantaneously opens thebreaker when its supply voltage drops below
a value between 35 % and 70 % of its ratedvoltage.
If the release is not energised, the breakercannot be closed (either manually ofelectrically). Any attempt to close will have
no effect on the main contacts.Closing is possible when the release voltagereaches 85 % of its rated value.
ctime delayed (MNR)To prevent the breaker tripping in the eventof transient voltage dips, this release has abuilt-in time delay.A special version, available on request,allows instantaneous tripping (from amushroom-head emergency off button) bythe wiring of an external contact.
closing release (XF)This device releases the breaker closingmechanism when the spring is charged.Energisation can be maintained, as theclosing release provides an antipumpingfunction.
Note: anti-pumping function:After the breaker has been opened, either by
fault trip or by manual or electrical operation,anti-pumping is provided by requiringcancellation of the initial closing command
before reclosure of the breaker is possible.The closing release is supplied on requestwith the manual operating mechanism
(1)500/525 V AC not available for MNR.
(2)MNR: DC, 125 V only.
0
16813
036051
Release combinationsEach Masterpact circuit breaker can beequipped with:1 MX + 1 MN + 1 XF, or2 MX + 1 XF
characteristics undervoltage and shunt releases closing release
MN MNR MX XF
breaker response time 90 ms 5 0.5 s-0.9 s 50 ms 10 70 ms + 10, 15at Un 1.5 s-3 s i3 200 A
80 ms 10 > 3 200 A
operating thresholds
opening from 0.35 to 0.7 Un 0.7 to 1.1 Un
closing 0.85 Un 0.85 to 1.1 Un
power supply
AC 50/60 Hz (V) 100 -110/127 -200 -220/250 -277 -380/415 -440/480 -500/525(1)
consumption (VA) 20
DC (V) (2) 24 - 30 - 48 - 60 - 100/110 - 125 - 200/220 - 250
consumption (W) 15
BTP207E-2.204-auxiliaries 21/12/01, 10:0816
-
8/11/2019 Catlogo Masterpact
40/114
17Merlin Gerin
Changeover switches to indicate "connected"position "CE"
Double break changeover switches "OF"
auxiliary switchesIn addition to the main contact positionindication on the front, 3 auxiliary switchblocks are available to indicate the open andclosed breaker positions.cstandard: 4 contacts (O) (2 normallyopen 2 normally closed);coptional: 4 directly-operated double
break changeover switches (OF)whichoperate only when the minimum isolatingdistance between the main contacts is
reached;coptional: 24 additional changeoverswitches (OFSUP block).Thesemicroswitches can be parallel connected inpairs to increase the rated current and
breaking capacity (in drawout version only).
"ready to close" contact(PF)Optional:This contact simultaneously indicates the
following:cthe breaker is open;cthe stored-energy mechanism is charged;
cthe mechanism is correctly reset;cthe breaker opening pushbutton is notlocked;
cno opening order is present.
This contact can be series connected to theclosing release (XF) to disable the anti-pumping function.
connected/disconnectedposition carriage switchesIn addition to the local "connected/test/
disconnected" position indicator, two seriesof optionalcarriage switches are availablefor the fixed chassis (of drawout circuit
breaker).ca block of 4 changeover switchestoindicate "connected" position (CE);
ca block of 2 changeover switchestoindicate "disconnected" position (CD). Thedisconnected position is indicated only whenthe minimum isolating distance betweenmain and auxiliary circuits has beenreached.
By series connection of these contacts thetest position can be indicated.c1 changeover switchto indicate "test"position (CT).
contact characteristics
"spring charged"contact (CH)In addition to the local mechanical indicatorand the "ready to close" contact, the gear-motor limit switch changeover contact canindicate that the operating mechanism isready (spring charged). This contact issupplied as standard with the gear motor.
fault-trip indication (SDE)As standard and independent from thedifferentiated fault indications on the controlunit, any fault-trip is indicated by:c1 fault-trip indicator/reset button;c1 changeover contact (SDE).
The reset button must always be pressedafter a fault-trip to enable breaker closing.Optional: automatic reset, allowing remotebreaker closing without local resetting (the
SDE contact operates up to the reset).
auxiliary contacts type O OF OFSUP SDE PF CE CD CT CH
quantity changeover 4 24 1 1 4 2 1 1
NO 2 NO
NC 2 NC
current rating (A) 10 10 10 10 10 10 10 10 10
breaking capacity 110 V 15
AC 50/60 Hz(A rms.) 240 V 10 10 10 10 10 10 10 10 10
pf u 0.3 380 V 6 10 6 5 5 6 6 6 6
480 V 6 10 6 6 6 6 6
600 V 3 6 3 3 3 3 3DC(A) 48 V 3 5 3 3 3 3 3 3 3
L/R i 0.01 s 125 V 0.5 3 0.5 0.3 0,3 0.5 0.5 0.5 0.5
250 V 0.25 3 0.25 0.15 0.15 0.25 0.25 0.25 0.25
500 V 0.5
0
16814
018242
016524
Additional changeover switches ("OFSUP" block)
BTP207E-2.204-auxiliaries 21/12/01, 10:0817
-
8/11/2019 Catlogo Masterpact
41/114
Merlin Gerin18
a: partitioning fixture (AC)b: interphase barrier (EIP)
Fixed portion of drawout circuit breakers with arc chute andterminal shield
035928
Fixed portion of drawout circuit breakers with safety shutters
safety shutters (VO)Optional:mounted on the fixed portion ofdrawout breakers, the safety shutters
automatically block access to thedisconnection contacts when the breaker isin the disconnected or test position (degree
of protection IP 20).
Masterpact: functions and characteristics
accessories
terminal shield (CB)Optional:attached to the fixed portion ofdrawout circuit breakers, this cover preventsaccess to the electrical auxiliary connectionterminals.
arc chute cover (CC)Optional: attached to the fixed portion ofdrawout circuit breakers or on the fixedcircuit breaker, this cover eliminates the
safety clearance requirement above thebreaker (this option is incompatible with frontconnection on top).
interphase barrier(EIP)Optional:attached to the fixed portion ofdrawout breaker (Masterpact iM40 3P), theinsulated partitions for vertical installationbetween connection pads to:creinforce insulation at connection points ininsulated busbar installation;cprevent arc propagation to the breaker inthe event of a line side fault on the mainbusbars.
partitioning fixture (AC)Optional:attached to the fixed portion ofdrawout breakers (except when equippedwith front connections), this fixture providesIP30 partitioning between the breakercompartment (accessible from the front) andthe connection zone (located in the rear). It
simplifies partition cut-outs.Example of partition cut-out forMasterpact M08 to M32.
shutter lock (VVC)Optional: mounted on the fixed portion ofdrawout breakers, a mobile and lockable
slide (padlocks not supplied) is used to:clock the shutters in the closed position;,chold the shutters in the open position.
A support is provided at the back of theframe to hold the slide when not in use. Asecond slide is supplied:con request for Masterpact i 3200 A ;cin standard for Masterpact 4000 Ato 6300 A.
360
445 (3 ples) et 560 (4 ples)
60
plan de fixationchssis
rfrence
445 (3 pole) and 560 (4 pole)
chassis
fixingdatum
016818
013280
a b
28518
BTP207E-2.206-accessories 21/12/01, 10:0918
-
8/11/2019 Catlogo Masterpact
42/114
19Merlin Gerin
Auxiliaries for drawout version
Auxiliaries for fixed version
016814
door frame (CDP)Optional:fixed to the cublicle door, thisframe provides an equipment seal function
(degree of protection IP 405).Suitable for fixed and drawout patterns.
Earth connectionThe earth connection terminal (drawoutpattern) is on the left hand side of thechassis. It is marked with the symbol t
transparent cover (CCP)Optional:hinge-mounted and equipped witha screw-closure, this cover is designed forthe door frame (CDP). It provides a degreeof protection of IP549.Suitable for fixed and drawout patterns.
01
6819
auxiliaries connection
Fixed versionConnection by one or two plugs,disconnectable and accessible from the front(screwless tunnel terminals for flex cable upto 2.5 mm2).
Drawout versioncstandard: connection to a terminal blockin the front of the fixed frame (screwless
tunnel terminals for flex cable up to2.5 mm2).The breaker auxiliary circuits are connected
by connection blocks that operateautomatically to isolate the auxiliaries whenthe breaker is in "disconnected" position.
On request, an additional 5-way terminalblock (BS) is available to provide five
common points.
coptional: by one or two plugs,disconnectable and accessible from the
front, installed on the mobile part of theassembly.
"Connected/disconnect/test" positioncontactsInstalled on the fixed chassis, these contacts
are directly connected by 6.35 mmconnectors.
015561
breaker mismatchprotectionOptional:for drawout version only, thissystems allows only correctly matchedbreakers (rating, type wiring, etc.) to beinserted in a given fixed frame.Two matching parts (1 for the fixed chassisand 1 for the mobile assembly) can be usedto create 20 different user selectedcombinations.
035940
BTP207E-2.206-accessories 21/12/01, 10:0919
-
8/11/2019 Catlogo Masterpact
43/114
Merlin Gerin20
"disconnected","connected" and "test"position locking (1)
Mounted on the frame and accessible withthe cubicle door locked, this system isavailable in two versions:
c"disconnected" position locking;
vas standard by 1 padlocking device (1 to 3padlocks not supplied),
voptional:by a locking device with 1 or 2
Profalux key locks;c"disconnected", "connected" and "test"
position locking (optional);
vby 1 padlocking device, with 1 to 3padlocks not supplied (VEC),
vby 1 locking device, with 1 or 2 Profaluxkey locks (VSPEC),
padlocks 1 keylock 2 keylocks
"disconnected"standard
"disconnected" "disconnected"standard optional
"disconnected" "disconnected" "disconnected"standard optional optional
"disconnected,connected"
"disconnected, "disconnected,
connected" connected""disconnected, "disconnected, "disconnected,connected" connected" connected"
pushbutton locking deviceOptional: this padlockable device (padlocksnot supplied) prevents direct operation of thecircuit breaker by covering the "on" and "off"pushbuttons. This locking device can also beused for lead sealing.
Masterpact: functions and characteristics
accessories (cont.)
(1) keylock typesProfalux B24 D4ZRonis 1351 BKirk CN22-12
Castell SK7113/1Trayvou L1P1E
"off" position lockingdeviceOptional:a Profalux key lock locks thebreaker in "off" position by holding thepushbutton in its depressed position.
pushbutton locking deviceby padlocks (not supplied) VBP
"off " position locking device (1)
1 Profalux key lock VSPA1
2 Profalux key locks, identical profiles VSPA2
adaptation fixture for 1 Profalux key lock, lock not supplied VSPRAC
On request1 Ronis key lock VSRA1
2 Ronis key locks, identical profiles VSRA2
adaptation for 1 Castell key lock, lock not supplied VSCA
adaptation for 1 Kirk key lock, lock not supplied VSKA
Remarkscthe keylocks are of the captive key type,i.e. key free when locked;cProfalux and Ronis keylocks can be usedtogether;
ca second Profalux or Ronis lock, identicalto the one mounted on the chassis, can besupplied separately.
035932
035931
BTP207E-2.208-accessories 21/12/01, 10:0920
-
8/11/2019 Catlogo Masterpact
44/114
21Merlin Gerin
016817
"disconnected" position lockingby padlocks (not supplied) as standard
1 Profalux key lock VSPC1
2 Profalux key locks, identical profiles VSPC2
2 Profalux key locks, different profiles 2 VSPC1
adaptation fixture for Profalux key lock (lock not supplied) VSPRCC
On request
1 Ronis key lock VSRC1
2 Ronis key locks, identical profiles VSRC2
2 Ronis key locks, different profiles 2 VSRC1
adaptation fixture for Castell key lock (lock not supplied) VSCC
adaptation fixture for Kirk key lock (lock not supplied) VSKC
adaptation fixture for Trayvou key lock (lock not supplied) VSTC
"disconnected", "connected" and "test" position lockingby padlocks (not supplied) VEC
1 Profalux key lock VSEPC
2 Profalux key lock, different profiles 2 VSEPC
On request
1 Ronis key lock VSERC
2 Ronis key locks, differents profiles 2 VSERC
adaptation fixture for Castell key lock (lock not supplied) VSECC
adaptation fixture for Kirk key lock (lock not supplied) VSEKC
door interlockOptional: mounted on the chassis, this lockprevents the cubicle door from being openedwhen the breaker is in the "connected"position. If the breaker is put into the"connected" position with the door open, the
latter can be closed without disconnectingthe breaker.
racking interlockOptional: this lock prevents insertion of thebreaker racking handle when the cubicle
door is open. It can be defeated by pressingon the unlocking mechanism.
withdrawal/spring chargedinterlockOptional: this lock prevents withdrawal ofthe breaker from the chassis when the
springs are charged.Incompatible with MN or MNR release.
a: racking interlockb: door latch
door interlock
right-hand side VPECD
left-hand side VPECG
racking interlock VPOC
withdrawal/spring charged interlock VEAA
a b
BTP207E-2.208-accessories 21/12/01, 10:0921
-
8/11/2019 Catlogo Masterpact
45/114
Merlin Gerin36
Masterpact: functions and characteristics
automatic source-changeover systems
Masterpact