    Obras Realizadas

    A Prodesmec

    A Poltica de Qualidade

    BBAP / BBCP - Barramento Blindado - 160A AT 800A

    BVAP / BVCP - Barramento Ventilado - 1000A AT 6000A

    BCAP / BCCP - Barramento Compacto - 1000A AT 6000ABRCP - Barramento Resinado - 1000A AT 4000A

    Cofre de derivao Plug-in

    Peas e acessrios para barramento blindado

    Critrios de barramento blindado

    Solicitaes especiais

    Critrios para utilizao de elementos de Dilatao e Bloqueio

    Normas de Fabricao e Testes

    03

    04

    05

    06

    08

    1012

    13

    14

    15

    16

    17

    18

    Obras Realizadas

    AEROPORTO DEVITRIA - ES

    HOSPITAL REGIONALNORTE - CE

    TRIBUNAL DE CONTASDO MUNICPIO - SP

    HOTEL COMFORTCONFINS - MG

    HIDROELTRICA HOJEDA- VENEZUELA

    SHOPPING COLINASSP

    DATA CENTERASCENTY - SP

    HOSPITALPAULISTANO - SP

    TEKSID DO BRASILMG

  • 7/24/2019 1441307192

    3/11

    54

    A Prodesmec Poltica de Qualidade

    Somos uma empresa nacional,especializada no desenvolvimento

    e fabricao de BarramentosBlindados para transporte e

    distribuio de energia eltricade baixa tenso (Bus-Way).

    Com mais de 1 dcada na rea

    de eletricidade, a Prodesmec unecada vez mais informaes para

    seu aperfeioamento dentro domercado, podendo assim mostrar

    sua grande expanso.

    Atender, satisfazer e superar todasas necessidades de nossos clientes

    atravs do atendimento aos requisitos.

    Melhorar continuamente a qualidadenos nossos processos, produtos e

    sistema de gesto da qualidade.

    Atualmente agrega esse know-how fabricao e montagem de

    equipamentos eltricos.

    Mais do que oferecer produtos e

    servios ao mercado, a empresa

    busca compreender as necessidadese peculiaridades de cada projeto,

    exercendo assim um controle rigoroso de

    custos e prazo, desenvolvendo soluesdenitivas, com garantia, segurana,

    qualidade e credibilidade aos seusmais diversos clientes.

    Com a Prodesmec

    a qualidade

    garantida!

  • 7/24/2019 1441307192

    4/11

    76

    Projetado para o transporte e distribuio de pequenas potncias. Possui o invlucro emchapa de ao galvanizado que tambm utilizado como condutor de proteo terra.

    Suas barras condutoras, em alumnio ou cobre eletrolticos so prensadas por isoladores dealta resistncia a esforos mecnicos e de curto-circuito alm de serem no higroscpicos.

    Com o grau de Proteo IP-42/54 ele protegido contra objetos slidos maiores que 1 mm,contra poeira e tambm contra queda de gotas dgua para uma inclinao mxima de 15 econtra projeo de gua.

    Esse produto, quando designado para a distribuio de energia, possui janelas de derivaoa cada 500mm para o acoplamento de cofres de derivao do tipo plug-in. Sua construopadro j dispe de dispositivo para lacre que impede o acesso indevido s barras condutoras,evitando assim riscos de acidentes.

    BBAP / BBCPBarramento Blindado -160A AT 800ADados TcnicosMODELO BBAP16 B BAP20 BBAP25 BBAP31 BBAP40 BBAP50 BBAP63 BBAP80

    Corrente Nominal A 160 200 250 315 400 500 630 800

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    D im en s es d o I nv l uc ro ( Ax L) m m 6 5x 17 0 6 5x 17 0 6 5x 17 0 8 5x 17 0 85 x1 70 1 05 x1 70 1 2 5x 17 0 1 45 x1 70

    Material do Invlucro Ao galvanizado

    Material do Condutor Alumnio

    Supercie do Condutor Estanhado

    Condutores por Fase / Neutro 1 1 1 1 1 1 1 1

    Corrente de curto circuito-Crista kA 24 30 40 50,4 52,5 58,8 60,9 69,3

    Corrente de curto circuito-Ecaz kA 12 15 20 24 25 28 29 33

    Resistncia por fase (20C) R20 m/m 0 ,2 58 9 0 ,2 04 2 0 ,1 57 6 0 ,12 50 0,09 93 0 ,0 75 9 0 ,0 61 4 0 ,0 49 0

    Resistncia por fase In R1 m/m 0 ,2 99 3 0 ,2 36 1 0 ,1 82 2 0 ,14 45 0,11 48 0 ,0 87 8 0 ,0 71 0 0 ,0 56 6

    Reatncia por fase X1 m/m 0 ,3 05 4 0 ,2 40 8 0 ,1 85 9 0 ,14 74 0,11 71 0 ,0 89 5 0 ,0 72 5 0 ,0 57 8

    Impedncia por fase Z1 m/m 0 ,4 27 6 0 ,3 37 3 0 ,2 60 3 0 ,20 64 0,16 40 0 ,1 25 4 0 ,1 01 5 0 ,0 80 9

    Queda de tenso - cos=0,7 V /1 00 m. A* 0 ,0 74 1 0 ,0 58 4 0 ,0 45 1 0 ,0 35 8 0 ,0 28 4 0 ,0 21 7 0 ,0 17 6 0 ,0 14 0

    Queda de tenso - cos=0,8 V /1 00 m. A* 0 ,0 73 2 0 ,0 57 7 0 ,0 44 6 0 ,0 35 3 0 ,0 28 1 0 ,0 21 5 0 ,0 17 4 0 ,0 13 8

    Queda de tenso - cos=0,9 V /1 00 m. A* 0 ,0 69 7 0 ,0 55 0 0 ,0 42 4 0 ,0 33 7 0 ,0 26 7 0 ,0 20 4 0 ,0 16 5 0 ,0 13 2

    Queda de tenso - cos=0,92 V /1 00 m. A* 0 ,0 68 4 0 ,0 54 0 0 ,0 41 6 0 ,0 33 0 0 ,0 26 2 0 ,0 20 1 0 ,0 16 2 0 ,0 12 9

    Queda de tenso - cos=1,0 V/ 10 0m .A * 0 ,0 51 8 0 ,0 40 9 0 ,0 31 6 0 ,0 25 0 0 ,0 19 9 0 ,0 15 2 0 ,0 12 3 0 ,0 09 8

    Peso - TRI+N+T (T = Carcaa) kg/m 9,3 9,6 10,1 11,2 11,8 13,3 14,8 16,7

    Peso - TRI+T (T = Carcaa) kg/m 9,0 9,2 9,6 10,6 11,0 12,3 13,6 15,1

    Grau de proteo IEC-60529 IP 42 / 54

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada

    Dados Tcnicos

    MODELO BBCP16 B BCP20 BBCP25 BBCP31 BBCP40 BBCP50 B BCP63 BBCP80

    Corrente Nominal A 160 200 250 315 400 500 630 800

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    D im en s es d o I nv l uc ro ( Ax L) m m 6 5x 17 0 6 5x 17 0 6 5x 17 0 6 5 x1 70 85 x1 70 8 5x 17 0 1 05 x1 70 1 05 x1 70

    Material do Invlucro Ao galvanizado

    Material do Condutor Cobre

    Supercie do Condutor Natural

    Condutores por Fase / Neutro 1 1 1 1 1 1 1 1

    Corrente de curto circuito-Crista kA 24 32 38 48,3 60,9 67,2 73,5 81,9

    Corrente de curto circuito-Ecaz kA 12 16 19 23 29 32 35 39

    Resistncia por fase (20C) R20 m/m 0 ,1 42 9 0 ,1 42 9 0 ,1 12 7 0 ,08 70 0,06 90 0 ,0 54 8 0 ,0 45 5 0 ,0 38 8

    Resistncia por fase In R1 m/m 0 ,1 64 7 0 ,1 64 7 0 ,1 29 9 0 ,10 02 0,07 95 0 ,0 63 2 0 ,0 52 4 0 ,0 44 8

    Reatncia por fase X1 m/m 0 ,1 68 0 0 ,1 68 0 0 ,1 32 5 0 ,10 23 0,08 11 0 ,0 64 4 0 ,0 53 5 0 ,0 45 7

    Impedncia por fase Z1 m/m 0 ,2 35 3 0 ,2 35 3 0 ,1 85 6 0 ,14 32 0,11 36 0 ,0 90 2 0 ,0 74 9 0 ,0 64 0

    Queda de tenso - cos=0,7 V/ 10 0m .A * 0 ,0 40 7 0 ,0 40 7 0 ,0 32 1 0 ,0 24 8 0 ,0 19 7 0 ,0 15 6 0 ,0 13 0 0 ,0 11 1

    Queda de tenso - cos=0,8 V/ 10 0m .A * 0 ,0 40 3 0 ,0 40 3 0 ,0 31 8 0 ,0 24 5 0 ,0 19 4 0 ,0 15 4 0 ,0 12 8 0 ,0 10 9

    Queda de tenso - cos=0,9 V/ 10 0m .A * 0 ,0 38 4 0 ,0 38 4 0 ,0 30 3 0 ,0 23 3 0 ,0 18 5 0 ,0 14 7 0 ,0 12 2 0 ,0 10 4

    Queda de tenso - cos=0,92 V/ 10 0m .A * 0 ,0 37 6 0 ,0 37 6 0 ,0 29 7 0 , 02 29 0, 01 82 0 , 01 44 0 ,0 12 0 0 ,0 10 2

    Queda de tenso - cos=1,0 V/ 10 0m .A * 0 ,0 28 5 0 ,0 28 5 0 ,0 22 5 0 ,0 17 4 0 ,0 13 8 0 ,0 10 9 0 ,0 09 1 0 ,0 07 8

    Peso - TRI+N+T (T = Carcaa) kg/m 12,0 12,0 13,1 14,5 16,7 19,0 21,4 23,5

    Peso - TRI+T (T = Carcaa) kg/m 11,0 11,0 11,9 12,9 14,7 16,5 18,4 19,9

    Grau de proteo IEC-60529 IP 42 / 54

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada* fotograa meramente ilustrativa

  • 7/24/2019 1441307192

    5/11

    98

    Dados Tcnicos

    M OD EL O B VA P1 00 B VA P1 25 B VA P1 60 BV AP 17 5 B VA P2 00 B VA P2 50 BV AP 30 0 B VA P3 50 B VA P4 00 B VA P4 50 B VA P5 00 B VA P6 00

    Corrente Nominal A 1000 1250 1600 1750 2000 2500 3000 3500 4000 4500 5000 6000

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    Dimenses do I nvlucro (Ax L) mm 1 25 x1 70 1 45 x1 70 1 0 5x 27 0 1 25 x2 70 1 25 x2 70 1 65 x2 70 1 45 x3 70 1 65 x3 70 1 45 x4 70 1 65 x4 70 1 65 x4 70 1 85 x4 70

    Material do Invlucro Ao galvanizado

    Material do Condutor Alumnio

    Supercie do Condutor Estanhado

    Condutores por Fase / Neutro 1 1 2 2 2 2 3 3 4 4 4 4

    Corrente de curto circuito-Crista kA 71,4 77,7 98,7 118,8 132 167,2 180,4 233,2 259,6 275 341 345,4

    Corrente de curto circuito-Ecaz kA 34 37 47 54 60 76 82 106 118 125 155 157

    Resistncia por fase (20C) R20 m/m 0 ,0490 0 ,03 76 0,0 307 0, 027 3 0 ,02 45 0, 018 8 0, 016 3 0,01 36 0, 0122 0 ,010 2 0,0 094 0, 0081

    Resistncia por fase In R1 m/m 0 ,0566 0 ,04 34 0,0 355 0, 031 5 0 ,02 83 0, 021 7 0, 018 9 0,01 57 0, 0142 0 ,011 8 0,0 109 0, 0094

    Reatncia por fase X1 m/m 0 ,0578 0 ,04 43 0,0 362 0, 032 1 0 ,02 89 0, 022 1 0, 019 3 0,01 60 0, 0144 0 ,012 0 0,0 111 0, 0096

    Impedncia por fase Z1 m/m 0 ,0809 0 ,06 20 0,0 507 0, 045 0 0 ,04 04 0, 031 0 0, 027 0 0,02 24 0, 0202 0 ,016 8 0,0 155 0, 0134

    Queda de tenso - cos=0,7 V /1 00 m. A* 0 , 01 40 0 ,0 10 7 0 ,0 08 8 0 ,0 07 8 0 ,0 07 0 0 ,0 05 4 0 ,0 04 7 0 ,0 03 9 0 ,0 03 5 0 ,0 02 9 0 ,0 02 7 0 ,0 02 3

    Queda de tenso - cos=0,8 V /1 00 m. A* 0 , 01 38 0 ,0 10 6 0 ,0 08 7 0 ,0 07 7 0 ,0 06 9 0 ,0 05 3 0 ,0 04 6 0 ,0 03 8 0 ,0 03 5 0 ,0 02 9 0 ,0 02 7 0 ,0 02 3

    Queda de tenso - cos=0,9 V /1 00 m. A* 0 , 01 32 0 ,0 10 1 0 ,0 08 3 0 ,0 07 3 0 ,0 06 6 0 ,0 05 1 0 ,0 04 4 0 ,0 03 7 0 ,0 03 3 0 ,0 02 7 0 ,0 02 5 0 ,0 02 2

    Queda de tenso - cos=0,92 V/ 10 0m .A * 0 ,0 12 9 0 , 00 99 0 ,0 08 1 0 ,0 07 2 0 ,0 06 5 0 ,0 05 0 0 ,0 04 3 0 ,0 03 6 0 ,0 03 2 0 ,0 02 7 0 ,0 02 5 0 ,0 02 1

    Queda de tenso - cos=1 V /1 00 m. A* 0 ,0 09 8 0 , 00 75 0 , 00 62 0 ,0 05 5 0 ,0 04 9 0 ,0 03 8 0 ,0 03 3 0 ,0 02 7 0 ,0 02 5 0 ,0 02 0 0 ,0 01 9 0 ,0 01 6

    Peso - TRI+N+T (T = Carcaa) kg/m 16,1 18,2 22,6 23,9 25,7 30,1 34,8 37,5 43,9 47,5 52,2 57,2

    Peso - TRI+T (T = Carcaa) kg/m 14,5 16,2 20,1 21,1 22,6 26,0 30,1 31,9 37,7 40,0 44,1 47,8

    Grau de proteo IEC-60529 IP 31

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada

    Dados Tcnicos

    M OD ELO BV CP 10 0 BV CP 12 5 B VC P1 60 B VC P1 75 B VC P20 0 BV CP 25 0 BV CP3 00 BV CP 350 B VC P4 00 BV CP 45 0 B VC P5 00 BV CP 60 0

    Corrente Nominal A 1000 1250 1600 1750 2000 2500 3000 3500 4000 4500 5000 6000

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    Dimenses do I nvlucro (Ax L) mm 1 05 x1 70 1 25 x1 70 1 4 5x 17 0 1 65 x1 70 1 05 x 27 0 1 25 x2 70 1 45 x2 70 1 65 x2 70 1 25 x3 70 1 45 x3 70 1 25 x4 70 1 45 x4 70

    Material do Invlucro Ao galvanizado

    Material do Condutor Cobre

    Supercie do Condutor Natural

    Condutores por Fase / Neutro 1 1 1 1 2 2 2 2 3 3 4 4

    Corrente de curto circuito-Crista kA 79,8 94,5 105 127,6 143 151,8 176 217,8 257,4 316,8 358,6 363

    Corrente de curto circuito-Ecaz kA 38 45 50 58 65 69 80 99 117 144 163 165

    Resistncia por fase (20C) R20 m/m 0 ,0 388 0, 033 9 0 ,02 70 0, 0245 0, 022 7 0 ,0169 0, 0135 0, 011 2 0,0 100 0, 0090 0 ,00 75 0,0 061

    Resistncia por fase In R1 m/m 0 ,0 448 0, 039 1 0 ,03 12 0, 0283 0, 026 2 0 ,0195 0, 0156 0, 013 0 0,0 116 0, 0104 0 ,00 87 0,0 071

    Reatncia por fase X1 m/m 0 ,0 457 0, 039 9 0 ,03 18 0, 0289 0, 026 7 0 ,0199 0, 0159 0, 013 2 0,0 118 0, 0106 0 ,00 88 0,0 072

    Impedncia por fase Z1 m/m 0 ,0 640 0, 055 8 0 ,04 45 0, 0404 0, 037 4 0 ,0279 0, 0223 0, 018 5 0,0 165 0, 0148 0 ,01 24 0,0 101

    Queda de tenso - cos=0,7 V /1 00 m. A* 0 ,0 11 1 0 , 00 97 0 , 00 77 0 ,0 07 0 0 ,0 06 5 0 , 00 48 0 ,0 03 9 0 ,0 03 2 0 ,0 02 9 0 ,0 02 6 0 ,0 02 1 0 ,0 01 7

    Queda de tenso - cos=0,8 V /1 00 m. A* 0 ,0 10 9 0 , 00 96 0 , 00 76 0 ,0 06 9 0 ,0 06 4 0 , 00 48 0 ,0 03 8 0 ,0 03 2 0 ,0 02 8 0 ,0 02 5 0 ,0 02 1 0 ,0 01 7

    Queda de tenso - cos=0,9 V /1 00 m. A* 0 ,0 10 4 0 , 00 91 0 , 00 73 0 ,0 06 6 0 ,0 06 1 0 , 00 46 0 ,0 03 6 0 ,0 03 0 0 ,0 02 7 0 ,0 02 4 0 ,0 02 0 0 ,0 01 6

    Queda de tenso - cos=0,92 V/ 10 0m .A * 0 ,0 10 2 0 , 00 89 0 , 00 71 0 ,0 06 5 0 ,0 06 0 0 , 00 45 0 ,0 03 6 0 ,0 03 0 0 ,0 02 6 0 ,0 02 4 0 ,0 02 0 0 ,0 01 6

    Queda de tenso - cos=1,0 V /1 00 m. A* 0 ,0 07 8 0 , 00 68 0 , 00 54 0 ,0 04 9 0 ,0 04 5 0 , 00 34 0 ,0 02 7 0 ,0 02 2 0 ,0 02 0 0 ,0 01 8 0 ,0 01 5 0 ,0 01 2

    Peso - TRI+N+T (T = Carcaa) k g/m 22,5 26,2 30,9 32,9 38,4 45,3 54,2 61,8 70,6 77,5 91,8 108,3

    Peso - TRI+T (T = Carcaa) kg/m 21,4 25,0 29,3 31,2 36,5 42,8 51,1 58,1 66,4 72,8 86,2 101,4

    Grau de proteo IEC-60529 IP 31

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada

    Projetado para transporte e distribuio de mdias e grandes potncias, ele possuiinvlucro ventilado construdo em chapa de ao galvanizado tambm utilizada comoproteo terra.

    Suas barras condutoras, em alumnio ou cobre eletroltico, so prensadas porisoladores de alta resistncia a esforos mecnicos e de curto-circuito, alm deserem no higroscpicos.

    Com o seu grau de proteo IP-31, ele protegido contra objetos slidos maioresque 2,5mm e tambm contra quedas eventuais de gotas dgua.

    Esse produto, quando designado para a distribuio de energia, possui janelas dederivao a cada 500mm para o acoplamento de cofres tipo plug-in. Sua construopadro j dispem de dispositivo para lacre que impede o acesso s barras condutoras.

    BVAP / BVCPBarramento Ventilado -1000A AT 6000A

    * fotograa meramente ilustrativa

  • 7/24/2019 1441307192

    6/11

    1110

    Projetado para mdias e grandes potncias, mais compacto e proporciona menor queda detenso quando comparado com outros modelos de mesmo calibre.

    Possui dimenses reduzidas para ocupar menos espao dentro do shaft. Com grau de proteoIP52/54, destinado distribuio e ao transporte de energia nas instalaes prediais ecomerciais com calibres de 1000A at 6000A.

    Com barras condutoras, em alumnio ou cobre eletroltico, so prensadas por isoladores dealta resistncia a esforos mecnicos e de curto-circuito, alm de serem no higroscpicos.Possui derivaes do tipo plug-in de at 630A que permitem a montagem dos diversossistemas de proteo (disjuntores, seccionadores, fusveis).

    BCAP / BCCPBarramento Compacto -1000A AT 6000A

    Dados Tcnicos

    M OD EL O B CA P1 00 BC AP 12 5 B CA P1 60 B CA P1 75 B CA P2 00 BC AP 25 0 BC AP 30 0 B CA P3 50 B CA P4 00 B CA P5 00 B CA P6 00

    Corrente Nominal A 1000 1250 1600 1750 2000 2500 3000 3500 4000 5000 6000

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    D im en s es d o I nv l ucro (Ax L) m m 129x 130 149x130 212x130 232x130 272x130 345x130 405x130 464x 130 544x130 690x130 810x 130

    Material do Invlucro Ao galvanizado

    Material do Condutor Alumnio

    Supercie do Condutor Estanhado

    Condutores por Fase / Neutro 1 1 2 2 2 3 3 4 4 6 6

    Corrente de curto circuito- Crista kA 10 5 1 36,4 149 ,6 16 2,8 1 76 1 84,8 1 98 211 ,2 22 6,6 2 53 261,8

    Corrente de curto circuito-Ecaz kA 50 62 68 74 80 84 90 96 103 115 119

    Resistncia por fase (20C) R20 m/m 0 ,0 40 7 0 ,0 34 9 0 ,0 24 5 0 ,0 22 2 0 ,0 18 8 0 , 01 48 0 ,0 12 5 0 ,0 11 1 0 ,0 09 4 0 ,0 07 4 0 ,0 06 3

    Resistncia por fase In R1 m/m 0 ,0 47 1 0 ,0 40 3 0 ,0 28 3 0 ,0 25 7 0 ,0 21 7 0 , 01 71 0 ,0 14 5 0 ,0 12 9 0 ,0 10 9 0 ,0 08 6 0 ,0 07 2Reatncia por fase X1 m/m 0 ,0 48 0 0 ,0 41 1 0 ,0 28 9 0 ,0 26 2 0 ,0 22 1 0 , 01 74 0 ,0 14 8 0 ,0 13 1 0 ,0 11 1 0 ,0 08 7 0 ,0 07 4

    Impedncia por fase Z1 m/m 0 ,0 67 3 0 ,0 57 6 0 ,0 40 4 0 ,0 36 7 0 ,0 31 0 0 , 02 44 0 ,0 20 7 0 ,0 18 4 0 ,0 15 5 0 ,0 12 2 0 ,0 10 3

    Queda de tenso - cos=0,7 V/ 10 0m .A * 0 ,0 11 6 0 ,0 10 0 0 ,0 07 0 0 ,0 06 4 0 ,0 05 4 0 ,0 04 2 0 ,0 03 6 0 ,0 03 2 0 ,0 02 7 0 ,0 02 1 0 ,0 01 8

    Queda de tenso - cos=0,8 V/ 10 0m .A * 0 ,0 11 5 0 ,0 09 9 0 ,0 06 9 0 ,0 06 3 0 ,0 05 3 0 ,0 04 2 0 ,0 03 5 0 ,0 03 1 0 ,0 02 7 0 ,0 02 1 0 ,0 01 8

    Queda de tenso - cos=0,9 V/ 10 0m .A * 0 ,0 11 0 0 ,0 09 4 0 ,0 06 6 0 ,0 06 0 0 ,0 05 1 0 ,0 04 0 0 ,0 03 4 0 ,0 03 0 0 ,0 02 5 0 ,0 02 0 0 ,0 01 7

    Queda de tenso - cos=0,92 V/ 10 0m .A * 0 ,0 10 8 0 ,0 09 2 0 ,0 06 5 0 ,0 05 9 0 ,0 05 0 0 ,0 03 9 0 ,0 03 3 0 ,0 02 9 0 ,0 02 5 0 ,0 02 0 0 ,0 01 7

    Queda de tenso - cos=1 V/ 10 0m .A * 0 ,0 08 2 0 ,0 07 0 0 , 00 49 0 ,0 04 5 0 ,0 03 8 0 ,0 03 0 0 ,0 02 5 0 ,0 02 2 0 ,0 01 9 0 ,0 01 5 0 ,0 01 3

    Peso - TRI+N+T (T = Carcaa) k g/m 17,6 19,7 25,7 26,9 30,1 36,6 39,0 53,8 60,2 73,2 78,0

    Peso - TRI+T (T = Carcaa) kg/m 15,7 17,5 22,6 23,5 26,0 31,4 32,9 46,9 52,1 62,9 65,8

    Grau de proteo IEC-60529 IP 52 / 54

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada

    Dados Tcnicos

    M OD EL O B CC P1 00 BC CP 12 5 B CC P1 60 B CC P1 75 B CC P2 00 BC CP 25 0 BC CP 30 0 B CC P3 50 B CC P4 00 B CC P5 00 B CC P6 00

    Corrente Nominal A 1000 1250 1600 1750 2000 2500 3000 3500 4000 5000 6000

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    D im en s es d o I nv l ucro (A xL) m m 99x130 119x 130 149x130 172x130 192x 130 252x 130 312x130 344x130 384x 130 504x 130 624x 130

    Material do Invlucro Ao galvanizado

    Material do Condutor CobreSupercie do Condutor Natural

    Condutores por Fase / Neutro 1 1 1 2 2 2 2 4 4 4 4

    Corrente de curto circuito-Crista kA 77,7 105 116,6 121 132 178,2 187 211,2 264 354,2 374

    Corrente de curto circuito-Ecaz kA 37 50 53 55 60 81 85 96 120 161 170

    Resistncia por fase (20C) R20 m/m 0 ,0 30 1 0 ,0 24 5 0 ,0 19 2 0 ,0 16 9 0 ,0 15 0 0 , 01 12 0 ,0 09 0 0 ,0 08 5 0 ,0 07 5 0 ,0 05 6 0 ,0 04 5

    Resistncia por fase In R1 m/m 0 ,0 34 7 0 ,0 28 3 0 ,0 22 2 0 ,0 19 5 0 ,0 17 3 0 , 01 30 0 ,0 10 3 0 ,0 09 8 0 ,0 08 7 0 ,0 06 5 0 ,0 05 2

    Reatncia por fase X1 m/m 0 ,0 35 4 0 ,0 28 9 0 ,0 22 6 0 ,0 19 9 0 ,0 17 7 0 , 01 32 0 ,0 10 5 0 ,0 10 0 0 ,0 08 8 0 ,0 06 6 0 ,0 05 3

    Impedncia por fase Z1 m/m 0 ,0 49 5 0 ,0 40 4 0 ,0 31 7 0 ,0 27 9 0 ,0 24 8 0 , 01 85 0 ,0 14 8 0 ,0 14 0 0 ,0 12 4 0 ,0 09 3 0 ,0 07 4

    Queda de tenso - cos=0,7 V/ 10 0m. A* 0 ,0 08 6 0 ,0 07 0 0 , 00 55 0 ,0 04 8 0 ,0 04 3 0 ,0 03 2 0 ,0 02 6 0 ,0 02 4 0 ,0 02 1 0 ,0 01 6 0 ,0 01 3

    Queda de tenso - cos=0,8 V/ 10 0m. A* 0 ,0 08 5 0 ,0 06 9 0 , 00 54 0 ,0 04 8 0 ,0 04 2 0 ,0 03 2 0 ,0 02 5 0 ,0 02 4 0 ,0 02 1 0 ,0 01 6 0 ,0 01 3

    Queda de tenso - cos=0,9 V/ 10 0m. A* 0 ,0 08 1 0 ,0 06 6 0 , 00 52 0 ,0 04 6 0 ,0 04 0 0 ,0 03 0 0 ,0 02 4 0 ,0 02 3 0 ,0 02 0 0 ,0 01 5 0 ,0 01 2

    Queda de tenso - cos=0,92 V /1 00 m. A* 0 ,0 07 9 0 ,0 06 5 0 , 00 51 0 ,0 04 5 0 ,0 04 0 0 ,0 03 0 0 ,0 02 4 0 ,0 02 2 0 ,0 02 0 0 ,0 01 5 0 ,0 01 2

    Queda de tenso - cos=1,0 V/ 10 0m. A* 0 ,0 06 0 0 ,0 04 9 0 , 00 38 0 ,0 03 4 0 ,0 03 0 0 ,0 02 2 0 ,0 01 8 0 ,0 01 7 0 ,0 01 5 0 ,0 01 1 0 ,0 00 9

    Peso - TRI+N+T (T = Carcaa) kg/m 28,2 32,9 40,4 45,3 44,4 61,8 89,5 90,6 88,8 123,6 179,0

    Peso - TRI+T (T = Carcaa) kg/m 26,8 31,2 38,2 42,8 41,6 58,1 84,8 85,6 83,2 116,1 169,6

    Grau de proteo IEC-60529 IP 52 / 54

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada

    * fotograa meramente ilustrativa

  • 7/24/2019 1441307192

    7/11

    1312

    Dados Tcnicos

    M OD EL O B RC P1 00 BR CP 12 5 B RC P1 60 B RC P1 75 B RC P2 00 BR CP 25 0 B RC P3 00 B RC P3 50 B RC P4 00

    Corrente Nominal A 1000 1250 1600 1750 2000 2500 3000 3500 4000

    Tenso Nominal de Isolao V 750

    Frequncia Hz 50 / 60

    Temperatura ambiente C 35

    Dimenses do Invlucro (AxL) mm 140x130 160x130 190x130 225x130 150x310 180x310 200x310 180x490 200x490

    Material do Invlucro Resina Poliester

    Material do Condutor Cobre

    Supercie do Condutor Natural

    Condutores por Fase / Neutro 1 1 1 2 2 2 2 3 3

    Corrente de curto circuito-Crista kA 77,7 105 116,6 121 132 178,2 187 211,2 264

    Corrente de curto circuito-Ecaz kA 37 50 53 55 60 81 85 96 120

    Resistncia por fase (20C) R20 m/m 0 ,0 30 1 0 ,0 245 0, 01 92 0 ,0 169 0 ,0 135 0 ,0 10 4 0 ,0 090 0 ,0 069 0 ,0 060

    Resistncia por fase In R1 m/m 0 ,0 34 7 0 ,0 283 0, 02 22 0 ,0 19 5 0 ,0 156 0 ,0 119 0 ,0 103 0 ,0 080 0 ,0 069

    Reatncia por fase X1 m/m 0 ,0 35 4 0 ,0 28 9 0 ,0 22 6 0 ,0 19 9 0 ,0 15 9 0 ,0 12 2 0 ,0 10 5 0 ,0 08 1 0 ,0 07 0

    Impedncia por fase Z1 m/m 0 ,0 49 5 0 ,0 40 4 0 ,0 31 7 0 ,0 27 9 0 ,0 22 3 0 ,0 17 1 0 ,0 14 8 0 ,0 11 4 0 ,0 09 8

    Queda de tenso - cos=0,7 V/ 10 0m .A * 0 , 00 86 0 ,0 07 0 0 ,0 05 5 0 ,0 04 8 0 ,0 03 9 0 ,0 03 0 0 ,0 02 6 0 ,0 02 0 0 ,0 01 7

    Queda de tenso - cos=0,8 V/ 10 0m .A * 0 ,0 08 5 0 ,0 06 9 0 ,0 05 4 0 ,0 04 8 0 ,0 03 8 0 ,0 02 9 0 ,0 02 5 0 ,0 01 9 0 ,0 01 7

    Queda de tenso - cos=0,9 V/ 10 0m .A * 0 ,0 08 1 0 ,0 06 6 0 ,0 05 2 0 ,0 04 6 0 ,0 03 6 0 ,0 02 8 0 ,0 02 4 0 ,0 01 9 0 ,0 01 6

    Queda de tenso - cos=0,92 V /1 00 m. A* 0 ,0 07 9 0 ,0 06 5 0 ,0 05 1 0 ,0 04 5 0 ,0 03 6 0 ,0 02 7 0 ,0 02 4 0 ,0 01 8 0 ,0 01 6

    Queda de tenso - cos=1,0 V/ 10 0m .A * 0 ,0 06 0 0 ,0 04 9 0 ,0 03 8 0 ,0 03 4 0 ,0 02 7 0 ,0 02 1 0 ,0 01 8 0 ,0 01 4 0 ,0 01 2

    Peso - TRI+N+T (T = Carcaa) kg/m 44,1 52,7 63,2 67,9 96,8 114,0 135,7 90,6 88,8

    Peso - TRI+T (T = Carcaa) kg/m 42,7 51,0 61,0 65,4 93,7 109,9 131,0 84,5 81,8

    Grau de proteo IEC-60529 IP 66

    Norma de Construo ABNT / IEC 60439-1/2

    * carga concentrada

    Desenvolvido para atender ambientes agressivos, como reas martimas e fbricas qumicas,o barramento resinado possui corpo em resina polister que atende o grau de proteo IP66que totalmente protegido contra poeira e gua e no absorve umidades.

    Suas barras condutoras em cobre eletroltico so isoladas por lme de polister, classe B130Cpor toda sua extenso.

    * fotograa meramente ilustrativa

    BRCP - Barramento Resinado - 1000A AT 4000A

    Os cofres de derivao Plug-in possibilitam ao instalador colocar ou retirar as derivaesde linha sem a necessidade do desligamento total ou parcial do sistema.

    Atravs de um conjunto de pinas utilizados na construo dos cofres, garantimos totalsegurana ao operador. Este sistema impede possveis acidentes com toques nointencionais.

    Os cofres de derivao podem ser equipados com vrios tipos de dispositivos de

    proteo como: bases fusveis NH, disjuntores ou chaves seccionadoras, com ou sembase de fusveis incorporados.

    Cofre Plug-inBase NH

    Cofre Plug-inDisjuntor

    Cofre Plug-inChave Seccionadora

    O Barramento Blindado PRODESMEC fabricado conforme a norma IEC-60529. Estanorma xa as condies exigveis para os invlucros de equipamentos eltricos quedevem oferecer um determinado grau de proteo, tanto para o equipamento como

    para as pessoas. A designao para indicar o grau de proteo constituda pelasletras IP seguidas de dois nmeros (os numerais caractersticos). Vide tabela abaixo.

    Exemplo de designao - IP31

    Cofre de derivao Plug-in

    Grau de proteo do invlucro

  • 7/24/2019 1441307192

    8/11

    1514

    Peas e Acessrios para Barramento Blindado

    Flange

    Utilizado para o perfeito acoplamento a painis,transformadores e geradores.

    Elemento RetoTrecho reto de 500 a 3000mm utilizado para otransporte e/ou distribuio.

    Cotovelo

    Fabricados nas dimenses necessrias, utilizado para odesvio de percursos nos sentidos verticais ou horizontais.

    Alimentao de cabos

    Utilizadas para a entrada ou sada de energia da linhapor cabos, podem tambm ser compostas por base NH,disjuntor e chaves seccionadoras.

    Elemento T

    Possibilita a derivao em dois sentidos simultneos,partindo de uma linha principal.

    Elemento Z

    Basicamente utilizado para o desvio de interfernciaao longo do trecho nos sentidos verticais e horizontais.

    TENSO NOMINAL VNVn 1000V - 50 / 60Hz

    CORRENTE NOMINAL (A)

    IN = Pinst .Fd .1000 ________________ 3 . Vn . cos

    QUEDA DE TENSO AVV = In . . (R1 . cos ) + X1 . sen). 3FRMULA SIMPLIFICADA:v =In . . k

    Onde:V = Queda de tenso no trecho considerado em (mV);In = Corrente passante em cada trecho, em Ampres; = Comprimento do trecho considerado, em metros;R1 = Resistncia por fase (IN), em (m/m) *;x1 = Reatncia por fase (m/m) *;cos = Fator de potncia.k = fator de queda de tenso*.* vide tabelas de dados tcnicos de cada produto.

    Onde:In = Corrente nominal em Ampres;Pinst = Potncia instalada (kW);Fd = Fator de demanda;Vn = Tenso nominal (V);cos = Fator de potncia.

    Critrios de Barramento Blindado

    Fator de correo da corrente nominal em funo da temperatura ambiente

    Temperatura ambiente mdia (C) 15 20 25 30 35 40 45 50 55 60 65

    Fator de correo 1,16 1,11 1,07 1,03 1,00 0,96 0,92 0,87 0,81 0,75 0,69

    RESISTNCIA S SOLICITAES DE CURTO CIRCUITO

    ICC= Zt= Vn______

    3 .ZT

    e, Z% .(VN)________

    PT .1000

    Onde:Icc = Corrente de curto circuito simtrico e equilibrado (kA);Vn = Tenso entre fases do Barramento Blindado, em volts;Zt = Impedncia do transformador ();Z% = Impedncia percentual;Pt = Potncia do transformador (kVA).

    O Barramento Blindado PRODESMECoferece diversas vantagens na sua instalao em comparaocom o sistema convencional que a utilizao de cabos. Logo abaixo podemos citar algumas dessasvantagens.

    Vantagens para utilizao do Barramento Blindado

    BARRAMENTO BLINDADO CABOS

    Flexibilidade para fazer novas derivaes para mquinas, equipamentos emudanas de layout, demonstrando, montando e reaproveitando os mdulos.

    Rigidez no acrscimo de novas cargas e problemca adaptaoa mudanas de layout.

    Sendo pr-fabricado, ele agiliza e diminui custos de instalao. Instalao bem lenta, que a cada emenda ou derivao necessrio ouso terminaes e caixa de passagem.

    Reduz, minimiza e at exngue a necessidade de ulizao de painis eltricos. Obrigatrio o uso de painis eltricos para distribuioe proteo dos circuitos.

    Seus componentes construvos propiciam uma excepcional vida l. Sua vida l e deteminada pelo material isolante ulizado na sua fabricao.

    Sistema de alta conabilidade e robustez. Bem menos resistente perante uma atuao de curto-circuito ousobrecorrente.

    Instalao simples, de fcil idencao visual, colaborando com umambiente limpo e organizado.

    Grande diculdade de idencar visualmente os circuitos.

  • 7/24/2019 1441307192

    9/11

    1716

    1 - Considerando que as duas extremidades da linha j contenham algum tipo de bloqueio, ex:ange, caixa de cabos, cotovelos, etc...1.1 - Em um comprimento inferior a 20 metros desnecessria a utilizao de elemento de dilatao.

    1.2 - Comprimento compreendido entre 20 e 50 metros, necessria a utilizao de umelemento de dilatao no centro da linha.

    1.3 - Comprimentos superiores a 50 metros, dividir a linha em trechos iguais de comprimentosinferiores a 50 metros utilizando um elemento de bloqueio entre os trechos e incluir umelemento de dilatao no centro de cada linha.

    Critrios para utilizao de elementos de Dilatao e Bloqueio

    2 - Considerando que apenas um lado da linha esteja bloqueada por algum elemento, ex:ange, caixa de cabos, cotovelos, etc...2.1 - Em um comprimento inferior a 30 metros no necessria a utilizao de elemento de dilatao.

    2.2 - Comprimentos compreendidos entre 30 e 50 metros, deve-se utilizar um elemento dedilatao e outro elemento de bloqueio dividindo a linha em trs trechos iguais.

    2.3 - Em comprimentos superiores a 75 metros, deve-se repetir o esquema acima quantasvezes forem necessrias.

    L < 20m

    20m < L < 50m

    DL

    L < 50m

    DL DLBQ

    L < 50m

    L < 50m

    L < 30m

    DL BQ

    =

    30m < L < 75m

    = =

    DL DLBQ

    =

    BQ

    L < 75m

    = == =

    Barras Condutoras

    O cliente pode solicitar tratamentos especiais nas barras condutoras, como conexesprateadas ou estanhadas;

    Caso haja necessidade, poder ser includa uma Barra Terra (Pe) 50% ou 100%adicional igual fase (sob consulta).

    Prumadas e Percursos Horizontais.O cliente pode solicitar a utilizao de Elementos Corta-fogo para impedir a propagaode chama, gases ou fumaas para outro pavimento ou entre ambientes. Tambmpodem ser acrescentados fechamentos (Chapa Passa-Teto ou Passa-Muro) para cadapavimento ou entre ambientes, assim efetuando o fechamento total da abertura criadapara a passagem do Barramento Blindado.

    Invlucro, Pintura e Acabamento.

    Sob encomenda podemos fabricar o invlucro do barramento blindado com chapas deespessuras superiores s utilizadas no produto convencional. O cliente pode solicitartratamentos especiais no invlucro do barramento, como pinturas executadas peloprocesso eletrosttico a p com tinta a base de epxi ou polister.

    Grau de Proteo

    Podemos aumentar o grau de proteo do barramento blindado acima do mencionado

    nas tabelas de dados tcnicos de cada produto. Consulte nosso departamento deengenharia.

    OBS.:Para os fornecimentos mencionados acima necessrio o envio da documentao ou especicao

    tcnica junto com a solicitao de oramento, para que possamos prever custos e possibilidade de

    fornecimento.

    Solicitaes Especiais

  • 7/24/2019 1441307192

    10/11

    1918

    ABNT NBR IEC 60439-1- Conjuntos de manobra e controle de baixa tenso.Parte 1: Conjuntos com ensaios de tipo totalmente testados (TTA) e conjuntos com ensaios detipo parcialmente testados (PTTA).

    ABNT NBR IEC 60439-2 - Conjuntos de manobra e controle de baixa tenso.Parte 2: Requisitos particulares para linhas eltricas pr-fabricadas (sistemas de barramentos

    blindados).

    ABNT NBR IEC 60529 - Graus de proteo para invlucro de equipamentos eltricos.

    ABNT NBR 16019- Linhas eltricas pr-fabricadas (barramentos blindados) de baixa tenso- Requisitos para instalao.

    Normas de Fabricao e Testes

    CERTIFICADONBR ISO 9001:2008

  • 7/24/2019 1441307192

    11/11

    (11) [email protected]

    Rua Tiguassu, 281/301 - Jd. Inamar - Diadema / SP - 09970-310