      HIMA Training HIMax or HIMatrix with RIO

    Page 2/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    1 Hardware Editor

    Open the Hardware editor of that resource to which you like to add a Remote I/O (RIO).

    Drag selected RIO type to the HW-Editor.

    Fig. 1.1: Inserting a RIO

    Open detail-view (Double-click to RIO) and enter a Name, Rack-ID (>=200), parameters.

    Fig. 1.2: RIO properties and System variables of the RIO

  • 8/16/2019 11 Silworx Rio e 06 Sw

    3/14

      HIMA Training HIMax or HIMatrix with RIO

    07-SILworX-RIO_E_06-SW.doc SILworX Page 3/14

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    Check the communication parameters for the “Config-Server” settings:

    Minimum values for the parameters:

    Timeout: 20.000ms

    Resend Time: 5.000ms Alive Interval: 2.500ms

    Note:

    The “Config-Server” is responsible for configuration, transmitting diagnose/status informationand also for commands.These tasks are actually not time critical. The recommended settings ensure well working

    communication even in huge systems with a big number of RIO’s.

    Basic function:The “Config-Server” on the CPU module addresses all RIO periodically (if no other config-

    data telegrams are active) in a time interval according the “Alive Interval”.If there is no valid reaction coming from the RIO a resend happens after the “Resend Time”Reaction from the RIO is expected within “Timeout”

    Minimum moni tor the Temperature state

    Open the detail-view of CPU (Double-click) and enter the IP Address:

    Fig. 1.3: IP-Settings

  • 8/16/2019 11 Silworx Rio e 06 Sw

    4/14

      HIMA Training HIMax or HIMatrix with RIO

    Page 4/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

     Assign variables to hardware:

    Double-click to a module in the RIO and drag the variables into the table.

    Fig. 1.4: Variable assignment

    2 Safeethernet settings

    In safeethernet Editor automatically appears a new link to the RIO.

    Fig. 2.1: Safeetherneteditor  

    Check the settings according communication manual:

    Fig. 2.2: Timeouts

  • 8/16/2019 11 Silworx Rio e 06 Sw

    5/14

      HIMA Training HIMax or HIMatrix with RIO

    07-SILworX-RIO_E_06-SW.doc SILworX Page 5/14

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    3 RIO Time synchronization over SNTP

    The RIO is synchronized over SNTP.In case the parent resource is a HIMax or HIMatrix 03 (enhanced performance), a SNTPServer must be created.In case the parent resource is a HIMatrix (standard), it only must be created if in this resource

    is also a SNTP client defined.

    Create a new Protocol, SNTP Server

    Fig. 3.1: Creating SNTP Server

    Set the properties of the SNTP Server.

    Select the module where the RIO is physically connected to.

    Fig. 3.2: Assigning a COM or CPU-module to the protocol

    For HIMax/HIMatr ix time synchronization over SNTP from PC please see the manual:

    “ SILworX-SNTP”

    Start the code generator of the resource. Do this two times, compare the two results.

     And if the CRC values of both runs are equal you can load the resource configuration into theresource.

  • 8/16/2019 11 Silworx Rio e 06 Sw

    6/14

      HIMA Training HIMax or HIMatrix with RIO

    Page 6/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    4 Start-up of the RIO

    Establish a direct connection between RIO and PC.

    Do a right mouse click on the element Hardware in the resource structure and select the

    function Online.

    Fig. 4.1: Hardware -> Online

    Click on the button ->to Module Login.

    Fig. 4.2: Module login

    Make a right mouse click on the CPU of the RIO and click on the function Detail View in theCPU context menu.

    Fig. 4.3: Detail view of the RIO CPU

  • 8/16/2019 11 Silworx Rio e 06 Sw

    7/14

      HIMA Training HIMax or HIMatrix with RIO

    07-SILworX-RIO_E_06-SW.doc SILworX Page 7/14

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    Now you get to the Module Login dialog.You do not really want to login, but you need this dialog to change the communicationsettings.

    For this you click on Search.

    TIP Move the now opened window a bit to the side, so that you can see the originaldata from the project.

    Type in the new window the Mac-Address and click again on Search and then on Change.

    Fig. 4.4: Search via Mac

    Change the entries for IP-Address, System ID and Rack ID according to the project data.

    Click in the field User group and activate with CTRL+A the administrator with administrator

    access.Click on Write.

    Fig. 4.5: Changing the RIO communication data

  • 8/16/2019 11 Silworx Rio e 06 Sw

    8/14

      HIMA Training HIMax or HIMatrix with RIO

    Page 8/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    For a short time the following window appears.

    Fig. 4.6: Changing message window

    Click again on Search to check if the data were really set.

    Fig. 4.7: Checking the setting of the data with Search

    Now you can click here Cancel, to get back to the original Login dialog. Don’t click  Apply.

     Activate the Administrator with Administrator access and click on Login.

    Fig. 4.8: Login dialog

    If you are able to login with the project data, the settings were done correct.You can now close the Control Panel of the RIO and connect the RIO with an Ethernet cable

    to the parent resource. After a wile the PROG LED will be activated very shortly and then the RIO will be set in thesame state like the parent resource.

  • 8/16/2019 11 Silworx Rio e 06 Sw

    9/14

      HIMA Training HIMax or HIMatrix with RIO

    07-SILworX-RIO_E_06-SW.doc SILworX Page 9/14

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    5 Diagnostic/Maintenance

    Open Hardware Online

    5.1 RIO System commands

    Context menu of RIO:

    Fig. 5.1: System Commands to a RIO

    5.2 RIO Module commands

    Double-click to the RIO CPU in order to get a Module Login for the RIO:

    Fig. 5.2: Opening Control Panel of a RIO

  • 8/16/2019 11 Silworx Rio e 06 Sw

    10/14

      HIMA Training HIMax or HIMatrix with RIO

    Page 10/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    Open detail view for advanced diagnostic:

    Fig. 5.3: Control Panel of a RIO

    Online commands:

    Fig. 5.4: Online Commands in the Control Panel of a RIO

  • 8/16/2019 11 Silworx Rio e 06 Sw

    11/14

      HIMA Training HIMax or HIMatrix with RIO

    07-SILworX-RIO_E_06-SW.doc SILworX Page 11/14

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    Diagnosis:For opening the diagnosis the Control Panel must be the active window and then you can get

    the diagnosis over the menu Online (see the screen shot above):

    Fig. 5.5: Diagnose

    5.3 Communication (safeethernet) diagnostic

    The Control Panel of the system is open.Select here the element safeethernet. Now you can see all communication partners

    according safeethernet.

    Fig. 5.6: Control Panel safeethernet

  • 8/16/2019 11 Silworx Rio e 06 Sw

    12/14

      HIMA Training HIMax or HIMatrix with RIO

    Page 12/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    Force-Editor, Inputs:The Control Panel of the system or other online access of the system is active.Now it is possible to open the Force Editor of the resource. Select the tab Inputs.

    Fig. 5.7: Force Editor Inputs

    For general diagnostic and alarming check “Connection State” and “Quality ch1”

    Communication OK “Connection State” = 2 and “Quality ch1 = 16#07

    Communication not OK “Connection State” = 1 and “Quality ch1 = 16#03

    For details see “Communication Manual”

  • 8/16/2019 11 Silworx Rio e 06 Sw

    13/14

      HIMA Training HIMax or HIMatrix with RIO

    07-SILworX-RIO_E_06-SW.doc SILworX Page 13/14

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    For alarming you can assign Global Variables to certain System Variables.Safeethernet Edit Double-click to a link System Variables

    Fig. 5.8: System variables of the safeethernet connection

  • 8/16/2019 11 Silworx Rio e 06 Sw

    14/14

      HIMA Training HIMax or HIMatrix with RIO

    Page 14/14 SILworX 07-SILworX-RIO_E_06-SW.doc

    © by HIMA Paul Hildebrandt GmbH + Co KG. Any copy, even in extracts, are prohibited unless by permission from HIMA.  

    6 Changes

    Rev.: Date/Name Text

    01 01/09 Kull Document new created. 

    02 03/09 Kull PC SNTP part moved into another document

    03 27/10/09 Kull Config-Server chapter 1

    04 26.03.2010/ML Some additional remarks for HIMatrix

    05 28.10.2010/ML Little updates

    06 29.11.2012/ML Little corrections